![Carrier Omnizone 09XC06 Скачать руководство пользователя страница 3](http://html1.mh-extra.com/html/carrier/omnizone-09xc06/omnizone-09xc06_installation-start-up-and-service-instructions-manual_2563570003.webp)
3
Fig. 2 —
Mounting Applications
Table 2 —
Physical Data
UNIT 09XC
06
08
12
14
16
24
NOMINAL CAPACITY (tons)
5
7.5
10
12
15
20
BASE UNIT OPERATING WEIGHT (lb)
823
1153
1352
1380
1645
2041
CONDENSER FAN
Adjustable, Belt-Drive, Centrifugal
Nominal Cfm
3400
4000
6000
8000
8000
10300
Cfm Range
2625-4300
2625 - 4300
4625-7375
6000 - 9500
6000 - 9500
9000-11300
Available Static (in. wg)
0 - 1.0
0 - 1.0
0 - 1.0
0 - 1.0
0 - 1.0
0 - 1.0
Condenser Fan Size
110-10R
110-10R
150-12R
150-15R
150-15R
150-11R
Number of Condenser Fans
2
2
2
2
3
3
Standard Speed Range (Rpm)
656 - 875
712 - 949
500-979
447-800
614-886
820 - 1041
Max. Allowable Rpm
1700
1700
1700
1600
1700
1700
Belt (Type)
BX66
BX65
BX75
BX77
BX82
BX87
Fan Pulley (Type)
BK70
BK65
BK90
BK100
BK130
BK85
Motor Pulley (Type)
1VP44
1VP34
1VP34
1VP34
1VL34
1VP50
Std HP
1
1.5
2
2
3.0
5
HP Range
1 - 1.5
1.5 - 2
2 - 3
2 - 3
3 - 5
5 - 7.5
Fan Shaft Size (in.)
1
1
1
1.1875
1.4375
1.4375
Motor Shaft Size (in.)
0.875
0.875
0.875
0.875
1.125
1.125
Center Distance (in.)
27.1
27.1
29.8
29.8
29.8
35.1
CONDENSER COIL
3
/
8
-in. OD, Enhanced Copper Tube, Aluminum Fins
Quantity Rows ... Fin/in.
6...16W
6...16W
6...16W
6...16W
5...16
6...16
Fin Block Size (H x L) (in.)
30 x 46
30 x 46
32 x 60
34 x 80
34 x 80
40 x 80
Face Area (sq ft)
9.58
9.58
13.33
18.89
18.89
22.2
Refrigerant Gas Inlet Connection
Size (in.)
0.625
0.625
0.875
0.875
1.125
(2).875
Refrigerant Liquid Connection
Size (in.)
0.5
0.5
0.625
0.625
0.625
(2).625
09XC
DISCHARGE
DUCT
INLET
DUCT
TO OUTSIDE
INSULATE IF THROUGH
CONDITIONED SPACE
HANGER
RODS
TO RAIN DRAIN
(REQUIRED IF RAIN
WILL ENTER UNIT)
TO REFRIGERANT
PIPING COMPRESSOR/
EVAPORATOR UNIT
09XC IN REMOTE APPLICATION WITH DUCTWORK
(Shown Suspended from Ceiling)