Carrier OMNIZONE 50XCA06 Скачать руководство пользователя страница 2

2

GENERAL

Omnizone™ indoor packaged units are designed to provide the

flexibility required in replacement, renovation, and new construc

-

tion. Units are available in 6 sizes from 5 tons to 20 tons. Belt-

drive  condensers  provide  adequate  static  to  overcome  normal

ducting and louver static losses. This allows units to be positioned

against an existing window or wall louver, or ducted to the outside

as required.

Convenient rear connections allow easy access for outside air con

-

nections. Unit supply air discharge is vertical as standard, and hor

-

izontal as optional for sizes 12 and 24

. These 

vertical packaged

units are fully piped and wired. Units are complete with a belt

drive evaporator section and built-in ducted air-cooled condenser.

Most units are designed to fit through most standard doors. See

Fig. 1-9 for unit dimensions and refer to Table 1 for unit operating

weights.

INSTALLATION

Omnizone 50XCA units are intended for indoor installation only.

Determine building alterations required to run piping, wiring and

ductwork. Follow dimensional drawings for ductwork, piping lo

-

cations, electrical wiring and overall unit dimensions. Read all in

-

stallation instructions before installing the unit.

Step 1 — Complete Pre-Installation Checks

Examine unit for damage that might have incurred during ship

-

ment. File claim immediately with transit company if damage is

found.  Check  the  shipment  for  completeness.  Verify  that  the

nameplate  electrical  requirements  match  the  available  power

supply.

DO NOT place the unit in a horizontal position. Do not allow re

-

frigerant lines to come into contact with wiring or sharp objects or

edges. Do not lift or move unit by putting pressure on refrigerant

lines, blowers, compressors, motors, or coils.

DANGER

DO NOT USE TORCH to remove any component. System

contains oil and refrigerant under pressure.

To remove a component, wear protective gloves and goggles

and proceed as follows:

a. Shut off electrical power to unit.

b. Recover refrigerant to relieve all pressure from system

using both high-pressure and low pressure ports.

c. Traces of vapor should be displaced with nitrogen and

the work area should be well ventilated. Refrigerant in

contact with an open flame produces toxic gases.

d. Cut component connection tubing with tubing cutter and

remove component from unit. Use a pan to catch any oil

that may come out of the lines and as a gage for how

much oil to add to the system.

e. Carefully un-sweat remaining tubing stubs when neces

-

sary. Oil can ignite when exposed to torch flame.

Failure to follow these procedures may result in personal inju

-

ry or death.

CAUTION

DO NOT re-use compressor oil or any oil that has been ex

-

posed to the atmosphere. Dispose of oil per local codes and

regulations. DO NOT leave refrigerant system open to air any

longer than the actual time required to service the equipment.

Seal circuits being serviced and charge with dry nitrogen to

prevent oil contamination when timely repairs cannot be com

-

pleted. Failure to follow these procedures may result in dam

-

age to equipment.

Содержание OMNIZONE 50XCA06

Страница 1: ...Fan Adjustment 34 Pulley Alignment 34 Belt Tension Adjustment 35 Changing Fan Wheel 35 Fan Bearing Replacement 35 Concentric Alignment 35 Evaporator and Condenser Motor Starter Setting after Lockout...

Страница 2: ...he nameplate electrical requirements match the available power supply DO NOT place the unit in a horizontal position Do not allow re frigerant lines to come into contact with wiring or sharp objects o...

Страница 3: ...NT VIEW CONTROL BOX DISCONNECT OPT TOP VIEW SIZE 06 RIGHT VIEW REAR VIEW TOP VIEW SIZE 08 EVAP ACCESS PANEL CONDENSER ACCESS PANEL NOTE Dimensions are in inches UNIT 50XCA WIDTH HEIGHT DEPTH COND SECT...

Страница 4: ...ACCESS PANEL CONDENSER ACCESS PANEL INDOOR SUPPLY AIR FLOW CONDENSER DISCHARGE CONTROL BOX FRONT VIEW NOTE Dimensions are in inches UNIT 50XCA WIDTH HEIGHT DEPTH COND SECTION EVAP SECTION EVAP RETURN...

Страница 5: ...U J U CONDENSER ACCESS PANEL CONDENSER DISCHARGE RIGHT VIEW FRONT VIEW REAR VIEW TOP VIEW L NOTE Dimensions are in inches UNIT 50XCA WIDTH HEIGHT DEPTH COND SECTION EVAP SECTION EVAP RETURN DUCT COND...

Страница 6: ...ACCESS PANEL CONDENSER ACCESS PANEL INDOOR SUPPLY AIR FLOW CONDENSER DISCHARGE CONTROL BOX FRONT VIEW NOTE Dimensions are in inches UNIT 50XCA WIDTH HEIGHT DEPTH COND SECTION EVAP SECTION EVAP RETURN...

Страница 7: ...DENSER DISCHARGE RIGHT VIEW FRONT VIEW REAR VIEW TOP VIEW CONDENSER ACCESS PANEL CONTROL BOX NOTE Dimensions are in inches UNIT 50XCA WIDTH HEIGHT DEPTH COND SECTION EVAP SECTION EVAP RETURN DUCT COND...

Страница 8: ...8 1 5 5 7 12 5 13 8 8 5 13 5 11 7 18 9 16 2 36 5 16 2 1 25 24 88 0 100 1 31 2 60 5 39 5 81 5 35 8 62 6 5 5 80 38 5 1 5 5 7 14 9 13 8 8 6 8 3 13 2 15 0 16 2 42 0 8 3 2 00 C 5 1 1 2 FLTR 6 8 4 FLTR E D...

Страница 9: ...56 7 5 5 80 32 8 1 5 5 7 12 5 13 8 2 6 13 5 11 7 18 9 16 2 36 5 16 2 1 25 24 88 0 100 1 31 2 60 5 39 5 81 5 35 8 62 6 5 5 80 38 5 1 5 5 7 14 9 13 8 2 6 8 3 13 2 15 0 16 2 42 0 8 3 2 00 V V Q Q N N N...

Страница 10: ...8 1 5 5 7 12 5 13 8 8 5 13 5 11 7 18 9 16 2 36 5 16 2 1 25 24 88 0 100 1 31 2 60 5 39 5 81 5 35 8 62 6 5 5 80 38 5 1 5 5 7 14 9 13 8 8 6 8 3 13 2 15 0 16 2 42 0 8 3 2 00 S T 13 2 U R U R R K J L M A...

Страница 11: ...8 56 7 5 5 80 32 8 1 5 5 7 12 5 13 8 2 6 13 5 11 7 18 9 16 2 36 5 16 2 1 25 24 88 0 100 1 31 2 60 5 39 5 81 5 35 8 62 6 5 5 80 38 5 1 5 5 7 14 9 13 8 2 6 8 3 13 2 15 0 16 2 42 0 8 3 2 00 A F I G H DI...

Страница 12: ...s Quantity Rows Fins in 3 15 4 15 3 15 4 15 4 15 4 15 Fin Block Size H x L in 28x35 28x46 32x60 32x60 32x80 36x80 Face Area sq ft 6 8 8 9 13 3 13 3 17 7 20 RETURN AIR FILTERS Std 1 in Throwaway 2 25 x...

Страница 13: ...ts Obstructions closer than 10 ft to the discharge air pattern can also cause significant recirculation See Fig 12 for recommended duct sizing CONDENSER AIR DUCT The condenser supply and discharge air...

Страница 14: ...LOUVER WIDTHS OVER 30 5 3 1 2 4 1 30 EXHAUST VANE DEFLECTOR CONDENSER INTAKE Access panel for condenser coil cleaning INLET LOUVER DETAIL DISCHARGE LOUVER DETAIL DEFLECTOR DETAIL DIMENSIONS in UNIT 50...

Страница 15: ...50XCA Installation Options Fig 14 Typical Fan Discharge Connections for Multiple Fan Units Provide access for cleaning condenser coil NOTE A min straight duct length Preferred for condenser discharge...

Страница 16: ...must be in accordance with local or NEC National Electrical Code regulations POWER WIRING The units must have adequate overcurrent protection fuses or HACR Heating Air Conditioning and Refrigeration b...

Страница 17: ...8 208 230 3 60 187 253 23 0 149 460 3 60 414 506 11 0 75 575 3 60 518 632 8 0 54 12 208 230 3 60 187 253 15 6 110 15 9 110 460 3 60 414 506 7 8 52 7 1 52 575 3 60 518 632 5 8 39 5 1 39 14 208 230 3 60...

Страница 18: ...5 8 in long screws provided with plenum Install 3 screws along each plenum side and 5 screws along plenum front and rear mounting angles 4 Adjust four way deflection vanes as needed to ensure ade qua...

Страница 19: ...Shaft alignment can be checked by measuring the distance between the shafts at 3 or more locations If the distances are equal then the shafts are parallel 2 Sheave Alignment Fixed sheaves To check th...

Страница 20: ...Solution a From Fig 20 find that deflection force for type A super belt with 5 in small sheave PD is 4 to 51 2 lb b Deflection 16 64 1 4 in c Increase or decrease belt tension until force required for...

Страница 21: ...are installed on the condenser fan before starting the unit CFM ESP in wg 0 00 0 10 0 20 0 30 0 40 0 50 0 60 0 70 0 80 0 90 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm...

Страница 22: ...684 0 61 744 0 74 800 0 87 854 1 01 906 1 16 956 1 32 1004 1 48 2950 655 0 58 714 0 71 771 0 83 826 0 97 878 1 12 928 1 27 976 1 43 1023 1 60 3100 688 0 68 745 0 80 799 0 94 852 1 08 902 1 23 950 1 39...

Страница 23: ...5300 503 0 88 552 1 04 597 1 20 640 1 37 680 1 54 719 1 72 757 1 90 793 2 10 5500 522 0 99 569 1 15 613 1 32 654 1 49 694 1 66 732 1 85 769 2 04 804 2 23 5700 541 1 10 587 1 27 629 1 44 670 1 62 708 1...

Страница 24: ...p Rpm Bhp 6000 496 1 03 533 1 17 570 1 36 608 1 58 646 1 82 683 2 06 719 2 31 755 2 56 6250 517 1 17 552 1 31 588 1 50 624 1 72 660 1 97 696 2 22 732 2 48 766 2 74 6500 537 1 31 571 1 46 605 1 65 640...

Страница 25: ...853 3 71 883 3 95 7750 588 1 99 629 2 22 667 2 45 704 2 68 739 2 92 772 3 16 804 3 40 836 3 64 866 3 89 895 4 14 8000 607 2 15 646 2 38 684 2 62 720 2 86 754 3 10 787 3 34 818 3 59 849 3 83 878 4 08 9...

Страница 26: ...890 5 25 920 5 64 9700 699 3 28 738 3 65 775 4 04 810 4 42 844 4 81 876 5 21 907 5 61 936 6 02 10000 721 3 59 759 3 98 795 4 37 829 4 77 862 5 17 893 5 58 923 5 99 953 6 41 10300 742 3 92 779 4 32 81...

Страница 27: ...29 1062 1 39 2300 731 0 67 774 0 75 816 0 83 857 0 92 897 1 01 935 1 10 973 1 20 1010 1 30 1046 1 40 1081 1 50 2400 763 0 76 804 0 85 845 0 93 884 1 02 922 1 11 960 1 21 996 1 31 1032 1 41 1067 1 51...

Страница 28: ...Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 2200 497 0 27 581 0 39 655 0 52 722 0 66 782 0 80 839 0 95 892 1 11 941 1 28 989 1 45 1034 1 62 2400 542 0 35 621 0 48 690 0 62 753 0 77 812 0 92 866 1 08 917 1 25 966...

Страница 29: ...806 1 38 852 1 56 897 1 76 4000 508 0 63 547 0 71 588 0 81 632 0 92 677 1 04 722 1 17 768 1 31 814 1 47 859 1 65 903 1 85 4200 533 0 73 570 0 82 609 0 92 650 1 03 693 1 15 736 1 28 780 1 42 823 1 58...

Страница 30: ...8 819 2 03 846 2 18 874 2 32 903 2 46 934 2 62 966 2 78 5700 733 1 28 763 1 61 789 1 85 815 2 05 841 2 22 867 2 37 894 2 52 921 2 67 950 2 82 980 2 98 5900 759 1 42 787 1 77 813 2 02 838 2 23 863 2 41...

Страница 31: ...673 1 90 718 2 13 761 2 37 802 2 61 841 2 86 879 3 11 916 3 37 951 3 63 6500 598 1 63 647 1 86 693 2 10 737 2 34 778 2 59 818 2 84 857 3 09 894 3 35 929 3 62 964 3 89 6750 621 1 83 668 2 07 713 2 32...

Страница 32: ...777 2 58 824 2 76 869 2 94 912 3 11 952 3 28 992 3 44 6 300 585 1 95 644 2 17 698 2 38 749 2 58 797 2 77 843 2 95 887 3 13 928 3 31 968 3 48 1007 3 64 6 600 613 2 14 669 2 36 722 2 57 771 2 77 818 2...

Страница 33: ...g parameters must be set on each unit To change the parameters 1 Press MENU 2 Select Parameters 3 Press ENTER 4 Select sub group first two digits of the parameters 5 Press SEL 6 Select parameter 7 Pre...

Страница 34: ...ay from fixed flange to decrease speed Increas ing fan speed increases load on motor Do not exceed maxi mum allowable fan speed or motor full load amps indicated on unit nameplate See Tables 2 and 3 f...

Страница 35: ...and reverse Steps 1 3 above Concentric Alignment Shaft and wheels must be concentrically centered with the venturi or air inlet of the fan housing see Fig 22 Fig 22 Concentric Alignment Shaft bearing...

Страница 36: ...utes before check ing charge 5 From standard Pressure Temperature chart for R 410A find equivalent saturated condensing temperature 6 Read liquid line temperature on thermometer then subtract from sat...

Страница 37: ...ent Protection Device All units are equipped with a current sensing lockout relay on each circuit This device will lock out the compressor after any safety trip high pressure switch low pressure switc...

Страница 38: ...phase Check TXV Check temperature in suction discharge line Unit is Noisy Compressor noise Check TXV and replace if necessary Check internal noise Tube vibration or condenser water problem Check and c...

Страница 39: ...building load Low refrigerant Check for and repair leaks and add refrigerant as necessary Low airflow in evaporator Clean filter Remove scale Check for blockage in ducts Check fan rotation Check moto...

Страница 40: ...at Relay IFC Indoor Fan Contactor IFM Indoor Fan Motor IFR Indoor Fan Relay LPS Low Pressure Switch LLT Liquid Line Temperature OFC Outdoor Fan Contactor OFM Outdoor Fan Motor OFR Outdoor Fan Relay PR...

Страница 41: ...11 10 12 601 RED 602 BLU 603 YEL 604 BRN 608 PNK 8 5 2 Y2 608 PNK W2 D2 D1 604 BRN 603 YEL 601 RED 550 BLK REMOVE JUMPER BLK 600 WHEN CONNECTING AIR SIDE ECONOMIZER OCCUPANCY CONTROL WHEN FIELD INSTA...

Страница 42: ...0 BRN DISC1 L2 L3 L1 GND 100 BLK 101 BLK 102 BLK 114BLK 115 YEL 116 BLU 117 GRN OFM 2 1 3 GND 2 1 3 COMP2 130 BLK 132 BLU 131 YEL 127 BLK 129 BLU 128 YEL C2 134 BLK 135 BLK CH2 CLO2 Loop T2 L2 T1 L1 T...

Страница 43: ...THE FACTORY SHORTING PLUG FIELD INSTALLED SAT SENSOR CONNECTS TO CIRCUITS 6 7 Continued on Line Voltage Diagram 501 RED 561 RED 1 3 CR1 531 BRN 609 PNK 609 PNK 9 4 2 CR1 3 LOGIC 1 2 CLO2 HPS2 FRZ2 LP...

Страница 44: ...1 10 12 601 RED 602 BLU 603 YEL 604 BRN 608 PNK 8 5 2 Y2 608 PNK W2 D2 D1 604 BRN 603 YEL 601 RED 550 BLK REMOVE JUMPER BLK 600 WHEN CONNECTING AIR SIDE ECONOMIZER OCCUPANCY CONTROL WHEN FIELD INSTALL...

Страница 45: ...45 Fig 29 Typical Wiring Schematic for Low Ambient Option 50XCA06 08 Units NOTE See legend and notes on page 40...

Страница 46: ...Catalog No 04 53500277 01 Printed in U S A Form 50XCA 9SI Pg 46 2 2020 Replaces 50XCA 8SI 2020 Carrier Corporation Fig 30 Typical Wiring Schematic for Low Ambient Option 50XCA12 24 Units NOTE See lege...

Страница 47: ...VE CONDENSERAND EVAPORATOR FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENTAND DO THE FAN BELTS HAVE PROPER TENSION Y N _______ HAS CORRECT FAN ROTATION OR EVAPORATORAND CONDENSER BEEN CONFIRME...

Страница 48: ...MEASUREMENTS COMPRESSORAMPS NOTES _______________________________________________________________________________________ _____________________________________________________________________________...

Отзывы: