10. Clean flame sensor with fine steel wool

11. Remove old sealant from center panel and collector box flange

and apply new sealant to collector box flange and reinstall on
center panel, making sure all 8 screws are secure.

NOTE:

A releasing agent such as PAM cooking spray or equiva-

lent (must not contain corn or canola oil, aromatic or halogenated
hydrocarbons or inadequate seal may occur) and RTV sealant
(G.E. 162, 6702, or Dow-Corning 738) are needed before starting
installation. DO NOT substitute any other type of RTV sealant.
G.E. 162 (P771-9003) is available through RCD in 3-oz tubes.

12. Reinstall relief box and inducer assembly.

NOTE:

If inducer assembly gasket is damaged, use RTV sealant

to seal inducer assembly to collector box.

13. Reconnect wires to the following components:

a. Blocked vent safeguard switch.

b. Inducer motor.

c. Pressure switch.

d. Limit overtemperature switch(es).

e. Gas valve.

f. Hot surface ignitor.

g. Flame-sensing electrode

h. Flame rollout switch(es), if applicable.

14. Reinstall vent connector to furnace flue collar. After fully

assembling vent connector to furnace flue collar, securely
fasten vent connector to flue collar with 2 field-supplied,
corrosion-resistant, sheet metal screws located 180 degrees
apart and midway up the collar.

15. Turn electrical power and gas to ON.

16. Set thermostat and check furnace for proper operation.

17. Verify blower airflow and speed changes between heating and

cooling.

18. Check for gas leaks.

Never use a match or other open flame to check for gas leaks.
Use a soap-and-water solution. A failure to follow this
warning could result in fire, personal injury, or death.

19. Replace control door.

Step 4—Electrical Controls and Wiring

There may be more than 1 electrical supply to unit. Check
accessories and cooling unit for additional electrical supplies.

The electrical ground and polarity for 115-v wiring must be
maintained properly. Refer to Fig. 5 for field wiring information
and to Fig. 6 for furnace wiring information.

NOTE:

If the polarity is not correct, the STATUS LED on the

control will flash rapidly and prevent the furnace from heating.
The control system also requires an earth ground for proper
operation of the control and flame-sensing electrode.

The 24-v circuit contains an automotive-type, 3-amp fuse located
on the control. (See Fig. 7.) Any shorts of the 24-v wiring during
installation, service, or maintenance will cause this fuse to blow. If
fuse replacement is required, use ONLY a 3-amp fuse. The control
LED will display status code 24 when fuse needs to be replaced.

With power to the unit disconnected, check all electrical connec-
tions for tightness. Tighten all screws on electrical connections. If
any smoky or burned connections are found, disassemble the
connection, clean all parts, strip wire, and reassemble properly and
securely.

Reconnect electrical power to the unit and observe unit through 1
complete operating cycle. Electrical controls are difficult to check
without proper instrumentation; if there are any discrepancies in
the operating cycle, contact your dealer and request service.

The control in this furnace is equipped with an LED status light to
aid in installation, servicing, and troubleshooting. It can be viewed

Fig. 5–Heating and Cooling Application Wiring Diagram

A98521

115-V FIELD-

SUPPLIED

DISCONNECT   

AUXILIARY
J-BOX   

24-V

TERMINAL

BLOCK  

THREE-WIRE

HEATING-ONLY

FIVE WIRE

   

NOTE 1

NOTE 2

FIELD-SUPPLIED
DISCONNECT

CONDENSING
UNIT   

TWO
WIRE
   

FURNACE

C
O
N

T

R
O

L

R

G

C

W

C

R

G

Y

GND

GND   

FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING   

208/230- OR
460-V 
THREE
PHASE   

208/230-V
SINGLE
PHASE   

BLOWER DOOR SWITCH  

WHT   

BLK   

WHT   

BLK   

NOTES:

Connect Y-terminal in furnace as shown for proper blower operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.

W

Y

GND

THERMOSTAT
TERMINALS  

1.
2.
3.

5

Содержание INDUCED COMBUSTION 58YAV

Страница 1: ...hen you see this symbol on the furnace and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION ...

Страница 2: ...nsult your local dealer as to proper frequency of maintenance and availability of a maintenance contract Never store anything on near or in contact with furnace such as 1 Spray or aerosol cans rags brooms dust mops vacuum cleaners or other cleaning tools 2 Soap powders bleaches waxes or other cleaning com pounds plastic or plastic containers gasoline kerosene cigarette lighter fluid dry cleaning f...

Страница 3: ...d not be dropped or bent as balance will be affected 8 If a greasy residue is present on blower wheel remove wheel from the blower housing and wash it with an appropriate degreaser To remove wheel a Mark blower wheel location on shaft before disassembly to ensure proper reassembly b Loosen setscrew holding blower wheel on motor shaft NOTE Mark blower mounting arms motor and blower housing so motor...

Страница 4: ...itor See Fig 3 for correct ignitor location 9 Using field provided small wire brush steel spring cable reversible electric drill and vacuum cleaner clean cells as follows a Assemble wire brush and steel spring cable 1 Use 48 in of 1 4 in diameter high grade steel spring cable commonly known as drain clean out or Roto Rootert cable 2 Use 1 4 in diameter wire brush commonly known as 25 caliber rifle...

Страница 5: ... must be maintained properly Refer to Fig 5 for field wiring information and to Fig 6 for furnace wiring information NOTE If the polarity is not correct the STATUS LED on the control will flash rapidly and prevent the furnace from heating The control system also requires an earth ground for proper operation of the control and flame sensing electrode The 24 v circuit contains an automotive type 3 a...

Страница 6: ...C CONDUCTOR ON PCB FIELD WIRING TERMINAL FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE L1 L2 L1 BLWR HI LO TO 115VAC FIELD DISCONNECT NOTE 4 EQUIPMENT GROUND SPARE 2 HEAT SPARE 1 COOL NOTE 7 COM HSIR EAC 1 START OL COM HI MED HI MED LO LO BLWM SCHEMATIC DIAGRAM NATURAL GAS PROPANE EAC 2 1 1 HSI 2 PL5 2 PL2 3 PL3 PR2 115VAC PR1 TRAN 24VAC 1 2 IDR TEST TWIN FU1 NOTE 6 CAP L2 PL1 8 FSE 9...

Страница 7: ...s and retrieval request is ignored 2 When above items have been completed the following will occur a LED flashes a status code 4 times Record this status code for further troubleshooting b Inducer motor starts and continues to run the entire component test c Hot surface ignitor is energized for 15 sec then de energized d Main blower operates at heating speed for 10 sec then turns off e Main blower...

Страница 8: ...lame roll out switch requires manual reset Check for Defective blower motor or capacitor Dirty filter or restricted duct system Loose blower wheel Defective switch or connections Inadequate combustion air supply Flame Roll out Switch or fuse link open Open Flame Roll out Switch or fuse link Manual reset or replace IGNITION PROVING FAILURE Control will try three more times before lockout 14 occurs ...

Страница 9: ...idly and test request will be ignored e Component Test will function as described in item 2 above f Check LED status g If LED status indicates proper operation RELEASE BLOWER ACCESS DOOR SWITCH replace blower access door and replace control access door WIRING DIAGRAMS Refer to Fig 5 6 and 7 for the 58YAV furnace wiring diagrams TROUBLESHOOTING Refer to service label See Fig 8 The Troubleshooting G...

Страница 10: ...ill start and run for the entire component test The HSI blower motor heat speed and blower motor cool speed will run for 10 15 sec each Determine status code The status code is a 2 digit number with the first digit determined by the number of short flashes and the second digit by the number of long flashes Was there a previous fault code other than No 11 Does control respond to W Y or G 24 vac the...

Страница 11: ...ed while gas valve was de energized Inducer will run until fault is cleared Check for Stuck open gas valve solenoid or leak Defective control center 23 PRESSURE SWITCH WILL NOT OPEN Check for Disconnected or obstructed pressure tubing Defective pressure switch 24 LOW VOLTAGE FUSE IS OPEN Check for Short in low voltage wiring including thermostat leads shorting to ductwork or furnace cabinet Discon...

Страница 12: ...231 58yav3sm Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 6a 8a PC 101 Catalog No 535 771 Printed in U S A Form 58YAV 3SM Pg 12 10 00 Replaces 58YAV 2SM ...

Отзывы: