Carrier OMNIZONE 50XJ104 Скачать руководство пользователя страница 20

20

FIRE INPUT (FSD) — This is a normally closed input con-

nected to the controller. When this input is opened, all control

outputs are immediately turned off, including the fan.
DUCT HIGH STATIC INPUT (DHS) — This differential air

pressure switch provides backup protection for the ductwork. It

is factory installed in the unit and wired to the unit controller.

This switch has a manually adjustable set point with a range of

1 to 5 in. wg. Upon switch closure, the controller immediately

turns all outputs off, including fan, and then indicates an alarm

both by turning on its alarm output, the BACview alarm lamp

and via communications (if used).
DIRTY FILTERS SWITCH (FLTS) — This  is  a  factory-in-

stalled option on the 50XJ unit. This input is used to connect a

pressure switch that measures the air pressure difference across

the filters. When the delta increases beyond the preset setting, a

dirty filter alarm is activated, indicating that the filters need

cleaning or replacement.

The switch is normally open, with manually adjustable set-

ting at the switch between 0.5 and 1.5 in. wg. Upon closure,

controller holds the alarm for 1 minute to assure that the condi-

tion is stable and then it activates the alarm. Beyond the alarm,

the dirty filter condition does not affect controller operation, so

the unit should operate normally.
COMPRESSOR OVERLOAD (COL)/SAFETIES — Each

compressor is provided with either an internal line-break over-

current protector or an external overload protection module.

Each compressor control circuit also contains a compressor lock-

out board (CLO), high-pressure switch (HPS), low-pressure

switch (LPS), and evaporator freeze switch (FRZ). Except for

the internal line-break protection, these devices are wired in se-

ries to the contactor for each compressor. A pilot relay is wired in

parallel with the compressor contactor to determine when the

compressor contactor is energized/de-energized.

The compressor lockout board (CLO) is located in the unit

control box, wired in the control line for the compressor contac-

tor, and incorporates a current loop which monitors one leg of the

compressor power leads. This board is powered along with the

related compressor contactor.

Whenever the compressor current falls below a threshold lev-

el (i.e., compressor not operating) on an energized circuit, the

lockout board activates an on-board relay which opens power to

the compressor contactor and pilot relay.  The pilot relay contacts

signal the controller with the compressor status. If any of the

safety devices described above opens, the compressor shutdown

sequence is started. In the event this occurs, the controller should

turn off this compressor, and start the next compressor in se-

quence. After a 5-minute period, the controller should restart this

compressor, and turn the other one off, as cooling demand re-

quires. If the “problem” compressor then operates for 10 minutes

of run time normally, the unit reverts to normal operation and

compressor sequencing. If not, and the same error occurs again,

this compressor should be shut down and replaced with the next

compressor, as before, and held off for 10 minutes. It should then

be restarted and the other compressor shut down, as before. If it

does not run successfully for 10 minutes of normal run time

again, it is shut down and replaced a third time. This time it is

held off for 15 minutes. If the "problem" compressor does not

operate successfully for the 10 minutes of normal run time this

third time, this compressor ONLY is shut down and locked out

for servicing. A compressor lockout alarm is generated and the

BACview alarm lamp is turned on.
HIGH-PRESSURE SWITCH (HPS) — This switch is located

in the discharge refrigerant line of each compressor, and is set

to open at pressures above 570 psig. It is wired in the 24-vac

control power line of the compressor contactor (in series with

the LPS and FRZ) and disables compressor operation when it

opens.
LOW-PRESSURE SWITCH (LPS) —   The  low-pressure

switch (LPS) is located in the suction refrigerant line of each

compressor, and is set to open at pressures below 27 psig. The

LPS is wired in the 24-vac control power line of the

compressor contactor (in series with the HPS and FRZ) and

disables compressor operation when it opens.
EVAPORATOR FREEZE SWITCH (FRZ) — The  evaporator

freeze switch (FRZ) is a thermal disk type switch, mounted on

a return bend of the evaporator, refrigerant circuit for which

corresponds to each respective compressor, and is set to open at

temperatures below 28 F. The FRZ is wired in the 24-vac con-

trol power line of the compressor contactor (in series with the

LPS and HPS) and disables compressor operation when it

opens.
COMPRESSOR EXTERNAL OVERLOAD PROTEC-

TION MODULE — This board is provided with each com-

pressor that does not include internal line-break overload pro-

tection. When installed, this board is in the compressor termi-

nal box. This board activates at an over temperature setting,

and locks out operation of the compressor for 30 minutes; there

is no method to override or reset this timer. Due to this timing

function, please note that the compressor will not attempt to re-

start until the third attempt described above.
COMPRESSOR INTERNAL LINE-BREAK OVERLOAD

PROTECTION MODULE — Some compressors are built

with internal line-break protection. When the winding tempera-

ture exceeds the protector setting, the protector opens two of

the three power lines within the compressor. This protector

keeps the compressor locked out until the winding temperature

falls below the protectors reset temperature. There is no meth-

od to override or reset this protector, except by lowering the

winding temperature. Under some circumstances, the compres-

sor may not attempt to restart until the third attempt described

above.
ALARMS — There are four methods to annunciate alarms:

BACview alarm lamp, BACview alarm display, network com-

munications, or the discreet alarm output dry contacts. Alarms

are covered in detail in the Troubleshooting section.

TROUBLESHOOTING

Standard Diagnostic Features, Alarms and
Alarm Lamps  — 

Unit reset of alarm failure operation is

automatic when fault is cleared, except as noted. 
SUPPLY AIR TEMPERATURE ALARM — If  supply  air

temperature input falls outside the range of 25 to 150 F, the

alarm output will close and the red alarm lamp will be lit. An

alarm with an ID of "sat_alarm" will be generated, but the unit

will operate normally.
SUPPLY AIR TEMPERATURE SENSOR FAILURE —   If

the supply air temperature sensor fails the system will display a

supply-air temperature of 0.00° F, the compressor outputs will

be disabled, the alarm output will close and the red alarm lamp

will be lit. An alarm with an ID of "sat_sen_alarm" will be

generated.
DUCT STATIC PRESSURE ALARM — If  the  duct  static

pressure input falls outside the range of 0.06 to 5.45 in. wg, the

alarm output will close and the red alarm lamp will be lit. An

alarm with an ID of "dsp_alarm" will be generated, but the unit

will operate normally.
DUCT STATIC PRESSURE SENSOR FAILURE — If  the

duct static pressure sensor fails, the system will display 0.00 in.

wg, the controller outputs will be forced off, the alarm output

will close and the red alarm lamp will be lit. An alarm with an

ID of "dsp_sens_alarm" will be generated.
DUCT HIGH STATIC INPUT (DHS) —   This  factory-

installed air switch provides over pressurization protection for

the ductwork. The switch is a normally open switch, with ad-

justable manual setting (range is 1 to 5 in. wg with a default of

3.0 in. wg). Upon switch closure, the controller outputs will be

forced off, the alarm output will close and the red alarm lamp

Содержание OMNIZONE 50XJ104

Страница 1: ...n working on this equipment observe precautions in the literature on tags stickers and labels attached to the equip ment and any other safety precautions that apply Follow all safety codes Wear safety...

Страница 2: ...tion Optional and Field Installed Accessory Sensors Devices These units can be ordered with options and ac cessories that add functionality and control These options and accessories are used as descri...

Страница 3: ...og 5K Sensor IN 10 W8 Therm Dry Water Econ Freezestat Sensor or Switch FREEZE Analog 10K 2 Sensor or Switch Closure IN 11 IW7 Therm Dry configurable Mixed Return Air Temperature MA_RA Analog 10K 2 Sen...

Страница 4: ...signal 1 to 5 vdc linearly The sensor s range is 0 to 550 psig Water Valve s Control Variable Building Waterflow Systems Variable waterflow configurations use only one water valve in the main water su...

Страница 5: ...l 16 and the negative to terminal 17 SUPPLY AIR RESET BY SPACE TEMPERATURE Use a 10K type II thermistor sensor installed at the entering water temperature sensor location on PCB2 and configure the uni...

Страница 6: ...e for remote annunciation connect wiring to terminal block J10 terminal 18 normally open terminal 17 common and or terminal 16 normally closed J4 9 10 RED BLK RED RED BLK BLK BLK RED BLK RED SENSOR 1...

Страница 7: ...t digital input such as duct high limit switch When the jumper is in the top position the input is configured for a voltage input for example a humidity sensor The bottom jumper position is used for m...

Страница 8: ...50 60 Hz 20VA 0 83A Use Copper Conductors Only 232 EIA EIA 485 Port 1 Port 2a Therm Dry Unused 5 6 7 8 Network Switches 0 off 1 on MSTP m MSTP s PTP SLTA PlugIn Ethernet 8 7 6 5 Protocol 0 0 0 0 0 0...

Страница 9: ...If the standby screen is visible press any key to switch to the HOME menu 2 If another screen is displayed press the HOME to switch to the HOME menu 3 Press the LOGOUT softkey to force the system to...

Страница 10: ...ompressor start stop test This is the same test point used to test the VFD bypass Since constant volume units do not have remote VAV termi nals there is no built in delay to allow remote boxes to open...

Страница 11: ...es Local schedules are one method of starting and stopping the unit at specified intervals There are four normal schedules that provide day to day opera tion There are twelve holiday schedules that ar...

Страница 12: ...ule When an override schedule is active it overrides any nor mal or holiday schedule and forces the unit to occupied mode In the example listed under the holiday schedule assume an override schedule...

Страница 13: ...runtime limits or clear the accumulated run times To view run times press the CONFIG softkey on the HOME menu then select the RUNTIME option from the CONFIGURATION menu Use the arrow keys to scroll th...

Страница 14: ...entry press EXIT and re start the procedure at Step 6 9905 Motor Nom Volt should equal unit voltage 230V or 460V 9906 Motor Nom Current equal to motor FLA see motor nameplate 9907 Motor Nom Freq alwa...

Страница 15: ...elp screens START UP WITH ASSISTANT To start up the VFD with the Start Up Assistant perform the following proce dure 1 Select MENU SOFT KEY 2 The Main menu will be displayed 2 Use the UP or DOWN keys...

Страница 16: ...and then press EXIT SOFT KEY 1 to return to main menu NOTE The current parameter value appears above the highlight parameter To view the default parameter value press the UP and DOWN keys simultaneous...

Страница 17: ...not be changed 6 Press EXIT SOFT KEY 1 twice to return to the main menu START UP General Complete the start up checklist on page CL 1 before attempting system start up Confirm that compressor suction...

Страница 18: ...of these sensors in the custom configuration The following sensors when valid are used for the space tempera ture sensor with the highest precedence at the top of the list Space temperature sensor SPT...

Страница 19: ...e 65 F HEAD PRESSURE CONTROL HPC In installations where entering water temperature can fall below 55 F where a water economizer described above is not installed the HPC provides an electronic water fl...

Страница 20: ...of each compressor and is set to open at pressures above 570 psig It is wired in the 24 vac control power line of the compressor contactor in series with the LPS and FRZ and disables compressor operat...

Страница 21: ...he compres sor and attempt to restart it 15 minutes later assuming there is still a call for cooling On a third failed attempt to run the compressor the compressor will be locked out pending a pow er...

Страница 22: ...r control of an air economizer OUTDOOR AIR TEMPERATURE ALARM OAT If an outdoor air temperature sensor is installed and configured an alarm with an ID of oat_alarm will be generated if the temperature...

Страница 23: ...ISC1 Disconnect Switch DSP Duct Static Pressure Transducer ECONO Economizer Valve Damper Control EWT Entering Water Temperature Sensor FLTS Filter Status Switch FREEZ Freeze Thermostat Water Economize...

Страница 24: ...3 L1 T1 L2 T2 L3 T3 FU10 FU11 FU12 COMP3 151 BLK 157 BLU 154 YEL 150 BLK 156 BLU 153 YEL 149 BLK 155 BLU 152 YEL C3 158 BLK 159 BLK CH3 2 1 3 L2 T2 L3 T3 FU13 FU14 FU15 COMP4 162 BLK 168 BLU 165 YEL 1...

Страница 25: ...Z2 409 PNK 408 PNK 407 PNK 406 PNK LPS2 400 BLU 534 BLU HPS1 FRZ1 404 BLU 403 BLU 402 BLU 401 BLU LPS1 TB5 531 BRN 528 BRN 525 BRN 522 BRN 532 BRN 427 BRN 433 BRN 432 BRN 430 BRN 428 BRN 429 BRN 431 B...

Страница 26: ...tion PUMP REQUEST FIELD Connection TOWER REQUEST FIELD Connection EXT DEHUMIDIFY Tower Sump Leaving Water 627 ORN 628 BLU 629 BRN FIELD Connection TRMOP FIELD Connection VENTR FIELD Connection TRMCT F...

Страница 27: ...701 GRN 630 ORN 631 VIO HRN3 4 3 FIELD Connection Exhaust Fan DSP 640 BLK A B BPS_S 617 BRN 6 5 638 BRN 638 BRN 627 ORN 628 BLU 629 BRN 603 RED 606 BRN 639 RED 607 RED 609 RED 611 RED 613 RED FIELD A...

Страница 28: ......

Страница 29: ......

Страница 30: ...right to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500117 01 Printed in U S A Form 50XJ 2T Pg 30 8 14 Replaces 50XJ 1...

Страница 31: ...INPUT POWER PHASE SEQUENCE BEEN CONFIRMED WITH A METER Y N _______ HAS THE FAN AND MOTOR PULLEY BEEN CHECKED FOR PROPER ALIGNMENT AND DOES THE FAN BELT HAVE PROPER TENSION Y N _______ HAS WATER BEEN P...

Страница 32: ..._____________________________________________________________________________________________ _______________________________________________________________________________________________ __________...

Отзывы: