Sequence  of  Operation  (VAV Only)  — 

The fol-

lowing control sequence of operation for the VAV units de-

scribes the various sequences that occur depending upon the

way an operation is triggered and which software control

points are involved.
SUPPLY FAN — The supply fan can be activated in any of

the following ways:
• Unoccupied space or return air temperature demand

• Unoccupied linkage demand

• Local time schedule (TIMCLOCK software point)

• Remote occupancy (ROCC software point)

• Remote-off-local switch in the local mode

• Enabled by schedule 

Once one of the above conditions exists, either TIME-

CLOCK or ROCC indicates ON or enable. The software point

OKFAN will turn on followed by the points TRMCT for air

terminal control and PUMP and TOWER to request condenser

water flow and temperature control. Approximately 20 to

30 seconds later, the supply fan (SF) point will turn ON and the

VFD output SPEED will increase. The SPEED point will

output a signal, determined by a PID (proportional integral de-

rivative loop) calculation, based on the duct static pressure

(DSP) input and the supply static pressure setpoint in

SETPT05.

Once the supply fan is running and the static pressure in-

creases above the supply fan status setpoint in SETPT01, the

supply fan status point (SFS) will indicate ON and the software

point SF_SFS will indicate TRUE. 
Enabled By Unoccupied Demand — A software point “space

control point” will display the current value of the sensor used

to determine unoccupied demand. The EWT sensor provides

this function for the 50BV unit. The display is based on the

sensors installed and the configuration of these sensors in the

custom configuration, or the status of linkage.

If there is no RAS connected to the EWT input, the space

control point will display a default value of 75 F. This value is

above the default occupied cooling set point and below the

unoccupied cooling set point. If this condition exists, supply air

reset from a sensor and unoccupied unit operation will not

occur.

If the unit is configured to use an RAS sensor for the Space

Control Point or if linkage is active and the space has unoccu-

pied demand, the software point OKFAN will turn on followed

by the software points TRMCT for air terminal control and

PUMP and TOWER to request condenser water flow and tem-

perature control. Approximately 20 to 30 seconds later the SF

point will turn ON and then the VFD output SPEED will in-

crease. If unoccupied demand is the reason the fan is on, a con-

trol force will appear next to the OKFAN point. Otherwise,

there should not be a force on that point.

If the fan is running due to unoccupied heating or cooling

demand, either the space temperature (if installed), return-air

temperature, or average linkage temperature must rise or drop

to within half way between the occupied and unoccupied set

points in order for the fan to turn back off.
Enabled by Switching to Local Mode — When the switch is

placed in the Local mode the ROCC point will indicate enable.

If ROCC is ENABLED a software routine will override the oc-

cupancy schedule so that TIMECLOCK will also turn on.

When ROCC is turned off the TIMECLOCK point will turn

off within 60 seconds.    
Supply Fan Shutdown — If the unoccupied demand is satis-

fied and TIMECLOCK and ROCC are off and disabled,

OKFAN will turn off, SF_SFS will turn off, Tower and PUMP

will turn off, and then 5 minutes later the SF point will turn off

and the VFD speed will go to 0%. 

During the 5-minute delay, the cooling and heating routines

become disabled. This delay allows a compressor that may

have just started to run for its 5-minute minimum on time with

the supply fan on. For example, if the staging routine had just

started Compressor 3 at the time the OKFAN point changed to

OFF, the cooling routine would become disabled and compres-

sors 1 and 2 would shut off right away. Compressor three

would continue to run for its minimum on time of 5 minutes.

The fan continues running until all compressors meet the mini-

mum on time and run with a load, preventing them from shut-

ting down due to a safety.
COMPRESSOR COOLING — If the fan is on and there is no

demand for heat, the Equipment mode (MODE) will be

COOL, and Cooling (COOLOK) will switch to ENABLE. 

COMRES triggers the compressor staging routine that con-

trols the number of compressors energized. Units are equipped

with 2 or 4 compressors piped in separate refrigerant circuits,

and staged On/Off in a fixed sequential manner (compressor

no. 1 through compressor no. 4). The compressor control rou-

tine uses a PID calculation to determine the percentage of cool-

ing required, from 1 to 100%. Demand for the PID calculation

is determined from the supply air temperature and the supply

air setpoint (SETPT06).

Compressor cooling (COMPRES) will be turned off for any

of the following reasons:
• There is no condenser water flow (CDWF is Off). 

• MODE changes to heat.

• OKFAN turns off during normal shut down. 

During normal compressor operation the minimum on time

is 5 minutes and the minimum off time is 5 minutes.
WATER ECONOMIZER COOLING — The  unit  diverts

condenser inlet waterflow through an optional economizer coil

to precool evaporator entering airflow. If the entering water

temperature is colder than the setting on the aquastat, and the

return-air temperature is warmer than the setting on the return-

air thermostat, the three-way diverting valve will direct water

to the economizer coil.

Economizer water flow is in series with the condensers,

allowing compressor operation while the economizer is

operating.
NOTE: The return-air thermostat (RAT) is separate from the

RAS sensor.
COOLING RESET — The 5 kiloohm temperature sensor will

be used as the space control point. If this variable goes below

the occupied high set point in the HEAT/COOL MODE AND

RESET set point (SETPT03), then for each degree that the

space control point is below the set point value, the supply air

set point will be reset by the value configured in the custom

configuration RESET RATIO. 

Diagnostic Features (CV Only) — 

The main con-

trol board (MCB) in the constant volume units has 2 LEDs that

provide diagnostic information. Refer to the Troubleshooting

section for a detailed description of the LED codes.

VAV Control and VFD Diagnostics — 

Refer to the

50BV,XJ Controls Operation and Troubleshooting manual for

detailed information about diagnosing and correcting control

and VFD messages.

Содержание OMNIZONE 50BV020

Страница 1: ...CV Unit Start Up 31 EVAPORATOR FAN COOLING HEATING Heat Pump Units Only VAV Unit Start Up 42 PERFORM AUTOMATIC RUN TEST CHECK VFD POWER UP LID DISPLAY Page LOG ON TO THE LID DISPLAY CHANGE THE DEFAULT...

Страница 2: ...e vent compressor short cycling Low Pressure Bypass Timer bypasses the low pressure switch for 90 seconds to avoid nuisance trips during cold start up High Pressure Switch Delay is a one second delay...

Страница 3: ...lar units with a fork truck using the baserails provided or use spreader bars and lifting straps as shown in Fig 1 For single piece units use spreader bars and rigging straps if lifting with a crane t...

Страница 4: ...hes mm 2 VAV models 50BVJ are rear return top supply only 3 Compressor controls and condenser access are through front panels 4 Field power connections are 1 3 4 inches Control connections are 7 8 inc...

Страница 5: ...r connections are 1 3 4 inches Control connections are 7 8 inches 5 Discharge hot gas connections are 1 1 8 in OD 6 Liquid line connections are 7 8 in OD 7 Optional blower orientation is selected in m...

Страница 6: ...11 00 3 19 5 50 65 50 54 75 2 00 23 25 5 00 51 63 1 50 1 50 LIFTING SUPPORT RAIL 69 50 SHIPPING SECTION 10 75 3 75 B A C D a50 8201 NOTES 1 Dimensions in inches 2 All units are rear return airflow con...

Страница 7: ...m service clearances are as follows a Front and rear 30 in 762 mm b Left or right side 65 in 1651 mm for coil removal c Side opposite coil removal 20 in 508 mm CONNECTIONS REPLACEMENT FILTERS EIGHT 8...

Страница 8: ...49 75 21 75 9 88 19 75 9 88 111 00 3 19 5 50 65 50 65 50 4 00 54 75 2 00 2 00 23 25 5 00 51 63 1 50 1 50 LIFTING SUPPORT RAIL 69 50 SHIPPING SECTION 69 50 SHIPPING SECTION 10 75 3 75 A B C D NOTES 1 D...

Страница 9: ...R IN 2 1 2 in FPT 3 in FPT 3 in FPT C CONDENSATE DRAIN 1 1 4 in FPT 1 1 4 in FPT 1 1 4 in FPT D ECONOMIZER DRAIN 1 1 4 in FPT 1 1 4 in FPT 1 1 4 in FPT NOTES 1 Dimensions in inches 2 All units are rea...

Страница 10: ...ensions in inches 2 All units are rear return airflow configuration 3 Constant volume units are available with front or rear air supply 4 VAV units 50BVX are available with rear supply only 5 Recommen...

Страница 11: ...gn Manual Part 3 5 Recommended minimum service clearances are as follows a Front and rear 30 in 762 mm b Left or right side 65 in 1651 mm for coil removal c Side opposite coil removal 20 in 508 mm CON...

Страница 12: ...NG SECTION 69 50 SHIPPING SECTION 10 75 E F A B C D A B C D Fig 10 50BVU X044 064 High Boy Dimensions NOTES 1 Dimensions in inches 2 All units are rear return airflow configuration 3 CV units are avai...

Страница 13: ...n 1651 mm for coil removal CONNECTIONS REPLACEMENT FILTERS SIXTEEN 16 AT 17 x 27 x 4 INCHES UNIT SIZE 044 054 064 A LIQUID LINE CIRCUIT 1 2 7 8 in OD 7 8 in OD 7 8 in OD B LIQUID LINE CIRCUIT 3 4 7 8...

Страница 14: ...20 028 with Optional Waterside Economizer Dimensions NOTES 1 Dimensions in inches mm 2 Refer to base unit certified drawing for additional unit dimensions service clearance and alternate airflow confi...

Страница 15: ...034 with Optional Waterside Economizer Dimensions NOTES 1 Dimensions in inches mm 2 Refer to base unit certified drawing for additional unit dimensions service clearances and alternate airflow configu...

Страница 16: ...0 40 40 40 40 40 40 FILTER ECONOMIZER SECTION EACH NUMBER OF SECTIONS 1 2 2 2 1 2 2 2 FILTER SECTION 310 310 310 310 310 310 310 310 ECONOMIZER OPTION 200 200 200 200 200 200 200 200 FAN SECTION EACH...

Страница 17: ...l RPM 5 HP 3450 3450 3450 3450 Fan Drive RPM Range Std Fan Drive 1 5 2 3 HP 753 952 753 952 753 952 Std Fan Drive 5 HP 967 1290 967 1290 967 1290 967 1290 Med Static Fan Drive 1 5 2 3 HP 872 1071 872...

Страница 18: ...960 Standard 10 15 20 HP Med Static 7 5 HP 805 991 805 991 805 991 805 991 Med Static 10 15 20 HP High Static 7 5 HP 960 1146 960 1146 960 1146 960 1146 High Static 10 15 20 HP 1119 1335 1119 1335 11...

Страница 19: ...onomizer section facing out and away from the main air conditioning section 2 If the unit has 2 filter economizer and 2 main air conditioning sections 40 through 60 ton units bolt the remaining filter...

Страница 20: ...point should be located near the end of the main supply trunk duct in a position free from turbulence effects and at least 10 duct di ameters downstream and 4 duct diameters upstream from any major t...

Страница 21: ...endent refrigerant circuits to operate while still modulating condenser water flow in response to loop water temperature A glycol solution should be used if ambient temperatures are expected to fall b...

Страница 22: ...o avoid the build up of dirt and bacterial growth HOT WATER HEATING COIL Optional A factory installed one or 2 row hot water heating coil is available as an option The coil is supplied with hot water...

Страница 23: ...economizer waterside pressure drop data The waterside economizer can also be ordered without factory installed piping or controls This offers additional flexibility for specific applications In this c...

Страница 24: ...tion instructions for additional guidance Remote air cooled 50BV units only are shipped with a dry nitrogen holding charge After refrigerant connections are made release nitrogen evacuate leak test an...

Страница 25: ...2 464 455 3 1371 3 457 7 457 IMPORTANT If supply voltage phase imbalance is more than 2 contact the local electric utility com pany immediately UNIT SIZE 50BVC E J K Q NOMINAL VOLTAGE 3 Ph 60 Hz VOLTA...

Страница 26: ...5 518 633 12 4 80 12 4 80 2 7 5 7 8 68 3 80 65 2 10 10 3 73 3 80 70 2 15 15 4 83 5 90 80 4 054 208 230 187 253 47 1 318 47 1 318 2 7 5 19 4 239 0 250 227 2 10 25 8 251 8 250 240 0 15 38 6 277 4 300 26...

Страница 27: ...typical thermostat wiring 50BVT U V044 064 Only Units larger than 30 tons have 4 independent refrigerant circuits These units can be controlled using a standard commercial 2 stage thermostat In this c...

Страница 28: ...The sensor should be located in the supply air duct about 1 ft from the unit discharge connection Fig 30 On units with 2 fans locate the sensor ap proximately 5 duct diameters downstream from pair of...

Страница 29: ...7 Modular Unit VAV Control Panel Fig 28 Single Piece Unit VAV Control Panel Fig 29 Supply Return Air Temperature Sensor P N HH79NZ043 Fig 30 Supply Air Temperature Sensor Installation Unit Discharge L...

Страница 30: ...The 50BVT U V W X034 064 units include crankcase heaters Crankcase heaters are ener gized as long as there is power to the unit and the compressor is not operating Wait 24 hours before starting the c...

Страница 31: ...cycle mode Set the thermostat below room temperature and confirm that the compressors and fan turn off Table 13 Fan Performance 50BVC E Q020 LEGEND NOTES 1 Units are available with the following motor...

Страница 32: ...7 000 604 774 0 87 666 906 1 02 726 1029 1 16 784 1170 1 32 841 1311 1 48 7 500 634 916 1 03 693 1057 1 19 750 1189 1 34 805 1330 1 50 858 1480 1 67 8 000 667 1085 1 22 723 1226 1 38 777 1377 1 55 82...

Страница 33: ...1664 1 93 816 1827 2 12 863 1989 2 31 908 2152 2 50 952 2323 2 69 10 000 802 1908 2 21 848 2080 2 41 892 2251 2 61 936 2422 2 81 978 2624 3 01 10 500 835 2179 2 53 879 2350 2 73 921 2531 2 93 963 2742...

Страница 34: ...59 2 59 822 2451 2 81 864 2642 3 03 906 2833 3 25 946 3024 3 47 12 000 805 2533 2 90 848 2733 3 13 889 2933 3 36 929 3133 3 59 968 3333 3 82 12 500 835 2842 3 26 877 3042 3 49 917 3251 3 73 955 3460 3...

Страница 35: ...8 780 8 260 9 91 810 8 561 10 44 839 8 990 10 97 868 9 427 11 50 13 000 777 8 595 10 49 806 9 050 11 04 835 9 504 11 59 863 9 949 12 14 891 10 403 12 69 13 500 804 9 572 11 68 832 10 043 12 25 860 10...

Страница 36: ...8 1050 9 915 12 09 1076 10 257 12 51 11 500 988 9 812 11 97 1014 10 155 12 39 1040 10 506 12 82 1065 10 848 13 23 1090 11 207 13 67 12 000 1006 10 771 13 14 1031 11 130 13 58 1056 11 490 14 02 1080 11...

Страница 37: ...40 691 3990 4 73 18 000 543 3001 3 56 584 3325 3 94 625 3640 4 32 664 3955 4 69 700 4252 5 04 19 000 568 3474 4 12 607 3815 4 53 646 4147 4 92 684 4488 5 32 720 4820 5 72 19 500 580 3728 4 42 619 407...

Страница 38: ...78 5 08 679 4628 5 49 715 4968 5 89 749 5299 6 29 20 000 617 4226 5 01 655 4584 5 44 691 4933 5 85 726 5282 6 27 761 5654 6 71 20 500 629 4505 5 34 665 4872 5 78 701 5238 6 21 736 5618 6 67 770 5980 7...

Страница 39: ...932 7 048 8 46 962 7 362 8 83 991 7 676 9 21 1019 7 999 9 60 1047 8 330 9 99 20 000 940 7 423 8 91 969 7 746 9 29 997 8 060 9 67 1025 8 253 10 07 1053 8 578 10 46 20 500 946 7 798 9 36 975 8 121 9 74...

Страница 40: ...8 34 754 7 380 8 85 784 7 798 9 36 815 8 225 9 87 845 8 510 10 38 25 000 750 7 816 9 38 780 8 260 9 91 810 8 561 10 44 839 8 990 10 97 868 9 427 11 50 26 000 777 8 595 10 49 806 9 050 11 04 835 9 504...

Страница 41: ...9 238 11 27 1024 9 572 11 68 1050 9 915 12 09 1076 10 257 12 51 23 000 988 9 812 11 97 1014 10 155 12 39 1040 10 506 12 82 1065 10 848 13 23 1090 11 207 13 67 24 000 1006 10 771 13 14 1031 11 130 13 5...

Страница 42: ...in edit mode The display will show 2 0 Global Dictionary OMNIZONE 9 Press The display will show Compressor Stages 2 00 sizes 020 034 4 00 sizes 044 064 10 If the number of compressor stages displayed...

Страница 43: ...ed alarm LED will be lit this is normal 2 If the unit access panel for power and controls is still on the unit remove it in order to view the control modules during start up 3 Switch the main unit pow...

Страница 44: ...e is entered in military time for example 14 59 for 2 59 pm Press then press the button The LID display will show Day of Week 1 5 Enter the day of week The numbers 1 through 7 corre spond to the days...

Страница 45: ...is the pressure set point below which the fan is con sidered to be off 5 Press The LID display will show Occupied Hi Setpoint 0 40 in H2O This is the pressure set point above which the fan is con sid...

Страница 46: ...UE UNITS STATUS FORCE NAME OMNIZONE HWP01 32 Hardware points Table 1 Supply Air Temperature 67 dF SAT Duct Static Pressure 0 2 in H2O DSP Comp Status MUX 1 86 Volts CSMUX Fire Alarm ShutDown Enable FS...

Страница 47: ...oil is powered by the energy man agement building automation system whose contacts are in series with the R 24 v ac terminal with potential across C transformer common With this terminal open power wi...

Страница 48: ...l also turn on When ROCC is turned off the TIMECLOCK point will turn off within 60 seconds Supply Fan Shutdown If the unoccupied demand is satis fied and TIMECLOCK and ROCC are off and disabled OKFAN...

Страница 49: ...y also be used to help re move grease and dirt Steam cleaning is NOT recommend ed After cleaning use a fin comb of the correct fin spacing when straightening mashed or bent coil fins Units installed i...

Страница 50: ...balanced To change the drive ratio follow the steps in the Evaporator Fan Performance Adjustment section page 51 After 1 to 3 minutes of operation check the belt tension Also check tension frequently...

Страница 51: ...ength of interconnecting piping and vertical separa tion between the indoor unit and the condenser s Table 25A Minimum Operating Charge lb 50BVE K Units Matched with 09DK Condensers Table 25B Minimum...

Страница 52: ...ARM red LED is lit after blinking 6 times Compressor 1 does not start Wiring open Compressor resistor board wiring error or failure High pressure switch low pressure switch coil frost switch or compre...

Страница 53: ...device and replace Check for missing phase Check TXV Check temperature in suction discharge line Unit is Noisy Compressor noise Check TXV and replace if necessary Compressor rotation incorrect check...

Страница 54: ...t 3 2nd Stage High Pressure Lockout 4 2nd Stage Low Pressure Lockout 5 Freeze Protection Lockout 6 Condensate Overflow Lockout STEP NO INSTRUCTION ACTION RESULT 1 Press 3 SET ENTER Controller Password...

Страница 55: ...board test mode jumper to yes reduces all time delays to 5 seconds 8 Freeze pins on UPM board must be jumped if freeze sensor is not installed Standard Components Legend 1 First Stage 2 Second Stage B...

Страница 56: ...n break 90 second low pres sure bypass and 5 second second stage delay 7 Setting the test mode jumper to yes reduces all time delays to 5 seconds Standard Components Legend Optional Components Legend...

Страница 57: ...nd void unit warranty 5 For alternative EMS coil voltages consult factory Standard Components Legend BM Blower Motor BR Blower Relay CBR 24 v Circuit Breaker CC Compressor Contactor CCH Crankcase Heat...

Страница 58: ...58 a50 8236 Fig 41 50BVJ K020 034 Variable Air Volume Low Voltage Schematic NOTE Jumper installed for condenser water flow switch when not supplied...

Страница 59: ...2 L3 T3 BR L1 T1 W VFD E U V R S T2 T3 T1 1 3 2 BYPASS GND 4 5 6 L3 L1 L2 TRANFORMER PRIMARY LEAD CLR PUR OR YEL BLK RED 460 575 380 240 208 GRY ORG RED L1 L2 L3 GND L3 L2 L1 PHASE L1 L3 PCB2 J1 3 COM...

Страница 60: ...60 a50 8237 NOTE Jumper installed for condenser water flow switch when not supplied Fig 43 50BVW X034 064 Variable Air Volume Low Voltage Schematic...

Страница 61: ...CMP 2 4 CMP 2 4 CBR BM BM T2 L2 L3 T3 BR L1 T1 T2 L2 L3 T3 BR L1 T1 W VFD E U V T R S T2 T3 T1 1 3 2 BYPASS GND 4 5 6 L3 L1 L2 TRANFORMER PRIMARY LEAD CLR PUR OR YEL BLK RED 460 575 380 240 208 GRY OR...

Страница 62: ...FSD ROCC A B A B A B B A REMOTE LOCAL OFF MODE SW TB2 FIELD CONN TB1 1 TB1 2 YEL BLU DIS 7 DIS 8 HIR TRANS 1 C TRANS 1 R VENTR 5 3 HIR 5 3 ECONO OPTION BYPASS OPTION DIS 5 VENTR A B A B A B B A A B 2...

Страница 63: ...0MA OTHER OTHER 10VDC AO DO AO DO CSMUX YEL DIS 1 DIS 2 DIS 3 DIS 4 YEL BLU OPTIONAL CLO1 2 OPTIONAL J6 TO SYSTEM DISPLAY COMMON C 24VAC R DISPLAY A B A B A B B A B A 10 10 144 143 137 136 135 10 139...

Страница 64: ...O AO DO CSMUX YEL DIS 1 DIS 2 DIS 3 DIS 4 YEL BLU OPTIONAL CLO4 2 CLO3 2 CLO3 1 CLO3 3 CLO1 2 OPTIONAL J6 TO SYSTEM DISPLAY COMMON C 24VAC R DISPLAY A B A B A B A B A B B A B A 10 10 144 143 137 136 1...

Страница 65: ...Relays OLR Compressor Motor Protector PCB1 Unit Control Board PCB2 3 I O Expansion Board PHASE Phase Rotation Monitor PHASER Phase Monitor Relay RAT Return Air Thermostat RESET External Reset ROCC Rem...

Страница 66: ...o discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500001 01 Printed in U S A Form 50BV 3SI Pg 66 10 08 Replaces 50BV 2SI Co...

Страница 67: ...ION Y N _______ HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE Y N _______ ARE PROPER AIR FILTERS IN PLACE AND CLEAN Y N _______ VERIFY THAT THE UNIT IS INSTALLED WITHIN LEVELING TOLERA...

Страница 68: ...____ _______________________________________________________________________________________________ _______________________________________________________________________________________________ ___...

Отзывы: