![Carrier WeatherMaker 48TC**04 Скачать руководство пользователя страница 14](http://html.mh-extra.com/html/carrier/weathermaker-48tc-04/weathermaker-48tc-04_product-data_2560314014.webp)
14
Table 8 – PHYSICAL DATA
(HEATING)
3 -- 6 TONS
48TC**04
48TC**05
48TC**06
48TC**07
Gas Connection
# of Gas Valves
1
1
1
1
Nat. gas supply line press (in. w.g.)/ (PSIG)
4 ---13 / 0.18 --- 0.47
4 ---13 / 0.18 --- 0.47
4 ---13 / 0.18 --- 0.47
4 ---13 / 0.18 --- 0.47
LP supply line press (in. w.g.) / (PSIG)
11 ---13 / 0.40 --- 0.47
11 ---13 / 0.40 --- 0.47
11 ---13 / 0.40 --- 0.47
11 ---13 / 0.40 --- 0.47
Heat Anticipator setting (Amps)
1st stage
0.14
0.14
0.14
0.14
2nd stage
0.14
0.14
0.14
0.14
Natural Gas Heat
LO
W
# of stages / # of burners (total)
1 / 2
1 / 2
1 / 2
1 / 2
Connection Size
1/2---in NPT
1/2---in NPT
1/2---in NPT
1/2---in NPT
Rollout switch opens / closes
195 / 115
195 / 115
195 / 115
195 / 115
Temperature Rise
25 --- 55
25 --- 55
20 --- 55
15 --- 55
ME
D
# of stages / # of burners (total)
1 or 2 / 3
1 / 3
1 / 3
1 / 3
Connection Size
1/2---in NPT
1/2---in NPT
1/2---in NPT
1/2---in NPT
Rollout switch opens / closes
195 / 115
195 / 115
195 / 115
195 / 115
Temperature Rise
55 --- 85
35 --- 65
30 --- 65
25 --- 65
HI
G
H
# of stages / # of burners (total)
---
1 or 2 / 3
1 or 2 / 3
2 / 3
Connection Size
---
1/2---in NPT
1/2---in NPT
1/2---in NPT
Rollout switch opens / closes
---
195 / 115
195 / 115
195 / 115
Temperature Rise
---
50 --- 80
40 --- 80
35 --- 80
Liquid Propane Heat
LO
W
# of stages / # of burners (total)
1 / 2
1 / 2
1 / 2
1 / 2
Connection Size
1/2---in NPT
1/2---in NPT
1/2---in NPT
1/2---in NPT
Rollout switch opens / closes
195 / 115
195 / 115
195 / 115
195 / 115
Temperature Rise
25 --- 55
25 --- 55
20 --- 55
15 --- 55
ME
D
# of stages / # of burners (total)
1 or 2 / 3
1 / 3
1 / 3
1 / 3
Connection Size
1/2---in NPT
1/2---in NPT
1/2---in NPT
1/2---in NPT
Rollout switch opens / closes
195 / 115
195 / 115
195 / 115
195 / 115
Temperature Rise
55 --- 85
35 --- 65
30 --- 65
25 --- 65
HI
G
H
# of stages / # of burners (total)
---
1 or 2 / 3
1 or 2 / 3
2 / 3
Connection Size
---
1/2---in NPT
1/2---in NPT
1/2---in NPT
Rollout switch opens / closes
---
195 / 115
195 / 115
195 / 115
Temperature Rise
---
50 --- 80
40 --- 80
35 --- 80
Low NOx Gas Heat
LO
W
# of stages / # of burners (total)
1 / 2
1 / 2
1 / 2
---
Connection Size
1/2---in NPT
1/2---in NPT
1/2---in NPT
---
Rollout switch opens / closes
195 / 115
195 / 115
195 / 115
---
Temperature Rise
20 --- 50
20 --- 50
15 --- 50
---
ME
D
# of stages / # of burners (total)
1 / 3
1 / 3
1 / 3
---
Connection Size
1/2---in NPT
1/2---in NPT
1/2---in NPT
---
Rollout switch opens / closes
195 / 115
195 / 115
195 / 115
---
Temperature Rise
30 --- 60
30 --- 60
25 --- 60
---
HI
G
H
# of stages / # of burners (total)
---
1 / 3
1 / 3
---
Connection Size
---
1/2---in NPT
1/2---in NPT
---
Rollout switch opens / closes
---
195 / 115
195 / 115
---
Temperature Rise
---
40 --- 70
35 --- 70
---
--- Not applicable
Содержание WeatherMaker 48TC**04
Страница 22: ...22 CURBS WEIGHTS DIMENSIONS cont C10298A Fig 5 Dimensions 48TC 08 12 ...
Страница 25: ...25 CURBS WEIGHTS DIMENSIONS cont A14149 Fig 9 Dimensions 48TC 14 ...
Страница 27: ...27 CURBS WEIGHTS DIMENSIONS cont C14151 Fig 12 Dimensions 48TC 16 ...
Страница 29: ...29 CURBS WEIGHTS DIMENSIONS cont C10772B Fig 15 Roof Curb Details 48TC 16 ...