3

Fig. 2 — 

Mounting Applications

Table 2 — 

Physical Data

UNIT 09XC

06

08

12

14

16

24

NOMINAL CAPACITY (tons)

5

7.5

10

12

15

20

BASE UNIT OPERATING WEIGHT (lb)

823

1153

1352

1380

1645

2041

CONDENSER FAN

Adjustable, Belt-Drive, Centrifugal

Nominal Cfm

3400

4000

6000

8000

8000

10300

Cfm Range

2625-4300

2625 - 4300

4625-7375

6000 - 9500

6000 - 9500

9000-11300

Available Static (in. wg)

0 - 1.0

0 - 1.0

0 - 1.0

0 - 1.0

0 - 1.0

0 - 1.0

Condenser Fan Size

110-10R

110-10R

150-12R

150-15R

150-15R

150-11R

Number of Condenser Fans

2

2

2

2

3

3

Standard Speed Range (Rpm)

656 - 875

712 - 949

500-979

447-800

614-886

820 - 1041

Max. Allowable Rpm

1700

1700

1700

1600

1700

1700

Belt (Type)

BX66

BX65

BX75

BX77

BX82

BX87

Fan Pulley (Type)

BK70

BK65

BK90

BK100

BK130

BK85

Motor Pulley (Type)

1VP44

1VP34

1VP34

1VP34

1VL34

1VP50

Std HP

1

1.5

2

2

3.0

5

HP Range

1 - 1.5

1.5 - 2

2 - 3

2 - 3

3 - 5

5 - 7.5

Fan Shaft Size (in.)

1

1

1

1.1875

1.4375

1.4375

Motor Shaft Size (in.)

0.875

0.875

0.875

0.875

1.125

1.125

Center Distance (in.)

27.1

27.1

29.8

29.8

29.8

35.1

CONDENSER COIL

3

/

8

-in. OD, Enhanced Copper Tube, Aluminum Fins

Quantity Rows ... Fin/in.

6...16W

6...16W

6...16W

6...16W

5...16

6...16

Fin Block Size (H x L) (in.)

30 x 46

30 x 46

32 x 60

34 x 80

34 x 80

40 x 80

Face Area (sq ft)

9.58

9.58

13.33

18.89

18.89

22.2

Refrigerant Gas Inlet Connection

Size (in.)

0.625

0.625

0.875

0.875

1.125

(2).875

Refrigerant Liquid Connection

Size (in.)

0.5

0.5

0.625

0.625

0.625

(2).625

09XC

DISCHARGE
DUCT

INLET
DUCT

TO OUTSIDE

INSULATE IF THROUGH
CONDITIONED SPACE

HANGER
RODS

TO RAIN DRAIN
(REQUIRED IF RAIN
 WILL ENTER UNIT)

TO REFRIGERANT
PIPING COMPRESSOR/
EVAPORATOR UNIT

09XC IN REMOTE APPLICATION WITH DUCTWORK

(Shown Suspended from Ceiling)

Содержание Omnizone 09XC06

Страница 1: ...des Wear safety glasses and work gloves WARNING Electrical shock can cause personal injury and death Shut off all power to this equipment during installation There may be more than one disconnect switch Tag all disconnect locations to alert others not to restore power until work is completed CAUTION Use care in handling rigging and setting bulky equipment Personal injury could result DANGER DO NOT...

Страница 2: ...mbi nation is not recommended See Application Data literature for more information on condenser combinations Fig 1 Base Unit Dimensions 09XC06 24 UNIT 50XCR CONDENSER QUANTITY 09XC SIZE 06 08 12 14 16 24 06 1 08 1 12 1 14 1 16 1 24 1 UNIT 09XC WIDTH HEIGHT DEPTH CONDENSER INLET LIQUID OUTLET CONDENSER DISCHARGE DUCT BLOWER OPENING COND RETURN DUCT COND INLET DIAMETER OD LIQUID OUTLET DIAMETER OD A...

Страница 3: ...BK85 Motor Pulley Type 1VP44 1VP34 1VP34 1VP34 1VL34 1VP50 Std HP 1 1 5 2 2 3 0 5 HP Range 1 1 5 1 5 2 2 3 2 3 3 5 5 7 5 Fan Shaft Size in 1 1 1 1 1875 1 4375 1 4375 Motor Shaft Size in 0 875 0 875 0 875 0 875 1 125 1 125 Center Distance in 27 1 27 1 29 8 29 8 29 8 35 1 CONDENSER COIL 3 8 in OD Enhanced Copper Tube Aluminum Fins Quantity Rows Fin in 6 16W 6 16W 6 16W 6 16W 5 16 6 16 Fin Block Size...

Страница 4: ...4 Unit Clearances Either provide inlet filters to protect the coils or locate the unit in an area free from airborne dirt or other foreign material which could clog the coils The units are designed to pass through most 36 in door openings POSITIONING THE 09XC UNIT Refer to Fig 4 for typical service clearances To suspend the unit use 4 field supplied 1 2 in diameter or larger threaded rods Mount 2 ...

Страница 5: ...iping If tubing size is other than unit connection sizes use adapter fittings Refer to 50XCR or other compressor bearing unit base unit in stallation instructions to determine refrigerant charge adjustment for remote and special piping applications NOTE When installing 09XC units in systems add charge for other components i e filter drier moisture indicator etc to de termine system charge quantity...

Страница 6: ... HG LIQ HG LIQ HG LIQ HG LIQ HG LIQ 06 1 5 8 1 2 7 8 1 2 7 8 1 2 7 8 5 8 7 8 5 8 08 1 5 8 1 2 7 8 1 2 7 8 1 2 7 8 5 8 7 8 5 8 12 1 7 8 5 8 7 8 5 8 11 8 5 8 11 8 5 8 11 8 5 8 14 1 7 8 5 8 7 8 5 8 11 8 5 8 11 8 5 8 11 8 5 8 16 1 11 8 5 8 11 8 5 8 11 8 5 8 13 8 7 8 13 8 7 8 24 1 11 8 5 8 11 8 5 8 13 8 7 8 13 8 7 8 13 8 7 8 HG Hot Gas Refrigerant Discharge LIQ Liquid UNIT 09XC A B C D E F G 06 24 111 ...

Страница 7: ...eld supplied wire nuts to make the connections to the terminal strip in the control box For field con trol connections all wiring enters the unit through a factory punched access hole on the right side of the unit See Fig 1 Table 4 Fan Electrical Data LEGEND NOTES 1 In compliance with NEC requirements for multimotor and combina tion load equipment NEC Articles 430 and 440 the overcurrent protectiv...

Страница 8: ...eter by scrolling to that parameter and press ing EDIT 5 Select the New Value then press SAVE Table 5 Low Ambient Operation Parameters Check Operation of Condenser Fan Motor Controls and Rotation of Fans Rotation should be clockwise as viewed from belt access panel Adjust Fan Speed The 09XC units are belt driven condenser units and allow for a wide range of inlet static and condenser airflow requi...

Страница 9: ...69 1 27 1018 1 43 1066 1 60 2600 577 0 40 644 0 51 708 0 62 767 0 75 824 0 89 878 1 03 930 1 18 980 1 34 1029 1 50 1075 1 67 2700 599 0 45 664 0 56 725 0 68 783 0 81 839 0 95 892 1 09 943 1 25 992 1 41 1039 1 57 1085 1 75 2800 621 0 50 684 0 61 744 0 74 800 0 87 854 1 01 906 1 16 956 1 32 1004 1 48 1050 1 65 1095 1 83 2900 644 0 56 704 0 67 762 0 80 817 0 94 870 1 08 920 1 23 969 1 39 1016 1 56 10...

Страница 10: ...684 0 61 744 0 74 800 0 87 854 1 01 906 1 16 956 1 32 1004 1 48 2950 655 0 58 714 0 71 771 0 83 826 0 97 878 1 12 928 1 27 976 1 43 1023 1 60 3100 688 0 68 745 0 80 799 0 94 852 1 08 902 1 23 950 1 39 997 1 55 1042 1 72 3250 721 0 78 776 0 91 828 1 05 878 1 20 927 1 36 973 1 52 1019 1 69 1063 1 86 3400 755 0 89 807 1 03 857 1 18 905 1 33 952 1 49 997 1 66 1041 1 83 3550 788 1 02 838 1 16 886 1 31 ...

Страница 11: ... 5300 503 0 88 552 1 04 597 1 20 640 1 37 680 1 54 719 1 72 757 1 90 793 2 10 5500 522 0 99 569 1 15 613 1 32 654 1 49 694 1 66 732 1 85 769 2 04 804 2 23 5700 541 1 10 587 1 27 629 1 44 670 1 62 708 1 80 745 1 98 781 2 18 816 2 38 5900 560 1 22 604 1 39 646 1 57 685 1 75 722 1 94 758 2 13 794 2 33 828 2 53 6100 578 1 35 622 1 53 662 1 71 700 1 90 737 2 09 772 2 29 807 2 49 840 2 70 6300 597 1 48 ...

Страница 12: ...PM BHP 6000 496 1 03 533 1 17 570 1 36 608 1 58 646 1 82 683 2 06 719 2 31 755 2 56 6250 517 1 17 552 1 31 588 1 50 624 1 72 660 1 97 696 2 22 732 2 48 766 2 74 6500 537 1 31 571 1 46 605 1 65 640 1 88 675 2 13 710 2 39 744 2 66 778 2 93 6750 558 1 47 590 1 62 623 1 81 657 2 05 691 2 30 724 2 57 757 2 85 7000 579 1 64 610 1 79 642 1 99 674 2 23 707 2 49 739 2 76 7250 599 1 82 629 1 98 660 2 18 691...

Страница 13: ... 853 3 71 883 3 95 7750 588 1 99 629 2 22 667 2 45 704 2 68 739 2 92 772 3 16 804 3 40 836 3 64 866 3 89 895 4 14 8000 607 2 15 646 2 38 684 2 62 720 2 86 754 3 10 787 3 34 818 3 59 849 3 83 878 4 08 907 4 33 8250 626 2 32 664 2 56 701 2 80 736 3 04 769 3 28 801 3 53 832 3 78 862 4 03 891 4 28 920 4 53 8500 645 2 50 682 2 74 718 2 98 752 3 23 784 3 48 816 3 73 846 3 98 876 4 23 905 4 48 933 4 74 8...

Страница 14: ... mounting bracket Do not loosen fan motor mounting bracket from unit 3 Loosen movable pulley flange setscrew Fig 7 CFM ESP in wg 0 00 0 10 0 20 0 30 0 40 0 50 0 60 0 70 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 8 500 613 2 20 657 2 54 698 2 87 737 3 22 773 3 56 808 3 91 841 4 27 873 4 63 8 800 634 2 45 677 2 79 717 3 14 755 3 49 790 3 85 824 4 21 857 4 58 889 4 95 9 100 656 2...

Страница 15: ...an wheels 4 Remove the shaft through the access panel on either side of the unit 5 Remove the fan cut off plate in the fan discharge 6 Remove the fan wheel through the fan discharge opening 7 Replace the wheel and reverse Steps 1 5 above Fan Bearing Replacement If a fan bearing fails replace it as follows 1 Shut off unit power supply Lock out power supply and tag disconnect locations 2 Remove belt...

Страница 16: ...30V 0 50 1 8 2 2 1 1 0 9 0 75 2 5 2 6 1 3 1 0 1 00 3 4 3 0 1 5 1 1 1 50 4 6 4 2 2 1 1 6 2 00 6 0 5 6 2 8 2 1 3 00 9 2 8 6 4 3 3 4 5 00 14 5 13 6 6 8 5 4 7 50 21 5 19 4 9 7 7 5 10 00 28 0 12 6 10 1 PROBLEM POSSIBLE CAUSE CORRECTION PROCEDURE Unit will not Start Loss of unit power Check power source Check fuses circuit breakers disconnect switch Check electrical contacts Unit voltage not correct Che...

Страница 17: ...e for at least 194 F 90 C when replacing factory wiring 4 Use copper conductors only 5 Wiring for field power supply must be rated at 165 F 75 C minimum LEGEND C Compressor Contactor DISC Disconnect GND Ground OFM Outdoor Fan Motor OFR Outdoor Fan Relay PRES Pressure Transducer TB Terminal Block VFD Variable Frequency Drive Terminal Block Connection Marked Terminal Unmarked Terminal Splice Factory...

Страница 18: ...tly thermally protected 2 Three phase motors are protected under primary single phase conditions 3 Use conductors suitable for at least 194 F 90 C when replacing factory wiring 4 Use copper conductors only 5 Wiring for field power supply must be rated at 165 F 75 C minimum LEGEND C Compressor Contactor DISC Disconnect GND Ground OFM Outdoor Fan Motor OFR Outdoor Fan Relay PRES Pressure Transducer ...

Страница 19: ...____ HAVE CONDENSER FANAND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENTAND DO THE FAN BELTS HAVE PROPER TENSION Y N _______ HAS CORRECT FAN ROTATION ON CONDENSER BEEN CONFIRMED Y N _______ ARE PROPERAIR FILTERS IN PLACE AND ARE FILTERS CLEAN Y N _______ VERIFY UNIT IS INSTALLED WITHIN LEVELING TOLERANCES Y N _______ CONTROLS HAVE CONTROL CONNECTIONS BEEN MADE AND CHECKED Y N _______ ARE ALL WIR...

Страница 20: ...ST 15 MINUTES RUNNING TIME RECORD THE FOLLOWING MEASUREMENTS COMPRESSORAMPS NOTES _______________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ ______________________________________...

Отзывы: