Carrier FV4C Скачать руководство пользователя страница 9

9

PRODUCT DAMAGE HAZARD

Failure to follow this caution may result in product or property

damage.
Wrap a wet cloth around rear of fitting to prevent damage to

TXV and factory--made joints

.

CAUTION

!

4. Evacuate coil and tubing system to 500 microns using deep

vacuum method.

Procedure 6 — CONDENSATE DRAIN

To connect drains the cap openings must be removed. Use a knife

to start the opening near the tab and using pliers, pull the tab to
remove the disk. Clean the edge of the opening if necessary and

install the condensate line. Finally caulk around the lines where

they exit the fitting to retain the low leak rating of the unit.

UNIT OR PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in product or

property damage.
The conversion of the fan coil to downflow requires special

procedures for the condensate drains on both A--coil and

slope units. The vertical drains have an overflow hole

between the primary and secondary drain holes. This hole is

plugged for all applications except downflow, but must be

used for downflow. During the conversion process, remove

the plastic cap covering the vertical drains only and discard.

Remove the plug from the overflow hole and discard. At

completion of the downflow installation, caulk around the

vertical pan fitting to door joint to retain the low air leak

performance of the unit.

CAUTION

!

Units are equipped with primary and secondary 3/4--in. (19mm)

FPT drain connections. For proper condensate line installation see
Fig. 2, 4, 5, 6, and 8.
To prevent property damage and achieve optimum drainage
performance, BOTH primary and secondary drain lines should be

installed and include properly--sized condensate traps. (See Fig. 14
and 16.) Factory--approved condensate traps are available. Be sure

to install plastic push--in plugs in unused condensate drain fittings.

It is recommended that PVC fittings be used on the plastic
condensate pan. Do not over--tighten. Finger--tighten plus 1--1/2

turns. Use pipe dope.

2” MIN

(51 mm)

UNIT

2” MIN

(51 mm)

A03002

Fig. 14 -- Recommended Condensate Trap

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in product or property

damage.
Shallow running traps are inadequate and DO NOT allow proper

condensate drainage. (See Fig. 15.)

CAUTION

!

DO NOT USE SHALLOW RUNNING TRAPS!

A03013

Fig. 15 -- Insufficient Condensate Trap

NOTE

: When connecting condensate drain lines avoid blocking

filter access panel. Prime both primary and secondary condensate
traps after connecting to drain pan.

NOTE

: If unit is located in or above a living space where damage

may result from condensate overflow, a field--supplied external
condensate pan should be installed underneath the entire unit, and a
secondary condensate line (with appropriate trap) should be run
from the unit into the pan.
Any condensate in this external condensate pan should be drained

to a noticeable place. As an alternative to using an external
condensate pan, some localities may allow the use of a separate

3/4--in. (19mm) condensate line (with appropriate trap) to a place

where the condensate will be noticeable. The owner of the structure
must be informed that when condensate flows from the secondary

drain or external condensate pan, the unit requires servicing, or
water damage will occur.
Install traps in the condensate lines as close to the coil as possible.
(See Fig. 16.) Make sure that the outlet of each trap is below its

connection to the condensate pan to prevent condensate from

overflowing the drain pan. Prime all traps, test for leaks, and
insulate traps if located above a living area.

FV4

C

 

 

 

Содержание FV4C

Страница 1: ...70 In Canada refer to the current editions of the Canadian Electrical Code CSA C22 1 Recognize safety information When you see this symbol on the unit and in instructions or manuals be alert to the p...

Страница 2: ...ng and or living area building codes may require a field supplied secondary condensate pan to be installed under the entire unit Some localities may allow the alternative of running a separate seconda...

Страница 3: ...DRAIN 1 3 4 44 mm FILTER ACCESS CLEARANCE A09323 Fig 3 Slope Coil in Horizontal Left Application Factory Ready A B C FACTOR Y SHIPPED HORIZONTAL LEFT APPLICATION AIR SEAL ASSEMBLY HORIZONTAL DRAIN PA...

Страница 4: ...ting metal support straps See Fig 4 D Horizontal Right Conversion of Units with Slope Coils PROPERTY DAMAGE HAZARD Failure to follow this caution may result in property damage Gasket kit number KFAHD0...

Страница 5: ...n knockouts on right side of coil access panel 12 Remove 2 oval coil access panel plugs and reinstall into holes on left side of coil access panel and fitting panel 13 Install condensate pan fitting c...

Страница 6: ...ctric heater is installed use heat resistant material for flexible connector between ductwork and unit at discharge connection Ductwork passing through unconditioned space must be insulated and covere...

Страница 7: ...e heater operation When additional heater staging is desired using outdoor thermostats or Intelligent Heat Staging remove Jumper J2 on PCB to enable staging Connect low voltage leads to thermostat and...

Страница 8: ...pump defrost cycle A corporate thermostat in conjunction with an outdoor sensor can be used to lock out supplemental heat above 40_F 4_C Refer to thermostat instructions for details If a non corporate...

Страница 9: ...See Fig 14 and 16 Factory approved condensate traps are available Be sure to install plastic push in plugs in unused condensate drain fittings It is recommended that PVC fittings be used on the plast...

Страница 10: ...STEM TYPE AC HP CFM ADJUST ON OFF DELAY CONTINUOUS FAN MED HI YEL LO AUX1 HUM1 AUX2 24VAC GRY HUM2 YEL WHT BLK ORN BLU VIO 0 15 875 0 10 675 0 90 30 90 0 0 0 5 625 TM A B C D E F KW CFM LOW VOLTAGE TE...

Страница 11: ...connector to MED 80 cooling mode airflow 3 HI speed move connector of HI 100 cooling mode air flow See Fig 17 F as indicated G Low Voltage Circuit Fusing and Reference The low voltage circuit is fuse...

Страница 12: ...y falls to a level which causes the humidistat to close its contacts When the contacts close the airflow will return to 100 of the selected cooling airflow To activate this mode remove Jumper J1 and w...

Страница 13: ...ltage present at each pin on 12 pin plug PL 1 See Table 7 for pin number on 16 pin plug which should have voltage when Easy Select Board screw terminals have 24vac C Use following procedure to check c...

Страница 14: ...ns is within sight from and is readily accessible from the unit Disconnect all electrical power to unit before performing any maintenance or service on it WARNING The minimum maintenance requirements...

Страница 15: ...volts and with 10KW heater and filter installed 4 Airflows shown are at standard air conditions Table 4 FV4C Fan Coil Airflow Delivery CFM in Heat Pump Only Heating Mode OPERATING MODE UNIT SIZE OUTD...

Страница 16: ...0 1350 1350 42 000 1140 1270 1460 1350 1350 1460 1525 1525 1525 48 000 1305 1450 1665 1350 1450 1665 1525 1525 1665 1750 1750 1750 60 000 1630 1810 2085 1630 1810 2085 1630 1810 2085 1750 1810 2085 NO...

Страница 17: ...be 400 psig DOT 4BA400 or DOT BW400 S Puron systems should be charged with liquid refrigerant Use a commercial type metering device in the manifold hose when charging into suction line with compresso...

Страница 18: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 05 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Отзывы: