RTU Open
49
Demand Limit
The RTU Open may employ a demand limit strategy. Demand limiting in the RTU Open works through setpoint
expansion. The controller’s heating and cooling setpoints are expanded in steps or levels. The degree to
which the setpoints are expanded is defined by the
Demand Level Setpoints
.
Each
Demand Level
(1 through 3) adjusts the heating and cooling setpoints outwards. By default,
Demand 1
yields a 1° expansion,
Demand 2
yields a 2° expansion, and
Demand 3
yields a 4° expansion.
The BACnet
Demand Limit
variable sets the desired level of setpoint expansion in the receiving controller.
Level 0
leaves the standard occupied and unoccupied heating and cooling setpoints in effect. Levels 1
through 3 expands occupied heating and cooling setpoints.
Door switch
A
Door Contact
may be configured on any unused binary input. A typical application is an occupancy sensor
mounted within the space served by a single zone rooftop.
Door Contact
disables mechanical cooling and
electric or gas heating, when active. Economizer cooling, if available, continues to operate.
Remote occupancy
Remote occupancy
may be configured on any unused binary input channel. A typical application is a remote
contact, controlled by a third party, to set the controller's occupied mode. The
Remote Occupancy
function
requires both an input configured for
Remote Occupancy
, and
Occupancy Source
set to
Remote Occ Input
to
operate.
Once configured, the controller will operate in the occupied or unoccupied mode, as determined by the state
of the
Remote Occupancy
input.
Fire Shutdown
Fire Shutdown
may be configured on Binary Input 5. A typical application involves a smoke detector or fire
shutdown contact, which, when active, immediately shuts down equipment operation.
Compressor Safety
Compressor Safety
may be configured on Binary Input 3. A compressor safety tripped indicator circuit is
available on most Carrier rooftop equipment.
A
Compressor Safety
Alarm
is shown on
Properties
page >
Equipment
tab >
Alarms
and indicates that the
equipment requires attention.