46
Table 21 — Controller Set Points
CHECK SYSTEM PARAMETERS — To check system
parameters, press the
button. The LID display will
show: “Hardware Points”. Press
to view the hard-
ware points. The user can navigate up and down through the
points with the
and
keys.
Press 2 and
to display the software points. The user
can navigate up and down through the points with the
and
keys.
Refer to Tables 22 and 23 for hardware and software points.
Table 22 — Controller Hardware Points
Table 23 — Software Points
DESCRIPTION
DISPLAY SCREENS
VALUE
UNITS
STATUS FORCE
NAME
OMNIZONE:SETPT01:
Supply fan Status
Occupied Lo Setpoint
0.3 in. H2O
OccLow
Occupied Hi Setpoint
0.4 in. H2O
OccHgh
Unoccupied Lo Setpoint
0.3 in. H2O
UnOccLow
Unoccupied Hi Setpoint
0.4 in. H2O
UnOccHgh
OMNIZONE:SETPT02:
VAVRESETbaseline
Occupied Lo Setpoint
0
dF
OccLow
Occupied Hi Setpoint
0
dF
OccHgh
Unoccupied Lo Setpoint
0
dF
UnOccLow
Unoccupied Hi Setpoint
0
dF
UnOccHgh
OMNIZONE:SETPT03:
Heat/Cool Mode & Reset
Occupied Lo Setpoint
70
dF
OccLow
Occupied Hi Setpoint
74
dF
OccHgh
Unoccupied Lo Setpoint
55
dF
UnOccLow
Unoccupied Hi Setpoint
85
dF
UnOccHgh
OMNIZONE:SETPT04:
Head Pressure Control
Occupied Lo Setpoint
225
PSIG
OccLow
Occupied Hi Setpoint
225
PSIG
OccHgh
Unoccupied Lo Setpoint
225
PSIG
UnOccLow
Unoccupied Hi Setpoint
225
PSIG
UnOccHgh
OMNIZONE:SETPT05:
Supply Static Pressure
Occupied Lo Setpoint
1.5 in. H2O
OccLow
Occupied Hi Setpoint
1.5 in. H2O
OccHgh
Unoccupied Lo Setpoint
1.5 in. H2O
UnOccLow
Unoccupied Hi Setpoint
1.5 in. H2O
UnOccHgh
OMNIZONE:SETPT06:
Supply Air Temperature
Occupied Lo Setpoint
55
dF
OccLow
Occupied Hi Setpoint
55
dF
OccHgh
Unoccupied Lo Setpoint
55
dF
UnOccLow
Unoccupied Hi Setpoint
55
dF
UnOccHgh
OMNIZONE:SETPT07:
Building Static Pressure
Occupied Lo Setpoint
0.02 in. H2O
OccLow
Occupied Hi Setpoint
0.02 in. H2O
OccHgh
Unoccupied Lo Setpoint
0.02 in. H2O
UnOccLow
Unoccupied Hi Setpoint
0.02 in. H2O
UnOccHgh
OMNIZONE:SETPT08:
BSP raw control
Occupied Lo Setpoint
12.32
ma
OccLow
Occupied Hi Setpoint
12.32
ma
OccHgh
Unoccupied Lo Setpoint
12.32
ma
UnOccLow
Unoccupied Hi Setpoint
12.32
ma
UnOccHgh
OMNIZONE:SETPT09:
Humidity Control
Occupied Lo Setpoint
0
%RH
OccLow
Occupied Hi Setpoint
99
%RH
OccHgh
Unoccupied Lo Setpoint
0
%RH
UnOccLow
Unoccupied Hi Setpoint
99
%RH
UnOccHgh
STAT
ENTER
STAT
DESCRIPTION
DISPLAY SCREENS
VALUE
UNITS
STATUS FORCE
NAME
OMNIZONE:HWP01-32:
Hardware points Table 1
Supply Air Temperature
67
dF
SAT
Duct Static Pressure
0.2 in. H2O
DSP
Comp. Status MUX
1.86
Volts
CSMUX
Fire Alarm/ShutDown
Enable
FSD
Cond. Water Flow Switch
Yes
CDWF
Remote Occupancy
Disable
ROCC
Duct High Press. Switch
Normal
DHS
Entering Water Temp.
69.9
dF
EWT
Compressor 1 Relay
Stop
CMP1
Compressor 2 Relay
Stop
CMP2
Compressor 3 Relay
Stop
CMP3
Compressor 4 Relay
Stop
CMP4
Supply Fan/VFD
Stop
SF
VFD Speed Signal
0
%
SPEED
Non Critical Fault
Off
WARN
Critical Fault
Off
ALARM
Mixed/Return Air Temp
77.2
dF
MA_RA
Dirty Filter Status
Clean
FLTS
Phase Loss Protection
Normal
PHASE
Ext. Supply Air Reset
0
dF
RESET
Water Econ. FreezeStat
Normal
FREEZ
Space_Reset Sensor
79.2
dF
SPT
VFD Bypass Enable
Disable
BYPAS
Head Pressure(Comp1)
118.76
PSIG
PRES
Ventilation Request
Close
VENTR
VAV Terminals Control
No
TRMCT
2-position/Econo Valve
0
%
ECONO
Reverse/Head Press Ctrl
100
%
Control
MVLV
Hot Water Valve
0
%
HWV
Heat Interlock Relay
Off
HIR
Bypass Start_Stop
Stop
BPS_S
VAV Terminals Open MAX
Close
TRMOP
OMNIZONE:HWP33-64:
Hardware points table 2
Cooling Tower Sump
Temp.
57.5
dF
TWR
Building Static Milliamp
12.51
ma
BSP
Condenser Leaving Water
70.3
dF
LWT
Indoor Air Quality
587.21
IAQ
Indoor Relative Humidity
49.7
%
IRH
Outdoor Air Temp.
76.1
dF
OAT
Heat Stage 1
Off
HEAT1
Heat Stage 2
Off
HEAT2
Heat Stage 3
Off
HEAT3
Heat Stage 4
Off
HEAT4
Pump Request
Off
PUMP
Cooling Tower Request
Off
TOWER
Exhaust Fan
0
%
EXH
Ext. Dehumidification
Stop
DEHUM
DESCRIPTION
DISPLAY SCREENS
VALUE UNITS STATUS FORCE
NAME
OMNIZONE:SWP65-96:
Software Points
Compressor 1 Status
Off
CLO1
Compressor 2 Status
Off
CLO2
Compressor 3 Status
Off
CLO3
Compressor 4 Status
Off
CLO4
Bypass Acc Panel Secure
No
BP_SAFE
DX VAVRESET control
0
dF
VAVRESET
Factory/Field Test
Stop
FLDTST
Building Static Pressure
0.03 in. H2O
BSP_IN
Time Clock
Off
TIMCLOCK
Cooling
Disable
COOLOK
Supply Fan Status
Off
Control
SFS
Ok to run Fan
No
OKFAN
OK Fan + Sup. Fan Stat
FALSE
SF_SFS
Fan + Cond. Water Flow
FALSE
FAN_CDWF
Equipment Mode
Cool
Control
MODE
Activate Evacuation
Mode
Disable
EVAC
Space Control Point
74
dF
CTRLPT
Mod. Econ Enabled
No
Control
ECON_OK
Head Pressure Control
Disable
Control
HEAD
Economizer Control
Temp.
77.22
dF
ECONPT
Compressor Cooling
Disable
COMPRES
Duct Static Failure
Normal
DSP_ALM
Compressor 1 Alarm
Normal
C1_ALM
Compressor 2 Alarm
Normal
C2_ALM
Compressor 3 Alarm
Normal
C3_ALM
Compressor 4 Alarm
Normal
C4_ALM
Cond. Flow Alarm Status
Disable
Control
CDWF_ST