Fig. 12 — Enclosure with Single or Dual Runout

Fig. 13 — Single or Dual Runout (with Kickstrip)

SINGLE  OR  DUAL  RUNOUT  WITH  KICKSTRIP  (SEE

FIG. 13)
1. Drill one 

3

/

16

-in. hole for attaching runout.

2. Cut runout enclosure and kickstrip to desired length; join

with No. 8 sheet metal screws.

3. Fit runout and kickstrip into slots of 2 end frames.
4. Hang  assembly  on  wall  mounting  strip  and  adjacent  to

unit enclosure.

5. Attach end frame to unit enclosure with one No. 8 sheet

metal screw (field-supplied).

Step 8 — Balance System (see Fig. 14)

1. Remove  construction  debris  from  unit.  Remove  protec-

tive plastic from thermostat cover.

2. Units are shipped with plenum damper wide open. Turn

damper adjustment screw clockwise to close damper and
decrease  nozzle  pressure  to  design  value. Two  or  three

runs may be necessary to obtain proper balance.

Note that 36SL,SM,SC,ST have different nozzle types.
Maximum allowable plenum pressure is 5-in. wg.

Fig. 14 — Pressure Measurements

Содержание INDUCTION AIR TERMINALS 36S

Страница 1: ...nclosure 7 Coil Reversal 8 GENERAL These units are controlled by varying water flow through coil Follow installation steps in sequence suggested Each step in cludes figure s and procedures required fo...

Страница 2: ...8 Install two No 10 24 bolts factory supplied through two No 10 24 speed nuts provided These or any other suitable means will be used for unit leveling 9 Mark base unit vertical center line on unit 1...

Страница 3: ...1 Position recirculation grille mounting frame using holes provided Install recirculation grille panel to grille frame 2 Install discharge grille frame and removable grille sec tions Field fabricated...

Страница 4: ...3 16 in holes for attaching runout 2 Cut runout enclosure and enclosure panel to desired length 3 Fit runout enclosure into slots of one end frame 4 Insert enclosure panel into end frame slots 5 Fit s...

Страница 5: ...sts on lower flange of end frame 6 Hang assembly on wall mounting strip and adjacent to unit enclosure Stiffener bracket lip must support bottom of runout 7 Attach end frame to unit enclosure with two...

Страница 6: ...d adjacent to unit enclosure 5 Attach end frame to unit enclosure with one No 8 sheet metal screw field supplied Step 8 Balance System see Fig 14 1 Remove construction debris from unit Remove protec t...

Страница 7: ...ve packing 2 Remove four No 10 16 x 1 2 in screws taped to inside of enclosure end panel 3 Remove Z bars from shipping position fasten to unit with screws and clips provided Install ceiling mounting p...

Страница 8: ...S 1SI Carrier Corporation 2018 Coil Reversal see Fig 17 Do not reverse coils having vent fittings except 36SL SM SC ST To reverse coils without vent fittings 1 Remove sheet metal screws fastening cond...

Отзывы: