FZ4ANP: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

2

A07565

Fig. 1 – Slope Coil Unit in Upflow Application

A07566

Fig. 2 – Slope Coil in Horizontal Left Application (Factory Configuration)

DOWNFLOW INSTALLATION

In this application, field conversion of the evaporator is required using

accessory downflow kit along with an accessory base kit. Use fireproof

resilient gasket, 1/8 to 1/4-in (3 to 6 mm) thick, between duct, unit, and

floor.

NOTE: 

To convert units for downflow applications, refer to Installation

Instructions supplied with kit for proper installation. For slope fan coils,

use  kit  Part  No.  KFADC0201SLP.  For  A-coils,  use  kit  Part  No.

KFADC0401ACL. Use fireproof resilient gasket, 1/8  to 1/4-in (3 to 6

mm) thick, between duct, unit, and floor.

NOTE: 

Gasket  kit  number  KFAHD0101SLP  is  also  required  for  all

downflow applications to maintain low air leak/low sweat performance.

HORIZONTAL INSTALLATION

Units must not be installed with access panels facing up or down. All

other  units  are  factory  built  for  horizontal  left  installation  (

Fig. 2

  and

Fig. 3

). When suspending unit from ceiling, dimples in casing indicate

suitable location of screws for mounting metal support straps (

Fig. 2

).

For horizontal applications having high return static  and humid return

air, the Water Management Kit, KFAHC0125AAA, may need to be used

to assist in water management.

A COIL

UNITS

POWER ENTRY

OPTIONS

LOW VOLT
ENTRY
OPTIONS

FIELD MODIFIED
SIDE RETURN
LOCATION FOR
SLOPE COIL
UNITS ONLY

FIELD SUPPLIED
RETURN PLENUM

UPFLOW/DOWNFLOW

SECONDARY DRAIN

UPFLOW/DOWNFLOW

PRIMARY DRAIN

UNIT

     018, 024

025 - 030

A

12" (305 mm)

17" (432 mm)

A

1.5" (38 mm) 

   2.5"
(64 mm) 

19" (483 mm)

FIELD SUPPLIED
SUPPLY DUCT

UPFLOW/DOWNFLOW

SECONDARY DRAIN

UPFLOW/DOWNFLOW

PRIMARY DRAIN

     036

19" (483 mm)

018 - 048  21" (533 mm) FRONT SERVICE
060 - 060  24" (610mm)  CLEARANCE

UNIT

FIELD
SUPPLIED
HANGING
STRAPS

LOW VOLT
ENTRY
OPTIONS

POWER
ENTRY OPTIONS

SECONDARY
DRAIN

018-048   21" (533 mm)
060-060   24" (610 mm) 
FRONT SERVICE
CLEARANCE
(FULL FACE
OF UNIT)

SECONDARY
DRAIN

A-COIL

HORIZONTAL LEFT

PRIMARY
DRAIN

PRIMARY
DRAIN

1.75" (44 mm) 
FILTER ACCESS
CLEARANCE

CAUTION

!

PRODUCT OR PROPERTY DAMAGE HAZARD

Failure to follow this warning caution may result in product or property

damage. 

The conversion of the fan coil to downflow requires special procedures

for  the  condensate  drains  on  both A-coil  and  Slope-coil  units.  The

vertical  drains  have  an  overflow  hole  between  the  primary  and

secondary drain holes. This hole is plugged for all applications except

downflow, and must be used for downflow.  During conversion process,

remove plastic cap covering vertical drains only and discard. Remove

plug  from  overflow  hole  and  discard.  At  completion  of  downflow

installation, caulk around vertical pan fitting to door joint to retain low

air leak performance of the unit.

Содержание FZ4ANP

Страница 1: ...s 5 through 30kW See Product Data literature for all available accessory kits HEATER PACKAGES This unit may or may not be equipped with an electric heater package For units not equipped with factory i...

Страница 2: ...mid return air the Water Management Kit KFAHC0125AAA may need to be used to assist in water management A COIL UNITS POWER ENTRY OPTIONS LOW VOLT ENTRY OPTIONS FIELD MODIFIED SIDE RETURN LOCATION FOR S...

Страница 3: ...f Units with A Coils 1 Remove blower and coil access panels Fig 5 2 Remove metal clip securing fitting panel to condensate pan Remove fitting panel 3 Remove 2 snap in clips securing A coil in unit 4 S...

Страница 4: ...ertical condensate pan 15 Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating MANUFACTURED HOUSING AND MOBILE HOME APPLICATIONS 1 Fan coil unit must be se...

Страница 5: ...ance with the NEC and any local codes or ordinances that may apply Use copper wire only The unit must have a separate branch electric circuit with a field supplied disconnect switch located within sig...

Страница 6: ...ay also be accomplished by using grounding lugs provided in control box MINIMUM CFM AND MOTOR SPEED SELECTION The fan speed selection is done at the motor connector Units with or without electric heat...

Страница 7: ...line Finally caulk around the lines where they exit the fitting to retain the low leak rating of the unit Units are equipped with primary and secondary 3 4 in FPT drain connections For proper condensa...

Страница 8: ...er motor When G is de energized there is a 90 second delay before relay opens COOLING MODE Thermostat energizes R to G R to Y and R to O heat pump only G energizes fan relay on PCB which completes cir...

Страница 9: ...placement or cleaning on a monthly basis CAUTION PRODUCT DAMAGE HAZARD Failure to follow this caution may result in poor unit performance and or product damage Never operate unit without a filter Fact...

Страница 10: ...cfm ton on 048 061 size could result in condensate blowing off coil or splashing out of drain pan Table 4 Airflow Performance CFM MODEL SIZE BLOWER SPEED 0 10 0 20 0 30 0 40 0 50 0 60 FZ4A 024 Tap 5 9...