N92ESN: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
24
115-V Wiring
Furnace must have a 115-v power supply properly connected and
grounded.
NOTE:
Proper polarity must be maintained for 115-v wiring. If polarity
is incorrect, control LED status indicator light will flashes rapidly
(Status Code 10) and furnace will
NOT
operate.
Verify that the voltage, frequency, and phase correspond to that specified
on unit rating plate. Also, check to be sure that service provided by
utility is sufficient to handle load imposed by this equipment. Refer to
rating plate or
for equipment electrical specifications.
U.S.A. Installations
: Make all electrical connections in accordance with
the current edition of the National Electrical Code (NEC) NFPA 70 and
any local codes or ordinances that might apply.
Canada Installations
: Make all electrical connections in accordance
with the current edition of the Canadian Electrical Code CSA C22.1 and
any local codes or ordinances that might apply.
Use a separate, fused branch electrical circuit with a properly sized fuse
or circuit breaker for this furnace. See
specifications. A readily accessible means of electrical disconnect must
be located within sight of the furnace.
A190079
Fig. 32 – Typical Single-Stage Wiring Diagram
A190279
Fig. 33 – Field-Supplied External Electrical Box on Furnace Casing
Table 10 – Electrical Data
J-Box Installation
The J-Box must be used when field line voltage electrical connections
are made to the furnace wiring harness inside the furnace casing. The
J-Box cover is not required if a field-supplied external electrical box is
attached to the outside of the furnace casing. The field ground wire and
furnace main ground wire are grounded when the J-Box bracket is
attached to the furnace and the field ground wire and factory ground wire
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage.
Do not connect aluminum wire between disconnect switch and furnace.
.
115-V FIELD-
SUPPLIED
DISCONNECT
AUXILIARY
J-BOX
24-V
TERMINAL
BLOCK
THREE-WIRE
HEATING-ONLY
FIVE WIRE
NOTE 1
NOTE 2
FIELD-SUPPLIED
DISCONNECT
CONDENSING
UNIT
TWO
WIRE
FURNACE
C
O
N
T
R
O
L
R
G
COM
W
C
R
G
Y
GND
GND
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
208/230- OR
460-V
THREE
PHASE
208/230-V
SINGLE
PHASE
BLOWER DOOR SWITCH
WHT
BLK
WHT
BLK
NOTES:
Connect Y-terminal in furnace as shown for proper blower operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
W
Y
GND
THERMOSTAT
TERMINALS
1.
2.
3.
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE
FURNACE SIZE
VOLTS-
HERTZ-
PHASE
OPERATING VOLTAGE
RANGE
*
*. Permissible limits of the voltage range at which the unit operates satisfactorily.
MAXIMUM
UNIT
AMPS
UNIT
AMPACITY
†
†. Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load amps
MINIMUM
WIRE SIZE
AWG
MAXIMUM
WIRE
LENGTH
FT (M)
‡
‡. Time-delay type is recommended.
MAXIMUM
FUSE OR CKT
BKR AMPS
**
**. Length shown is as measured one way along wire path between furnace and service panel for maximum 2 percent voltage drop.
Maximum
Minimum
0401410
115-60-1
127
104
7.1
9.8
14
37 (11.5)
15
0401712
115-60-1
127
104
7.1
9.8
14
37 (11.5)
15
0601412
115-60-1
127
104
7.2
9.9
14
37 (11.4)
15
0601714
115-60-1
127
104
7.2
9.9
14
37 (11.4)
15
0801716
115-60-1
127
104
7.2
9.9
14
37 (11.4)
15
0802120
115-60-1
127
104
9.6
12.9
14
28 (8.7)
15
1002120
115-60-1
127
104
9.7
13.0
14
28 (8.7)
15
1002122
115-60-1
127
104
12.9
17.0
12
33 (10.3)
20
1202420
115-60-1
127
104
9.7
13.0
14
28 (8.7)
15
CAUTION
!
FURNACE MAY NOT OPERATE HAZARD
Failure to follow this caution may result in intermittent furnace
operation.
Furnace control must be grounded for proper operation or else control
will lock out. Control must remain grounded through green/yellow wire
routed to gas valve and manifold bracket screw.
WARNING
!
FIRE OR ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage.
High voltage field connections must be located in J-Box with furnace,
or in field supplied external disconnect mounted to furnace.
If field-supplied manual disconnect switch is to be mounted on furnace
casing side, select a location where a drill or fastener cannot damage
electrical or gas components.