37
Electrical
parts problem
Electrical parts/
sensors
malfunction 20%
Solution level
electrode
malfunctions 80%
High-temp.
generator
problem (16DJ)
Combustion
chamber and
smoke tube are
sooted
90%
Too much gas/oil
8%
Baffles provided in smoke tube are defective. 2%
APPENDIX 1 - TROUBLESHOOTING FLOWCHART - CONT.
(Generator alarm)
Microprocessor malfunctions.
Cam switches malfunction.
Pressure switch malfunctions.
Microprocessor solution level incorrect.
Temperature sensor malfunctions.
Electrode surface is contaminated.
Electrode is defective.
Teflon tube on electrode has been removed.
Incorrect combustion adjustment.
Blower suction is clogged
‡
air/gas/oil ratio is incorrect.
Flue is clogged
‡
air/gas/oil ratio is incorrect.
Gas pressure increases.
Incorrect gas/oil linkage adjustment.