Carrier Infinity 25VNA Скачать руководство пользователя страница 13

13

Brown--Out Protection

If the line voltage is less than 187v for at least 4 seconds, the

contactor and fan relay are de--energized. Compressor and fan
operation are not allowed until voltage is a minimum of 190v. The

control will flash the appropriate fault code (see Table 7).

230V Line (Power Disconnect) Detection

If there is no 230v at the contactor when the indoor unit is powered

with a cooling or heating demand, the appropriate fault code is

displayed. Verify the disconnect is closed and 230v wiring is
connected to the unit.

Inverter Voltage Sensing

The control board senses the presence or absence of 230 V through

the feedback from inverter. The control monitors the high voltage
to the inverter. Voltage should be present anytime the contactor is

energized and voltage should not be present when the contactor is
de--energized.

Temperature Thermistors

Thermistors are electronic devices which sense temperature. As the

temperature increases, the resistance decreases. Thermistors are
used to sense outdoor air (OAT), coil temperature (OCT) and the

suction line thermistor (OST) located between the reversing valve
and the accumulator.
Refer to Table 4 and Fig. 14 for resistance values versus

temperature.

Table 4 – Resistance Values versus Temperature

TEMPERATURE

RESISTANCE (ohms)

25.0° C (77.0° F)

10.0 + / - 2.3%

0.0° C (32.0° F)

32.6 + / - 3.2%

-28.0° C (-18.4° F)

85.5 + / - 3.4%

0

10

20

30

40

50

60

70

80

90

0

20

40

60

80

100

120

TEMPERATURE (DEG. F)

RESISTANCE (KOHMS)

THERMISTOR CURVE

A91431

Fig. 14 -- Thermistor Resistance Versus Temperature

If the outdoor air or coil thermistor should fail, the control will
flash the appropriate fault code (see Table 7.)

IMPORTANT:

The outdoor air thermistor, coil thermistor and

suction thermistor should be factory mounted in the final
locations.

Check to ensure thermistors are mounted properly

(See Fig. 15, 16 and 17).

Thermistor Sensor Comparison

The control continuously monitors and compares the outdoor air
temperature sensor and outdoor coil temperature sensor to ensure

proper operating conditions. The comparison is:

S

In cooling if the outdoor air sensor indicates

10

_

F (

5.6

_

C)

warmer than the coil sensor (or) the outdoor air sensor indicates

20

_

F (

11

_

C) cooler than the coil sensor, the sensors are out

of range.

S

In heating

i

f the outdoor air sensor indicates

35

_

F (

19.4

_

C)

warmer than the coil sensor (or) the outdoor air sensor indicates

10

_

F (

5.6

_

C) cooler than the coil sensor, the sensors are out

of range.

If the sensors are out of range, the control will flash the appropriate
fault code as shown in Table 7.
The thermistor comparisons are not performed during low ambient
cooling or defrost operation.

Failed Thermistor Default Operation

Factory defaults have been provided in the event of failure of

outdoor air thermistor (OAT) and/or outdoor coil thermistor
(OCT).
If the OAT sensor should fail, low ambient cooling will not be

allowed and the one--minute outdoor fan off delay will not occur.
Defrost will be initiated based on coil temperature and time.
If the OCT sensor should fail, low ambient cooling will not be
allowed. Defrost will occur at each time interval during heating

operation, but will terminate after 5 minutes.
If there is a thermistor out--of--range error, defrost will occur at
each time interval during heating operation, but will terminate after

5 minutes.
Count the number of short and long flashes to determine the

appropriate flash code. Table 7 gives possible causes and actions
related to each error.

Outdoor Coil Thermistor

The outdoor coil thermistor is a 10Kohm resistor used for multiple
system operations. It provides the coil/liquid line temperature to

the heat pump board and user interface. Low ambient operation,
defrost initiation, defrost termination and assistance with OAT

temperature measurement of some of the functions. The sensor
must be securely mounted to the tube connecting the EXV and

distributor. See Fig. 15 for proper placement. See Table 4 for

proper resistances.

OAT Thermistor must be

locked in place with

spherical nib end facing

towards the front of the

control box

A11142

Fig. 15 -- OAT Thermistor Location (Bottom of Control Box)

A14303

Fig. 16 -- Outdoor Coil Thermistor (OCT) Attachment

(On Distributor Tube)

Содержание Infinity 25VNA

Страница 1: ...factory authorized kits or accessories when modifying this product Refer to the individual instructions packaged with the kits or accessories when installing Follow all safety codes Wear safety glass...

Страница 2: ...tructure and unit to absorb vi bration 6 When passing refrigerant tubes through the wall seal open ing with RTV or other pliable silicon based caulk see Fig 1 7 Avoid direct tubing contact with water...

Страница 3: ...tion to building Consult local codes governing rooftop applications Roof mounted units exposed to winds above 5 mph may require wind baffles Consult the Service Manual Residential Split System Air Con...

Страница 4: ...INJURY AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Use all...

Страница 5: ...LICATIONS Over 80 ft 24 38 m REQUIRED FOR SEA COAST APPLICATIONS Within 2 miles 3 22 km Installations with Radio Frequency Interference Concerns in the Range of 2 to 30 MHZ Crankcase Heater Standard S...

Страница 6: ...urface is avoided S Insulating the muffler with Armaflext tape is recommended EXTERIOR WALL VAPOR LINE MUFFLER TO DWELLING A11543 Fig 5 Muffler Installation A05227 Fig 6 Liquid Line Filter Drier Refri...

Страница 7: ...Fig 8 Line Power Connections Connect Control Wiring Connect to Infinity connections Only two wires AB to Infinity capable indoor unit furnace or fan coil is required Typical 4 wire ABCD may be connect...

Страница 8: ...arge re moval may be necessary 3 Fully open liquid and vapor service valves A11104 Fig 9 Required Charge Adjustment Calculated in UI 4 Set User Interface to operate cooling in CHARGING mode Charging m...

Страница 9: ...may not begin to cycle until about 40_F 4 4_C OAT The outdoor unit fan will cycle on and off based on outdoor coil temperature outdoor air temperature and suction pressure measurements to keep the com...

Страница 10: ...ize before declaring a properly charged system The use of a commercial charge metering device restrictor such as Imperial liquid low side charger model 535 C or Watsco ChargeFaster model CH200 is reco...

Страница 11: ...o be isolated in indoor coil and lineset Set desired time period Default time peri od for the procedure is 120 minutes 4 Select Start on UI to begin the pumpdown process Unit will begin running in sel...

Страница 12: ...ard controls the operation of the contactor TROUBLESHOOTING Systems Communication Failure If communication with the Infinity control is lost with the User Interface UI the control will flash the appro...

Страница 13: ...proper operating conditions The comparison is S In cooling if the outdoor air sensor indicates 10_F 5 6_C warmer than the coil sensor or the outdoor air sensor indicates 20_F 11_C cooler than the coil...

Страница 14: ...N ECM Fan Motor If verification of proper operation is required for the ECM motor used in this unit follow these steps 1 Verify that the 230v input to the transformer is present 2 Verify that the cont...

Страница 15: ...urnace or Fan Coil A12055 Fig 18 Infinity Furnace or Fan Coil Wiring with Communicating Variable Speed HP D C B A VS HP OAT G Y O W C HUM Furnace or Fan Coil C B A UT IL C LS O Y R G Y O W C R Convent...

Страница 16: ...PL5 PL3 HPS Utility Interface A11544 Fig 20 Variable Speed Control Board with optional Utility Relay CB MODEL PL8 FORCED DEFROST J2 1 BRN RED SEC1 SEC2 PWM2 PWM1 INVERTER PL1 PL2 RVS CC PL11 PL4 PL6 O...

Страница 17: ...p Out of Range Event 59 15 Compressor No Start 62 15 Compressor Sump Heater Active 68 NA Inverter Compressor Internal Fault 69 5 Compressor Motor Temp Out of Range Event 71 5 Suction Over Temp Event 7...

Страница 18: ...ow side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only com...

Отзывы: