GUIDE SPECIFICATIONS -- 48TC**04--16
Gas Heat/Electric Cooling Packaged Rooftop
HVAC Guide Specifications
Size Range:
3 to 15 Nominal Tons
Section
Description
23 06 80
Schedules for Decentralized HVAC Equipment
23 06 80.13
Decentralized Unitary HVAC Equipment Schedule
23 06 80.13.A. Rooftop unit schedule
1. Schedule is per the project specification requirements.
23 07 16
HVAC Equipment Insulation
23 07 16.13
Decentralized, Rooftop Units:
23 07 16.13.A. Evaporator fan compartment:
1. Interior cabinet surfaces shall be insulated with a minimum 1/2--in. thick, minimum 1 1/2 lb density, flexible
fiberglass insulation bonded with a phenolic binder, neoprene coated on the air side.
2. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
23 07 16.13.B. Gas heat compartment:
1. Aluminum foil--faced fiberglass insulation shall be used.
2. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
23 09 13
Instrumentation and Control Devices for HVAC
23 09 13.23
Sensors and Transmitters
23 09 13.23.A. Thermostats
1. Thermostat must
a. energize both “W” and “G” when calling for heat.
b. have capability to energize 2 different stages of cooling, and 2 different stages of heating.
c. include capability for occupancy scheduling.
23 09 23
Direct--digital Control system for HVAC
23 09 23.13
Decentralized, Rooftop Units:
23 09 23.13.A. PremierLink controller
1. Shall be ASHRAE 62--2001 compliant.
2. Shall accept 18--32 VAC input power.
3. Shall have an operating temperature range from --40
_
F (--40
_
C) to 158
_
F (70
_
C), 10% -- 95% RH (non--condens-
ing).
4. Shall include an integrated economizer controller to support an economizer with 4 to 20 mA actuator input and
no microprocessor controller.
5. Controller shall accept the following inputs: space temperature, setpoint adjustment, outdoor air temperature,
indoor air quality, outdoor air quality, indoor relative humidity, compressor lock--out, fire shutdown, enthalpy, fan
status, remote time clock/door switch.
6. Shall accept a CO
2
sensor in the conditioned space, and be Demand Control Ventilation (DCV) ready.
7. Shall provide the following outputs: economizer, fan, cooling stage 1, cooling stage 2, heat stage 1, heat stage 2,
heat stage 3/ exhaust/ reversing valve/ dehumidify/ occupied.
8. Unit shall provide surge protection for the controller through a circuit breaker.
9. Shall be Internet capable, and communicate at a Baud rate of 38.4K or faster
10. Shall have an LED display independently showing the status of activity on the communication bus, and processor
operation.
11. Shall include an EIA--485 protocol communication port, an access port for connection of either a computer or a
Carrier technician tool, an EIA--485 port for network communication to intelligent space sensors and displays,
and a port to connect an optional LonWorks plug--in communications card.
12. Shall have built--in Carrier Comfort Network
t
(CCN) protocol, and be compatible with other CCN devices,
including ComfortLink
t
and ComfortVIEW
t
controllers.
13. Shall have built--in support for Carrier technician tool.
Содержание WeatherMaker 48TC**04
Страница 22: ...22 CURBS WEIGHTS DIMENSIONS cont C10298A Fig 5 Dimensions 48TC 08 12 ...
Страница 25: ...25 CURBS WEIGHTS DIMENSIONS cont A14149 Fig 9 Dimensions 48TC 14 ...
Страница 27: ...27 CURBS WEIGHTS DIMENSIONS cont C14151 Fig 12 Dimensions 48TC 16 ...
Страница 29: ...29 CURBS WEIGHTS DIMENSIONS cont C10772B Fig 15 Roof Curb Details 48TC 16 ...