35
Fig. 21 — Fan Pulley Adjustments
Belt Tension Adjustment
Shut off unit power supply. Lock out power supply and tag discon
-
nect locations. Loosen fan motor mounting plate bolts. Do not
loosen motor mounting bracket from unit. Adjust belt tensioning
bolts until proper belt tension is obtained.
Changing Fan Wheel
If a fan wheel should fail, it may be replaced as follows:
1. Remove belts from fan pulley.
2. Loosen locking collars on the fan bearings and set screws on
the fan wheels.
3. Remove the shaft through the access panel on either side of
the unit.
4. Remove the fan cut-off plate in the fan discharge.
5. Remove the fan wheel through the fan discharge opening.
6. Replace the wheel, and reverse Steps 1-4 above.
Fan Bearing Replacement
If a fan bearing fails, replace it as follows:
1. Remove belts from the fan pulley.
2. Support fan shaft.
3. Loosen locking collar on fan bearing.
4. Remove bearing from the shaft.
5. Install new bearing onto the shaft, and reverse Steps 1-3
above.
Concentric Alignment
Shaft and wheels must be concentrically centered with the venturi
or air inlet of the fan housing (see Fig. 22).
Fig. 22 — Concentric Alignment
Shaft bearings are supports by bearing supports (Fig. 23). If shaft
and wheels are concentrically misaligned from shipping shock, it
is possible to re-bend the bearing support arms to the original posi
-
tions. Replace the bearing support if it has extensive damage.
Fig. 23 — Fan Shaft Bearings
Evaporator and Condenser Motor Starter Setting
(after Lockout/Tagout)
Motor starter is factory set. If starter is replaced in the field, use the
following procedure to set:
1. On the starter, adjust the Motor Overload to match the
FLA
Rating
of the installed motor by turning the Overload Set
-
point wheel to the appropriate value. See Fig. 24. Evaporator
and condenser motor FLA Ratings are listed in Table 21.
2. On the starter, turn the Motor Overload Reset wheel to
M-O
(referred to as Manual Reset).
3. On the starter, depress the Motor Overload Reset wheel
(wheel also acts as reset button).
4. Turn the Power Switch/Disconnect Switch of the Start/Stop
Station to the
ON
Position.