background image

CAUTION: A brazing shield MUST be used when tubing sets are being brazed to the unit connections to prevent

damage to the unit surface and condensate pan fitting caps. Failure to follow this CAUTION could result in minor personal
injury or product and property damage.

Units have sweat suction and liquid tube connections. Make suction tube connection first.

1. Cut tubing to correct length.

2. Insert tube into sweat connection on unit until it bottoms.

3. Braze connection using silver bearing or non-silver bearing brazing materials. Do not use solder (materials which melt below 800°F).

Consult local code requirements.

Fig. 9—FV4B Fan Coil Wiring with 1-Speed Air Conditioner

A98477

O/W2

Y1/W2

W/W1

G

R

W2

Y1

INDOOR CONTROL

FAN COIL

1-SPEED

AIR CONDITIONER

W1

G

C

Y

C

DHUM

HUM

B

S1

S2

Y/Y2

R

O

C

DH

HEAT STAGE 2

N/A

HEAT STAGE 1

COOL STAGE 1

 FAN

24 VAC HOT

24 VAC COMM

DEHUMIDIFY

HUMIDIFY

N/A

OUTDOOR

SENSOR

CONNECTION

Y/Y2

HUMIDIFIER

(24 VAC)

OUTDOOR 

SENSOR

REMOVE J2 JUMPER
FOR HEAT STAGING

REMOVE 
J1 JUMPER 
FOR 
DEHUMIDIFY
MODES

Fig. 10—FV4B Fan Coil Wiring with 2-Speed Air Conditioner

A98478

O/W2

W/W1

Y1/W2

G

R

W2

W1

INDOOR CONTROL

FAN COIL

2-SPEED

AIR CONDITIONER

Y1

G

C

Y2

R

Y1

C

DHUM

HUM

B

S1

S2

Y/Y2

R

O

C

DH

HEAT STAGE 2

HEAT STAGE 1

COOL STAGE 1

COOL STAGE 2

 FAN

24 VAC HOT

24 VAC COMM

DEHUMIDIFY

HUMIDIFY

N/A

OUTDOOR

SENSOR

CONNECTION

Y/Y2

HUMIDIFIER

(24 VAC)

OUTDOOR 

SENSOR

REMOVE J2 JUMPER
FOR HEAT STAGING

REMOVE 
J1 JUMPER FOR
DEHUMIDIFY
MODES

—8—

Содержание FV4B

Страница 1: ...work gloves Use quenching cloth for brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions attached to the unit Consult local buildi...

Страница 2: ...orizontal left applications as factory shipped See Fig 2 4 and 8 Units can be installed for horizontal right applications with field modifications Units may be converted for downflow applications usin...

Страница 3: ...ide of unit and reinstall on coil support rail on right side of unit Fig 2 Slope Coil Unit in Upflow Application A00091 A COIL UNITS POWER ENTRY OPTIONS LOW VOLT ENTRY OPTIONS FIELD MODIFIED SIDE RETU...

Страница 4: ...e sheets f Install hose onto plastic spout 7 Install horizontal pan on right side of coil assembly Fig 4 Slope Coil in Horizontal Left Application Factory Ready A00096 UNIT FIELD SUPPLIED HANGING STRA...

Страница 5: ...cal pan fitting to door joint to retain the low air leak performance of the unit Failure to follow this CAUTION could result in personal injury or product and property damage In this application field...

Страница 6: ...nect switch remote to the unit is turned off Failure to do so will result in electrical shock causing personal injury or death A Line Voltage Connections If unit contains an electric heater remove and...

Страница 7: ...nufactured housing applications the Code of Federal Regulations Title 24 Chapter XX Part 3280 714 requires that supplemental electric heat be locked out at outdoor temperatures above 40 deg F except f...

Страница 8: ...n Coil Wiring with 1 Speed Air Conditioner A98477 O W2 Y1 W2 W W1 G R W2 Y1 INDOOR CONTROL FAN COIL 1 SPEED AIR CONDITIONER W1 G C Y C DHUM HUM B S1 S2 Y Y2 R O C DH HEAT STAGE 2 N A HEAT STAGE 1 COOL...

Страница 9: ...Wiring with 1 Speed Heat Pump A98475 O W2 W W1 Y1 W2 G R O W2 INDOOR CONTROL FAN COIL 1 SPEED HEAT PUMP W1 G C Y R W2 O C DHUM HUM B S1 S2 Y Y2 R Y1 C DH HEAT STAGE 3 HEAT STAGE 2 HEAT COOL STAGE 1 R...

Страница 10: ...condensate flows from the secondary drain or external condensate pan the unit requires servicing or water damage will occur Install traps in the condensate lines as close to the coil as possible See...

Страница 11: ...ory setting for air conditioner or heat pump size is the largest unit meant for application with the model of fan coil purchased Installer needs to select air conditioner or heat pump size to ensure t...

Страница 12: ...ave a 1 minute off delay and zero on delay programmed into the ECM motor that cannot be overridden Four motor operation delay profiles are provided to customize and enhance system operation See Fig 17...

Страница 13: ...AC HP CFM ADJUST Select NOM 5 ON OFF DELAY Select 0 90 profile 6 CONTINUOUS FAN Select desired fan speed when thermostat is set to continuous fan I COMFORT OPTIONS WARMER HEATING AND SUPER DEHUMIDIFY...

Страница 14: ...AUX and HUM terminals on the Easy Select Board are tied directly to the G terminal and provide a 24 vac signal whenever the G terminal is energized See Fig 17 and 18 During Super Dehumidify and SuperC...

Страница 15: ...iguration instructions If the indoor temperature is below the temperature set point and the humidity is above the humidity set point the Thermidistat closes circuit R to O opens circuits R to DH and R...

Страница 16: ...60 1050 610 770 1225 700 880 1400 875 1100 1750 NOTE 1 The above airflows result with the AC HP CFM ADJUST select jumper set on NOM 2 Airflow can be adjusted 15 percent or 10 percent by selecting HI o...

Страница 17: ...LO NOM HI 005 30 000 975 975 1040 1100 1100 1100 36 000 980 1085 1250 1100 1100 1250 1250 1250 1250 42 000 1140 1270 1460 1140 1270 1460 1250 1270 1460 48 000 1305 1450 1665 1305 1450 1665 1305 1450 1...

Страница 18: ...SELECT BOARD 1 Unplug harness from board 2 Check for appropriate voltages on pins with Easy Select Board screw terminals jumpered See Table 7 for values and see example below If proper signals are no...

Страница 19: ...e The disconnect when used on access panel does not disconnect power to the line side of disconnect but does allow safe service to all other parts of unit If unit does not have a disconnect disregard...

Страница 20: ...utor for maintenance procedures WARNING As with any mechanical equipment personal injury can result from sharp metal edges etc therefore care should be taken when removing parts Using the Owner s User...

Страница 21: ...n as other HFC s is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not install a s...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...2003 CAC BDP 7310 W Morris St Indianapolis IN 46231 imfv4B02 24 Book Tab 1 4 3d 2e Catalog No 63FV 4B1...

Отзывы: