Step 13 —
Adjust Factory-Installed Options
SMOKE DETECTORS
Smoke detector(s) will be connected at the Controls Connections
Board, at terminals marked “Smoke Shutdown.” Cut jumper JMP
3 when ready to energize unit.
ECONOMI$ER IV OCCUPANCY SWITCH
Refer to Fig. 80 for general EconoMi$er IV wiring. External occu
-
pancy control is managed through a connection on the Controls
Connections Board.
If external occupancy control is desired, connect a time clock or
remotely controlled switch (closed for Occupied, open for Unoc
-
cupied sequence) at terminals marked OCCUPANCY. Cut jumper
JMP 2 to complete the installation.
Step 14 —
Install Accessories
Available accessories include:
• Roof curb
• Thru-base connection kit (must be installed before unit is
set on curb)
• LP conversion kit
• Flue discharge deflector
• Manual outside air damper
• Two-position motorized outside air damper
• EconoMi$er IV (with control)
• EconoMi$er2 (without control/for external signal)
• Power exhaust
• Differential dry-bulb sensor (EconoMi$er IV)
• Outdoor enthalpy sensor
• Differential enthalpy sensor
• CO
2
sensor
• DDC interface (PremierLink
™
controller)
• Louvered hail guard
• Motormaster
®
head pressure controls
• Phase monitor control
Refer to separate installation instructions for information on in
-
stalling these accessories.
Step 15 —
Check Belt Tension
Measure the belt span length as shown in Fig. 81. Calculate the re
-
quired deflection by multiplying the belt span length by
1
/
64
. For
example, if the belt span length is 32 inches:
32 x
1
/
64
=
1
/
2
-in. deflection.
BELT FORCE — DEFLECTION METHOD
Check the belt tension with a spring-force belt force deflection
gage (available from drive belt manufacturer).
1. Place a straightedge along the belt between the two pul
-
leys. Measure the distance between the motor shaft and the
blower shaft.
2. Set the tension gage to the desired tension (see Table 1 in
Fig. 81). Place the large O-ring at that point.
3. Press the tension checker downward on the belt until the
large O-ring is at the bottom of the straightedge.
4. Adjust the belt tension as needed.
Adjust belt tension by loosing the motor mounting plate front bolts
and rear bolt (see Fig. 82) and slide the plate towards the fan (to
reduce tension) or away from the fan (to increase tension). Ensure
the blower shaft and motor shaft are parallel to each other (pulleys
aligned). Tighten all bolts securely when finished.
Содержание WeatherMaker 48TC A/B07 Series
Страница 5: ...5 Fig 2 Dimensional Drawing for Units Built On and After 4 15 19 Size 07 ...
Страница 6: ...6 Fig 3 Dimensional Drawing for Units Built Prior To 4 15 19 Size 07 ...
Страница 7: ...7 Fig 4 Unit Corner Weights and Clearances Size 07 ...
Страница 8: ...8 Fig 5 Base Rail Details Size 07 ...
Страница 9: ...9 Fig 6 Thru the Base Charts Size 07 ...
Страница 10: ...10 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Страница 11: ...11 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Страница 12: ...12 Fig 8 Unit Dimensional Drawing Size 14 ...
Страница 13: ...13 Fig 8 Unit Dimensional Drawing Size 14 cont ...
Страница 14: ...14 Fig 9 Unit Dimensional Drawing Size 16 ...
Страница 15: ...15 Fig 9 Unit Dimensional Drawing Size 16 cont ...
Страница 20: ...20 Fig 14 48TC 16 Roof Curb Details ...
Страница 39: ...39 Fig 69 48TC 07 14 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Страница 40: ...40 Fig 70 48TC 16 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Страница 57: ...57 Fig 83 Ultra Tech Scroll Compressor Diagram ...