9
Table 2 — Operating Weights
*Not available for size 11 units.
Step 2 — Plan for Sequence of Unit Installation
The support method used for this unit will dictate different se-
quences for the steps of unit installation. For example, on curb-
mounted units, some accessories must be installed on the unit be-
fore the unit is placed on the curb. See the following recom-
mended sequences for installation steps:
CURB-MOUNTED INSTALLATION
1. Install curb
2. Install field-fabricated ductwork inside curb
3. Install accessory thru-base service connection package
(affects curb and unit) (refer to accessory installation
instructions for details)
4. Prepare bottom condensate drain connection to suit
planned condensate line routing (see Step 9 for details)
5. Rig and place unit
6. Install outdoor air hood
7. Install condensate line trap and piping
8. Make electrical connections
9. Install other accessories
PAD-MOUNTED INSTALLATION
1. Prepare pad and unit supports
2. Check and tighten the bottom condensate drain connec-
tion plug
3. Rig and place unit
4. Convert unit to side duct connection arrangement
5. Install field-fabricated ductwork at unit duct openings
6. Install outdoor air hood
7. Install condensate line trap and piping
8. Make electrical connections
9. Install other accessories
FRAME-MOUNTED INSTALLATION
Frame-mounted applications generally follow the sequence for a
curb installation. Adapt as required to suit specific installation
plan.
Step 3 — Inspect Unit
Inspect unit for transportation damage. File any claim with trans-
portation agency.
Confirm before installation of unit that voltage, amperage and
circuit protection requirements listed on unit data plate agree
with power supply provided.
On units with hinged panel option, check to be sure all latches
are snug and in closed position.
Locate the carton containing the outside air hood parts; refer to
Fig. 12 on page 13. Do not remove carton until unit has been
rigged and located in final position.
Step 4 — Provide Unit Support
ROOF CURB MOUNT
Accessory roof curb details and dimensions are shown in Fig. 6
on page 10. Assemble and install accessory roof curb in accor-
dance with instructions shipped with the curb.
NOTE: The gasketing of the unit to the roof curb is critical for a
watertight seal. Install gasket supplied with the roof curb as
shown in Fig. 6 on page 10. Improperly applied gasket can also
result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to function
properly. Unit leveling tolerances are shown in Fig. 5. Refer to
Accessory Roof Curb Installation Instructions for additional in-
formation as required.
Fig. 5 — Unit Leveling Tolerances
Install insulation, cant strips, roofing felt, and counter flashing as
shown. Ductwork must be attached to curb and not to the unit.
The accessory thru-the-base power package must be installed be-
fore the unit is set on the roof curb.
If electric and control wiring is to be routed through the basepan,
attach the accessory thru-the-base service connections to the
basepan in accordance with the accessory installation
instructions.
SLAB MOUNT (HORIZONTAL UNITS ONLY)
Provide a level concrete slab that extends a minimum of 6 in.
(150 mm) beyond unit cabinet. Install a gravel apron in front of
condenser coil air inlet to prevent grass and foliage from ob-
structing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
50HC*
UNIT WEIGHT LB (KG)
07
08
09
11, 12
Base Unit
715 (324)
860 (390)
860 (390)
1025 (466)
Economizer
Vertical
75 (34)
75 (34)
75 (34)
75 (34)
Horizontal
122 (55)
122 (55)
122 (55)
122 (55)
Powered Outlet
35 (16)
35 (16)
35 (16)
35 (16)
Humidi-MiZer
®
System*
80 (36)
80 (36)
80 (36)
80 (36)
Curb
14 in. (356 mm)
143 (65)
143 (65)
143 (65)
143 (65)
24 in. (610 mm)
245 (111)
245 (111)
245 (111)
245 (111)
A-B
0.5″ (13)
B-C
1.0″ (25)
A-C
1.0″ (25)
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
Содержание WeatherMaster 50HC*A07 Series
Страница 4: ...4 Fig 2 Unit Dimensional Drawing Sizes 07 09 ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing Sizes 07 09 cont ...
Страница 6: ...6 Fig 3 Unit Dimensional Drawing Sizes 11 and 12 ...
Страница 7: ...7 Fig 3 Unit Dimensional Drawing Sizes 11 and 12 cont ...
Страница 25: ...25 Fig 42 Electro Mechanical Control Wiring Diagram ...
Страница 26: ...26 Fig 43 Electro Mechanical Control Wiring Diagram with Humidi MiZer System ...
Страница 27: ...27 Fig 44 Typical ComfortLink Control Wiring Diagram 50HC 08 09 shown ...
Страница 29: ...29 Fig 46 Typical PremierLink Control Wiring Diagram ...
Страница 30: ...30 Fig 47 Typical PremierLink Control Wiring Diagram with Humidi MiZer System Option ...
Страница 31: ...31 Fig 48 Typical RTU Open Controller Wiring Diagram ...
Страница 32: ...32 Fig 49 Typical RTU Open Controller Wiring Diagram with Humidi MiZer System Option ...