PRESSURES
Refrigerant Suction
CIRCUIT A _____________ PSIG
CIRCUIT B _____________ PSIG
Refrigerant Discharge
CIRCUIT A _____________ PSIG
CIRCUIT B _____________ PSIG
Verify Refrigerant Charge using Charging Charts (Y/N) _____
GENERAL
Economizer minimum vent and changeover settings to jo
b
re
q
uirements (if e
q
uipped) (Y/N) _____
Verify smoke detector unit shutdown
b
y utilizing magnet test (Y/N) _____
IV. PREMIERLINK
™
START-UP
STEPS
1. Check CTB for jumper 5, 6, 7 (Jumper 5, 6, 7 must
b
e cut and open) (Y/N) _____
2. Open humidistat contacts (Y/N) _____
3. Start unit In cooling (Close Y1) (Y/N) _____
OBSERVE AND RECORD
A. Suction pressure
_______________ PSIG
B. Discharge pressure
_______________ PSIG
C. Entering air temperature
_______________ ° F
D. Li
q
uid line temperature at outlet or reheat coil
_______________ ° F
E. Confirm correct rotation for compressor (Y/N) _____
F. Check for correct ramp-up of outdoor fan motor as condenser coil warms (Y/N) _____
4. Check unit charge per charging chart (Y/N) _____
5. Switch unit to high-latent mode (su
b
-cooler)
b
y closing humidistat with Y1 closed (Y/N) _____
OBSERVE
A. Reduction in suction pressure (5 to 7 psi expected) (Y/N) _____
B. Discharge pressure unchanged (Y/N) _____
C. Li
q
uid temperature drops to 50°F to 55°F range (Y/N) _____
D. LSV solenoid energized (valve closes) (Y/N) _____
6. Switch unit to dehumid (reheat)
b
y opening Y1 (Y/N) _____
OBSERVE
A. Suction pressure increases to normal cooling level
B. Discharge pressure decreases (35 to 50 psi)
C. Li
q
uid temperature returns to normal cooling level
D. LSV solenoid energized (valve closes)
E. DSV solenoid energized, valve opens
7. With unit in dehumid mode close W1 compressor and outdoor fan stop; LSV and DSV solenoids de-energized
(Y/N) _____
8
. Open W1 restore unit to dehumid mode (Y/N) _____
9. Open humidistat input compressor and outdoor fan stop; LSV and DSV solenoids de-energized (Y/N) _____
10. Restore set-points for thermostat and humidistat (Y/N) _____
Содержание WeatherMaster 50HCQ 04 Series
Страница 4: ...4 Fig 2 50HCQ 04 06 Units Built On and After 4 15 2019 ...
Страница 5: ...5 Fig 3 50HCQ 04 06 Units Built Prior to 4 15 2019 ...
Страница 6: ...6 Fig 4 50HCQ 04 06 Corner Weights and Clearances ...
Страница 7: ...7 Fig 5 50HCQ 04 06 Base Rail Details ...
Страница 8: ...8 Fig 6 50HCQ 04 06 Thru the Base Charts ...
Страница 23: ...23 Fig 41 Electro Mechanical Control Wiring 208 230v 460v ...
Страница 24: ...24 Fig 42 Electro Mechanical Control Wiring 575v ...
Страница 25: ...25 Fig 43 Electro Mechanical Power Wiring 208 230 1 60 ...
Страница 26: ...26 Fig 44 Electro Mechanical Power Wiring 208 230 3 60 ...
Страница 27: ...27 Fig 45 Electro Mechanical Power Wiring 460 3 60 ...
Страница 28: ...28 Fig 46 Electro Mechanical Power Wiring 575 3 60 ...
Страница 29: ...29 Fig 47 PremierLink Wiring Schematic 208 230 460v ...
Страница 30: ...30 Fig 48 PremierLink Wiring Schematic 575v ...
Страница 31: ...31 Fig 49 RTU Open System Control Wiring ...