Table 7 – Troubleshooting
FAULT/OPERATION DESCRIPTION
FLASH CODE
(Amber LED)
RESET TIME
(minutes)
Standby
ON, no flash
--- ---
Variable Capacity or Emergency Mode
1, pause
--- ---
Variable Speed Range Cutback
1 (2 sec ON), longer pause (1 second OFF)
--- ---
Communications Loss
16
N/A
Invalid Model
25
N/A
High Pressure Switch Open
31
15
Low Pressure Trip
32
15
Control Fault
45
N/A
Brownout Event
46
Revert to 5 min cycle delay
Lost Inverter Communications
48
Revert to 5 min cycle delay
230VAC Dropout---Reset Event
49
Revert to 5 min cycle delay
Outdoor Air Temp Sensor Fault
53
N/A
Suction Temp Sensor Fault
54
N/A
Coil Temp Sensor Fault
55
N/A
OAT---OCT Thermistor Out of Range
56
N/A
Suction Pressure Sensor Fault
57
N/A
Suction Thermistor Range Fault
58
N/A
Compressor Scroll Temp Out of Range Event
59
15
Compressor No Start*
62
15
Compressor Sump Heater Active
68
NA
Inverter / Compressor Internal Fault
69
5
Compressor Motor Temp Out of Range Event
71
5
Suction Over Temp Event
72
5
Inverter Temp Out of Range Event
75
5
Inverter Over Current Event
77
5
Compressor No---Pump Event
79
5
Suction Over Temp Lockout
82
4 Hours
Low Pressure Lockout for 4 Hours
83
4 Hours
High Pressure Lockout for 4 Hours
84
4 Hours
Compressor Temp Lockout
85
4 Hours
Compressor Lost Rotor or Temp Sensor Fault**
86
15
Inverter Temp Lockout
88
4 Hours
Inverter VDC---Out Over Voltage Event
91
15
Inverter VDC---Out Under Voltage Event
92
15
230VAC Under Voltage Event
93
15
230VAC Over Voltage Event
94
15
High Current Lockout
95
2 Hours
VDC Under Voltage Lockout
96
2 Hours
VDC Over Voltage Lockout
97
2 Hours
High Torque Event
98
10
High Torque Lockout
99
2 Hours
--- ---
OFF
N/A
* Fault code present software V6 and later