10
PERFORMANCE DATA
DESCRIPTION
UNIT SIZE
060---14
080---14
080---20
100---20
120---20
Certified Temp Rise Range (
_
F)
Low
40—70
40—70
40—70
40—70
40—70
High
35—65
40—70
35—65
45—75
45—75
Certified Ext Static Pressure (ESP) (in. wc)
Heating
0.12
0.15
0.15
0.20
0.20
Cooling
0.50
0.50
0.50
0.50
0.50
Airflow CFM*
Heating Low
670 (735
{
)
910 (1000
{
)
870 (955
{
)
1060 (1165
{
) 1345 (1480
{
)
Heating High
1055
1390
1500
1525
1880
Cooling (Max)
1400
1395
1990
2000
2100
Output Capacity Btuh
}
(ICS)
Low
37,000
50,000
50,000
63,000
75,000
High
56,000
75,000
75,000
94,000
113,000
AFUE%
}
95.0
95.0
95.0
95.0
95.0
Input Btuh**
Low
39,000
52,000
52,000
65,000
78,000
High
60,000
80,000
80,000
100,000
120,000
* Airflow shown is for bottom only return---air supply with factory---supplied 1---in. washable filter(s). For air delivery above 1800 CFM, see Air Delivery table for
other options.
{
Low heat CFM when low---heat rise adjustment switch (SW1---3) on furnace control is used.
}
AFUE and capacity in accordance with U.S. Government DOE test procedures.
** Gas input ratings are certified for elevations to 2000 ft. For elevations above 2000 ft, reduce ratings 2% for each 1000 ft above sea level. In Canada, derate
the unit 5% for elevations from 2000 to 4500 ft above sea level.
58U
VB