Troubleshooting
VVT Zone II Controller
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
62
If Run LED shows...
And Error LED shows...
Status is...
5 flashes per second
Off
Firmware transfer in progress, Boot is running
7 flashes per second
7 flashes per second,
alternating with
Run
LED
Ten second recovery period after brownout
14 flashes per second
14 flashes per second,
alternating with
Run
LED
Brownout
On
On
Failure. Try the following solutions:
•
Turn the VVT Zone II off, then on.
•
Download memory to the VVT Zone II.
•
Replace the VVT Zone II.
NOTE
If you resolve the issue but the
Error
LED does not turn off, cycle power to the controller.
To get the serial number
If you need the VVT Zone II's serial number when troubleshooting, the number is on a Module Status report
(Modstat) under
Core
(or
Main
)
board hardware
To obtain a modstat in the i-Vu® interface:
1
Select the VVT Zone II in the navigation tree.
2
Right-click and select
Module Status
.