background image

PG80MSU: Installation, Start-up, Operating and Service and Maintenance Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

31

Consult your local dealer about proper frequency of maintenance and the

availability of a maintenance contract.

The minimum maintenance on this furnace is as follows: 

1. Check and clean/replace air filter each month or more frequently if

required. Replace if torn.

2. Check burner inlet elbow opening for cleanliness and any visible

debris.  Burner  assembly  removal  should  only  be  performed  for

troubleshooting  and  diagnosis  of  operational  issues.  Refer  to

troubleshooting and service guide.

3. Check  blower  motor  and  wheel  for  cleanliness  each  heating  and

cooling season. Clean as necessary.

4. Check electrical connections for tightness and controls for proper

operation each heating season. Service as necessary.

5. Inspect  the  vent pipe/vent  system before  each  heating  season  for

rust,  corrosion,  water  leakage,  sagging  pipes  or  broken  fittings.

Have vent pipes/vent system serviced by a qualified service agency.

6. Inspect any accessories attached to the furnace such as a humidifier

or electronic air cleaner. Perform any service or maintenance to the

accessories as recommended in the accessory instructions. 

Cleaning and/or Replacing Air Filter

The air filter arrangement will vary depending on the application. The

filter is exterior to the furnace casing.

NOTE: 

If the filter has an airflow direction arrow, the arrow must point

towards the blower.

Table 20 – Filter Size Information (In. / mm)

Media cabinet filter procedures: 

1. Turn off electrical supply to furnace before removing filter access

door.

2. Remove filter cabinet door.
3. Slide filter out of cabinet.
4. If equipped with permanent, washable 3/4-in. (19 mm) filter, clean

filter by spraying cold tap water through filter in opposite direction

of airflow. Rinse filter and let dry. Oiling or coating of the filter is

not recommended. See 

Table 20

 for size information. 

5. If equipped with factory-specified disposable media filter, replace

only with media filter having the same part number and size. For

expandable  replacement  media,  refer  to  the  instructions  included

with the replacement media. 

6. Slide filter into cabinet.
7. Replace filter cabinet door.
8. Turn on electrical supply to furnace. 

Blower Motor and Wheel Maintenance

NOTE: 

The blower wheel should not be dropped or bent as balance will

be  affected.  The  following  steps  should  be  performed  by  a  qualified

service agency.
To  ensure  long  life  and  high  efficiency,  clean  accumulated  dirt  and

grease from blower wheel and motor annually. 
The  inducer  and  blower  motors  are  pre-lubricated  and  require  no

additional lubrication. These motors can be identified by the absence of

oil ports on each end of the motor. 
Clean blower motor and wheel as follows: 

1. Turn off electrical supply to furnace.
2. Remove outer door.
3. Remove two screws from blower access door and remove blower

access door.

4. All  factory  wires  can  be  left  connected,  but  field  thermostat

connections may need to be disconnected depending on their length

and routing.

5. Remove two screws holding blower assembly to blower deck and

slide blower assembly out of furnace.

6. Clean  blower  wheel  and  motor  using  a  vacuum  with  soft  brush

attachment. Blower wheel blades may be cleaned with a small paint

or flux brush. Do not remove or disturb balance weights (clips) on

blower wheel blades.

7. Vacuum any loose dust from blower housing, wheel and motor.
8. If a greasy residue is present on blower wheel, remove wheel from

the blower housing and wash it with an appropriate degreaser. To

remove wheel:

NOTE: 

Before disassembly, mark blower motor, and blower housing so

motor  and  each  arm  is  positioned  at  the  same  location  during

reassembly.

a. Disconnect power choke wires (if used) and ground wire 

attached to blower housing.

b. Remove screws securing cutoff plate and remove cutoff plate 

from housing.

c. Loosen set screw holding blower wheel on motor shaft (160+/-20 

in.-lb. when reassembling).

WARNING

!

ELECTRICAL SHOCK AND FIRE HAZARD

Failure to follow this warning could result in personal injury, death or

property damage. 

Turn off the gas and electrical supplies to the unit and install lockout tag

before  performing  any  maintenance  or  service.  Follow  the  operating

instructions on the label attached to the furnace.

WARNING

!

CARBON MONOXIDE POISONING AND FIRE 

HAZARD

Failure  to  follow  this  warning  could  result  in  personal  injury,  death

and/or property damage. 

Never operate unit without a filter or with filter access door removed.

CAUTION

!

CUT HAZARD

Failure to follow this caution may result in personal injury. 
Sheet metal parts may have sharp edges or burrs. Use care and wear

appropriate  protective  clothing,  safety  glasses  and  gloves  when

handling parts and servicing furnaces.

FURNACE 

CASING 

WIDTH

In. (mm)

FILTER SIZE (In. / mm)

FILTER TYPE

Side Return

Bottom Return

17-1/2 (445)

16 X 25 X 3/4 (406 

x 635 x 19)

16 X 25 X 3/4

(406 x 635 x 19)

Washable

*

 

*. Recommended

21 (533)

16 x 25 x 3/4

(406 x 635 x 19)

20 X 25 X 3/4

(508 x 635 x 19)

Washable

*

 

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death. 

Blower  access  door  switch  opens  115-V  power  to  control.  No

component operation can occur unless switch is closed. Caution must

be taken when manually closing this switch for service purposes.

Содержание PG80MSU

Страница 1: ...NFORMATION GUIDE 40 MODEL NOMENCLATURE 40 To learn more about this appliance and installation via a mobile device go to https www payne com NFC or use the QR code below To access airflow tables or tro...

Страница 2: ...se carbon monoxide poisoning explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qualified service agency local gas supplier or your distri...

Страница 3: ...ply ducts carry air circulated by the furnace to areas outside the space containing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the...

Страница 4: ...db Failure to follow these return air temperature limits may affect reliability of heat exchangers motors and controls see Fig 4 For accessory installation details refer to the applicable instruction...

Страница 5: ...city firmly touch a clean unpainted metal surface of the furnace again before touching control or wires 5 Use this procedure for installed and uninstalled ungrounded furnaces 6 Before removing a new c...

Страница 6: ...ut rating for all gas appliances installed in the space Spaces having less than 50 cubic feet per 1 000 BTUh require the OUTDOOR COMBUSTION AIR METHOD Spaces having at least 50 cubic feet per 1 000 BT...

Страница 7: ...ss volume than 50 cubic feet per 1 000 BTUh of the maximum input ratings for all gas appliances installed in the space and 2 The air infiltration rate is not known to be less than 0 40 air changes per...

Страница 8: ...ings with unusually tight construction additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section Unusually tight construction is defined as construction...

Страница 9: ...own in Fig 13 NOTE It is required that the perforated supply air duct flanges be completely folded over or removed from furnace when installing the furnace on a factory supplied cased coil or coil box...

Страница 10: ...Protection Provide a minimum 17 3 4 in x 22 in 451 mm x 559 mm piece of sheet metal for flame roll out protection in front of burner area for furnaces closer than 12 inches 305 mm above the combustibl...

Страница 11: ...n a 1 in 25 mm clearance from combustible materials to supply air ductwork for a distance of 36 in 914 mm horizontally from the furnace See NFPA 90B or local code for further requirements Ductwork Aco...

Страница 12: ...GC Installations must be made in accordance with all authorities having jurisdiction If possible the gas supply line should be a separate line running directly from meter to furnace NOTE In the state...

Страница 13: ...and downstream of manual equipment shutoff valve A02035 Fig 22 Typical Gas Pipe Arrangement Piping should be pressure and leak tested in accordance with NFGC in the United States local and national pl...

Страница 14: ...in Step 1 5 Route J Box wires within furnace away from sharp edges rotating parts and hot surfaces WARNING ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal inju...

Страница 15: ...ket BX Cable Installation in Furnace J Box 1 Remove cover from J Box 2 Route BX cable into 7 8 inch diameter hole in J Box 3 Secure BX cable to J Box bracket with connectors approved for the type of c...

Страница 16: ...sted or draft hood equipped appliances in accordance with the NFGC the local building codes and furnace and vent manufacturers instructions The following information and warning must be considered in...

Страница 17: ...in operation Seal any unused openings in venting system Inspect the venting system for proper size and horizontal pitch as required in the current edition of National Fuel Gas Code ANSI Z223 1 NFPA 5...

Страница 18: ...condensation and corrosion in the venting system Do not use vent dampers on appliances common vented with this furnace Additional Venting Requirements A 4 101 mm round vent elbow is supplied with the...

Страница 19: ...t connector is required refer to Note 1 above 3 Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace except when factory authorized Downflo...

Страница 20: ...0 935 875 815 750 690 620 570 520 470 6 1050 995 935 880 820 755 700 645 595 550 7 1130 1075 1020 970 915 855 800 745 690 645 8 1200 1150 1100 1050 1000 945 890 840 785 735 9 1285 1240 1190 1145 1095...

Страница 21: ...315 175 3 1035 935 830 745 640 550 460 365 235 140 4 1095 1000 900 815 725 630 545 455 360 240 5 1205 1125 1035 945 870 780 695 620 540 455 6 1290 1210 1125 1040 965 890 805 725 645 570 7 1385 1310 1...

Страница 22: ...ct Super Plug available from distributor replacement component for the control board to copy the correct model program onto the new board Further details and instructions for these programming methods...

Страница 23: ...Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 23 A221015 Fig 34 3 Digit Display Flow Char...

Страница 24: ...to the gas valve if a flame rollout or overheating condition occurs in the gas control area DO NOT bypass the switches Correct inadequate combustion air supply problem before resetting the switches CA...

Страница 25: ...e unit rating plate For installation above 2 000 ft 610 M multiply the input on the rating plate by the derate multiplier in Table 14 for the correct input rate A180238 Fig 37 Orifice Hole WARNING FIR...

Страница 26: ...door switch f Set thermostat to call for heat g Remove regulator seal cap and turn regulator adjusting screw counterclockwise out to decrease input rate of clockwise in to increase input rate h Instal...

Страница 27: ...2 6 2 7 2 8 2 9 850 2 4 2 5 2 6 2 7 to 875 2 3 2 4 2 5 2 5 900 2 2 2 3 2 3 2 4 5000 925 2 1 2 1 2 2 2 3 1524 950 2 0 2 0 2 1 2 2 975 1 9 1 9 2 0 2 0 1000 1 8 1 8 1 9 1 9 U S A Only 725 3 2 3 3 3 4 3...

Страница 28: ...U S A Only 725 2 9 3 0 3 1 3 1 750 2 7 2 8 2 9 3 0 5001 775 2 5 2 6 2 7 2 8 1524 800 2 4 2 4 2 5 2 6 825 2 2 2 3 2 4 2 5 to 850 2 1 2 2 2 2 2 3 875 2 0 2 0 2 1 2 2 5400 900 1 9 1 9 2 0 2 1 1646 925 1...

Страница 29: ...failure If limit control does not function during this test cause must be determined and corrected a Run furnace for at least 5 minutes b Gradually block off return air with a piece of cardboard or sh...

Страница 30: ...es proceed with the following NOTE NO thermostat signal may be present at control and all blower OFF delays must be completed a Leave 115 V power to furnace turned on b Remove outer access door c Remo...

Страница 31: ...d dirt and grease from blower wheel and motor annually The inducer and blower motors are pre lubricated and require no additional lubrication These motors can be identified by the absence of oil ports...

Страница 32: ...eel wool 0000 grade Do not use sand paper or emery cloth To reinstall igniter and flame sensor 1 Install the Hot Surface Igniter HSI and bracket with igniter gasket into burner assembly 2 Install flam...

Страница 33: ...end of spring cable end opposite brush 2 Insert brush end of cable into the outlet opening of cell and slowly rotate with drill DO NOT force cable Gradually insert cable into upper pass of cell see Fi...

Страница 34: ...iod the control CPU will open the gas valve relay GVR de energizing the gas valve solenoid GV The control CPU will repeat the ignition sequence for up to three more Trials for Ignition before going to...

Страница 35: ...er motor BLWM operation 4 Heat pump When installed with a heat pump the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles Whenever W...

Страница 36: ...lation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 36 TROUBLESHO...

Страница 37: ...U Installation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 37 A2...

Страница 38: ...Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 38 A221105 Fig 40 T...

Страница 39: ...re only furnace is running Firing rate heat content btu cu ft X size of the dial cu ft rev X of rev per 60 sec rev sec X 3600 sec hr Example 1050 btu cu ft X 0 5 cu f t rev X 2 revs 60sec X 3600 sec h...

Страница 40: ...ll Cell panel Inducer Group Housing assembly Transducer Inducer motor Inducer wheel TO OBTAIN INFORMATION ON PARTS Consult your installing dealer or a licensed Heating and Air Conditioning company of...

Отзывы: