background image

24VNA6 / 25VNA4: Service Manual

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

38

TXV Operation

The TXV is a metering device that is used in air conditioning and heat
pump  systems  to  adjust  to  changing  load  conditions  by  maintaining  a

preset  superheat  temperature  at  the  outlet  of  the  evaporator  coil.  The
volume of refrigerant metered through the valve seat is dependent upon
the following: 

1. Superheat  temperature  is  sensed  by  cap  tube  sensing  bulb  on

suction  tube  at  outlet  of  evaporator  coil.  This  temperature  is
converted  into  pressure  by  refrigerant  in  the  bulb  pushing
downward  on  the  diaphragm  which  opens  the  valve  via  the  push

rods.

2. The  suction  pressure  at  the  outlet  of  the  evaporator  coil  is

transferred  via  the  external  equalizer  tube  to  the  underside  of  the
diaphragm.  This is needed to account for the indoor coil pressure
drop.  Residential coils typically have a high pressure drop, which

requires this valve feature.

3. The pin is spring loaded, which exerts pressure on the underside of

the  diaphragm.  Therefore,  the  bulb  pressure  works  against  the
spring pressure and evaporator suction pressure to open the valve. 

If the load increases, the temperature increases at the bulb, which
increases the pressure on the top side of the diaphragm. This opens
the  valve  and  increases  the  flow  of  refrigerant.  The  increased

refrigerant  flow  causes  the  leaving  evaporator  temperature  to
decrease.  This lowers the pressure on the diaphragm and closes the
pin. The refrigerant flow is effectively stabilized to the load demand

with negligible change in superheat.

Accumulator

The accumulator is specifically designed to operate with Puron® or R22
respectfully; use only factory-authorized components. Under some light
load conditions  on  indoor coils,  liquid  refrigerant is present in suction
gas returning to compressor. The accumulator stores liquid and allows it
to boil off into a vapor so it can be safely returned to compressor. Since a
compressor  is  designed  to  pump  refrigerant  in  its  gaseous  state,
introduction of liquid into it could cause severe damage or total failure of
compressor.
The  accumulator  is  a  passive  device  which  seldom  needs  replacing.
Occasionally  its  internal  oil  return  orifice  or  bleed  hole  may  become
plugged. Some oil is contained in refrigerant returning to compressor. It
cannot boil off in accumulator with liquid refrigerant.  The bleed hole
allows a small amount of oil and refrigerant to enter the return line where
velocity of refrigerant returns it to compressor. If bleed hole plugs, oil is
trapped in accumulator, and compressor will eventually fail from lack of
lubrication. If bleed hole is plugged, accumulator must be changed. The
accumulator has a fusible element located in the bottom end bell. (See

Fig. 38

.)  This fusible element will melt at 430°F//221°C and vent the

refrigerant if this temperature is reached either internal or external to the
system.  If fuse melts, the accumulator must be replaced.
To change accumulator:

1. Shut off all power to unit.
2. Recover all refrigerant from system.
3. Break vacuum with dry nitrogen. Do not exceed 5 psig.

NOTE: 

Coil  may  be  removed  for  access  to  accumulator.  Refer  to

appropriate sections of Service Manual for instructions.

4. Remove accumulator from system with tubing cutter.
5. Tape ends of open tubing.

6. Scratch  matching  marks  on  tubing  studs  and  old  accumulator.

Scratch matching marks on new accumulator. Unbraze stubs from
old accumulator and braze into new accumulator.

7. Thoroughly  rinse  any  flux  residue  from  joints  and  paint  with

corrosion-resistant coating such as zinc-rich paint.

8. Install factory authorized accumulator into system with copper slip

couplings.

9. Evacuate and charge system.

Pour  and  measure  oil  quantity  (if  any)  from  old  accumulator.  If  more
than 20 percent of oil charge is trapped in accumulator, add new PVE oil
to compressor to make up for this loss. 

A88410

Fig. 38 – Accumulator

Vapor Injection Operation (5 Ton Models)

Some 25VNA4 and 24VNA6 models contain an additional refrigeration
circuit known as a vapor injection circuit. When active this circuit will
increase  the  capacity  of  the  outdoor  unit  with  a  minimal  increase  in

power consumption. The result is higher capacity at a higher efficiency.
This circuit is only active at extreme heating and cooling temperatures
and only in efficiency mode. 
The vapor injection circuit routes a portion of the subcooled liquid from
the  condenser  through  a  vapor  injection  EXV  (EXV-VI)  and  into  a

brazed-plate  heat  exchanger  (BPHX)  The  resulting  superheated  vapor
will  return  to  the  compressor  and  be  "injected"  into  the  mid  port.
Meanwhile subcooled liquid leaving the condenser is routed through the

other portion of the BPHX and is further subcooled before exiting to the
evaporator section of system, thus improving the capacity.

A200183

Fig. 39 – Vapor Injection Operation

CAUTION

!

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal injury.
Wear  safety  glasses,  protective  clothing,  and  gloves  when  handling
refrigerant.

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.
Before  installing,  modifying,  or  servicing  system,  main  electrical
disconnect switch must be in the OFF position. There may be more than
1 disconnect switch. Lock out and tag switch with a suitable warning

label. 

430

°

 FUSE

ELEMENT

A88410

 

BPHX

EXV-VI

COMPRESSOR

MID-PORT

DISCHARGE PORT

SUCTION PORT

CONDENSER

HX

EVAPORATOR

EX VALVE

Содержание Infinity 24VNA6

Страница 1: ...ons 9 Cooling Control 9 Heating Control 9 Super Heat Control 9 Defrost Mode 9 Defrost Interval 10 Defrost Process 10 PCM Indicators and Display Operation 10 Status Light 10 Comm Light 10 VFD Comm Ligh...

Страница 2: ...et the HP unit achieves a Seasonal Energy Efficiency Ratio SEER of up to 24 and up to 13 Heating Seasonal Performance Factor HSPF and the AC achieves up to 26 SEER To ensure all of the above technolog...

Страница 3: ...not controlled relative to the phase of the power provided by the transformer in the indoor equipment Rh Wiring requirements in this manual do not connect Rc and Rh together For any non standard wirin...

Страница 4: ...any time specifications and designs without notice and without obligations 4 Fig 2 Compressor Fan Sub System Diagram Fig 3 Wiring Diagram 24VNA6 25VNA4 Model sizes 2 5 tons 208 230 1 FILTER REACTOR S...

Страница 5: ...nding on air movement requirements The fan on board VFI will automatically limit fan speed if fan load current reaches operating limits Crankcase Heater Some equipment has a crankcase heater band inst...

Страница 6: ...P Swtich Settings IMPORTANT The R Rc signal on the PCM comes from the transformer in the equipment The phase of this transformer connection is not controlled relative to the phase of the transformer i...

Страница 7: ...he right to change at any time specifications and designs without notice and without obligations 7 A200049 A200044 Fig 7 PCM Control Board Bluetooth Service Port Status LED Yellow CCN Communication LE...

Страница 8: ...valve for regulating refrigerant flow during heating operation The EXV H is driven by a 12VDC 2 phase uni polar stepper motor The EXV H has a 475 step range between fully closed and fully open The PCM...

Страница 9: ...oor equipment and under charged or over charged systems Sump Heat When the compressor is not running the compressor sump may need to be heated to prevent liquid refrigerant from collecting in the sump...

Страница 10: ...eceived within the last 2 minutes and the equipment is operating in emergency communicating mode VFD Comm Light The VFD Comm light blinks every time there is a message received from the VFD If a messa...

Страница 11: ...IOR TO TOUCHING ELECTRICAL COMPONENTS Verify less than zero 0 vdc voltage at VFD connections shown on cover Table 2 VFD LED Indicator Functions LED Identification Color Function R1 Red Used to indicat...

Страница 12: ...emand is present and until pressure equalization is complete if necessary and the fan has successfully started Diagnostic Code Recall The Diagnostic Code Recall mode will be enabled if the Forced Defr...

Страница 13: ...hutdown occurs the next operating cycle will operate at 25 less capacity Each fault after that will reduce capacity by an additional 25 Each hour of operation without a fault will increase the availab...

Страница 14: ...at the bottom of the control box with the sensing element protruding through the bottom of the control box to be in contact with the outside air The OAT thermistor location is illustrated in Fig 13 A...

Страница 15: ...are displayed as critical faults even during cooling operation so that service may be performed before heating is required Pressure Sensors The equipment contains two pressure transducers Suction Pres...

Страница 16: ...VI valve bodies are different for different models the stator for all valves have the same electrical properties The EXV coil resistance should fall between 43 and 49 ohms when measured from common t...

Страница 17: ...d on board header Also inspect and repair any wire damage on harness If no green or red led is present on the Bluetooth module disconnect harness at the Bluetooth module and check for 18 30 VAC betwee...

Страница 18: ...ed with new undamaged part LLS are field installed accessories Check LLS wiring for shorts See wiring diagram for fuse size and location Code 31 11 Compressor High Pressure Limiting Code 31 58 Compres...

Страница 19: ...sor The PEV is included to ensure compressor will never start against a high pressure differential This fault will become active if a demand exists and the PEV is not successful in lowering pressure d...

Страница 20: ...f OAT thermistor is higher than the electrical circuit is capable of measuring this fault will be generated Measure resistance value of thermistor at the PCM connector If value is above 465kohm look f...

Страница 21: ...Code 57 42 P1 Shorted Lockout Code 58 02 P2 Shorted Fault Code 58 42 P2 Shorted Lockout Pressure transducers are dynamically assigned based on their relative values within PCM software This feature a...

Страница 22: ...day the EXV VI will test itself by operating to a known position as the valve does not have the capability to feedback actual position The PCM software must know the starting point and then count whe...

Страница 23: ...PCM reset the VFD and restart if demand is still present The system should resume operation after 5 minute compressor protection time delay expires 4 occurrences of code 82 15 within a 1 hour period w...

Страница 24: ...t in 86 46 malfunction which has a 1 hour lockout When code 86 06 is set VFD will shut down compressor and fan and re initialize in an attempt to re establish communication between VFD and PCM Inspect...

Страница 25: ...res Three occurrences of code 88 36 within a 4 hour period will result in 88 76 malfunction and 4 hour lockout While this fault or malfunction is active the unit is inoperable This malfunction once se...

Страница 26: ...e 33 15 55 Compressor Low Discharge Limit 34 11 58 Compressor High Temperature Limit 35 11 58 Compressor High Compression Limit 36 15 55 Compressor Low Compression Limit 38 13 53 Compressor Starting E...

Страница 27: ...12 Compressor Current Limit 2 Speed Reduction 15 55 Compressor Current Limit 3 Shutdown 16 56 Compressor Current Limit 4 Shutdown 57 Compressor Underspeed Shutdown 84 11 58 VFD Heat Sink Overtemp Shut...

Страница 28: ...nd designs without notice and without obligations 28 A200187 Fig 19 2T 3T Control Box A200188 Fig 20 4T 5T Control Box Note 4T VFD similar not exact 5T reactors have additional chokes to meet FCC requ...

Страница 29: ...otice and without obligations 29 A200191 Fig 23 2 3T VFD Connections VFD control relay and LED Fan motor connections VFD to PCM comm connection DC DC terminals Fan motor fuse Compressor UVW connection...

Страница 30: ...192 Fig 24 4 5T VFD Connections Note 4T uses separate terminals VFD to PCM comm connection Fan motor connections Compressor UVW connections DC DC terminals Reactor connection Filter board input VFD co...

Страница 31: ...24VNA6 25VNA4 Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 31 A200193 Fig 25 PCM used on all models...

Страница 32: ...designs without notice and without obligations 32 A200194 Fig 26 Bluetooth Module used on all models A200195 Fig 27 Fan Motor used on all models A200196 Fig 28 2 3 4T Rector Note 4Tuses 2 reactors A2...

Страница 33: ...rer reserves the right to change at any time specifications and designs without notice and without obligations 33 A200199 Fig 31 PCM to Bluetooth Module Comm Cable used on all models A200200 Fig 32 VF...

Страница 34: ...24VNA6 25VNA4 Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 34 A200201 Fig 33 PCM Wiring Diagram...

Страница 35: ...brazing alloy is used on copper to brass copper to steel or copper to copper Flux is required when using silver brazing alloy Do not use low temperature solder 3 Fluxes should be used carefully Avoid...

Страница 36: ...flow of refrigerant in system This reversing valve device is easy to troubleshoot and replace The reversing valve solenoid can be checked with power off with an ohmmeter Check for continuity and shor...

Страница 37: ...where acid might occur such as burnout Heat pump units must have the drier installed between the compressor and accumulator only Remove after 10 hours of operation Never leave suction line filter drie...

Страница 38: ...ventually fail from lack of lubrication If bleed hole is plugged accumulator must be changed The accumulator has a fusible element located in the bottom end bell See Fig 38 This fusible element will m...

Страница 39: ...igerant is leaking at that point A simple and inexpensive method of testing for leaks is to use soap bubbles See Fig 41 Any solution of water and soap may be used Soap solution is applied to all joint...

Страница 40: ...idential HVAC training resources that help strengthen careers and businesses We believe in providing high quality learning experiences both online and in the classroom Access My Learning Center with y...

Отзывы: