4. Set meter to read DC voltage. Place meter between pins #1 and #14 and check for (-) 12vdc (common side of meter on pin #1). If signal

is present, the problem is in the module or motor. If signal is not, problem is either in wiring harness or Easy Select Board.

These steps can be repeated for other modes of operation.

To check Easy Select Board:

1. Leave jumper wire in place between R and Y/Y2.

2. Check Table 7 under

Wiring Harness Connection to Easy Select Board

column and row for pin #14 to see pin# on Easy Select Board

that should have voltage. The correct pin is #2. The column on far right will show voltage that should be present between pin #2 and #9
(or #10 common).

3. Place meter between pins #2 and #9 on Easy Select Board and check for (-) 12vdc.

4. If voltage is present, the wiring harness is bad; if not, the Easy Select Board is bad.

D.

Verify Motor Winding Section:

Before proceeding with module replacement, check the following to ensure motor winding section is functional. With control module removed
and unplugged from winding section:

1. The resistance between any 2 motor leads should be similar.

2. The resistance between any motor lead and the unpainted motor end plate should be greater than 100K ohms.

If motor winding section fails one of these tests, it is defective and must be replaced.

START-UP PROCEDURES

Refer to outdoor unit Installation Instructions for system start-up instructions and refrigerant charging method details.

CARE AND MAINTENANCE

For continuing high performance, and to minimize possible equipment failure, it is essential that periodic maintenance be performed on this
equipment. The only required maintenance that may be performed by the consumer is filter maintenance.

WARNING: Disconnect all power to unit before servicing field wires or removing control package. The disconnect

(when used) on access panel does not disconnect power to the line side of disconnect, but does allow safe service to all
other parts of unit. If unit does not have a disconnect, disregard the foregoing. Instead, make sure that a disconnecting
means is within sight from, and is readily accessible from, the unit. Disconnect all electrical power to unit before performing
any maintenance or service on it. A failure to follow this warning can cause electrical shock, fire, personal injury, or death.

The minimum maintenance requirements for this equipment are as follows:

1. Inspect and clean or replace air filter each month or as required.

2. Inspect cooling coil, drain pan, and condensate drain each cooling season for cleanliness. Clean as necessary. An inspection port is provided

on all A-coil delta plates. Remove plastic plug to inspect.

Table 7—Wiring Connections of FV Fan Coil Wiring Harness

16-IN PLUG ON WIRING HARNESS TO MOTOR

WIRING HARNESS CONNECTION TO EASY SELECT BOARD

Pin on 16-Pin Plug

Description

Pin on 12-Pin Plug
or Set-up Selection

Wire Color

Signal on Pin with

Screw Terminal
Jumpered to R*

1

Common

Pin 9 on PL-1

Brown

2

W1

Auxiliary Heat Stage 1

Pin 7 on PL-1

Violet

24VAC**

3

Common

Pin 10 on PL-1

Orange

4

On/Off Delay Selection

On/Off Delay Selection

White

5

AC/HP Size Selection

AC/HP Size Selection

Blue

6

Y1

Low Speed AC or HP

Pin 3 on PL-1

Black

(-) 12VDC**

7

AC/HP CFM Adjust

Selection

AC/HP CFM Adjust

Selection

Black

8

Not Used

N/A

Not Used

9

System Type Selection

System Type Selection

Orange

10

Dehumidify

Pin 12 on PL-1

Gray

0V (24VAC on no call)

11

Aux Heat Size

Selection

Aux Heat Size

Selection

Violet

12

24v AC

Pin 8 on PL-1

Red

24VAC continuous

13

W2

Auxiliary Heat Stage 2

Pin 4 on PL-1

White

24VAC**

14

Y/Y2

Single Speed AC or

HP, High Speed

2-Speed AC or HP

Pin 2 on PL-1

Yellow

(-) 12VDC**

15

G

Fan

Pin 1 on PL-1

Green

24VAC**

16

Not Used

N/A

Not Used

* Check voltages with 16-Pin Plug disconnected from motor.
** These signals will start motor.

—19—

Содержание FV4B

Страница 1: ...work gloves Use quenching cloth for brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions attached to the unit Consult local buildi...

Страница 2: ...orizontal left applications as factory shipped See Fig 2 4 and 8 Units can be installed for horizontal right applications with field modifications Units may be converted for downflow applications usin...

Страница 3: ...ide of unit and reinstall on coil support rail on right side of unit Fig 2 Slope Coil Unit in Upflow Application A00091 A COIL UNITS POWER ENTRY OPTIONS LOW VOLT ENTRY OPTIONS FIELD MODIFIED SIDE RETU...

Страница 4: ...e sheets f Install hose onto plastic spout 7 Install horizontal pan on right side of coil assembly Fig 4 Slope Coil in Horizontal Left Application Factory Ready A00096 UNIT FIELD SUPPLIED HANGING STRA...

Страница 5: ...cal pan fitting to door joint to retain the low air leak performance of the unit Failure to follow this CAUTION could result in personal injury or product and property damage In this application field...

Страница 6: ...nect switch remote to the unit is turned off Failure to do so will result in electrical shock causing personal injury or death A Line Voltage Connections If unit contains an electric heater remove and...

Страница 7: ...nufactured housing applications the Code of Federal Regulations Title 24 Chapter XX Part 3280 714 requires that supplemental electric heat be locked out at outdoor temperatures above 40 deg F except f...

Страница 8: ...n Coil Wiring with 1 Speed Air Conditioner A98477 O W2 Y1 W2 W W1 G R W2 Y1 INDOOR CONTROL FAN COIL 1 SPEED AIR CONDITIONER W1 G C Y C DHUM HUM B S1 S2 Y Y2 R O C DH HEAT STAGE 2 N A HEAT STAGE 1 COOL...

Страница 9: ...Wiring with 1 Speed Heat Pump A98475 O W2 W W1 Y1 W2 G R O W2 INDOOR CONTROL FAN COIL 1 SPEED HEAT PUMP W1 G C Y R W2 O C DHUM HUM B S1 S2 Y Y2 R Y1 C DH HEAT STAGE 3 HEAT STAGE 2 HEAT COOL STAGE 1 R...

Страница 10: ...condensate flows from the secondary drain or external condensate pan the unit requires servicing or water damage will occur Install traps in the condensate lines as close to the coil as possible See...

Страница 11: ...ory setting for air conditioner or heat pump size is the largest unit meant for application with the model of fan coil purchased Installer needs to select air conditioner or heat pump size to ensure t...

Страница 12: ...ave a 1 minute off delay and zero on delay programmed into the ECM motor that cannot be overridden Four motor operation delay profiles are provided to customize and enhance system operation See Fig 17...

Страница 13: ...AC HP CFM ADJUST Select NOM 5 ON OFF DELAY Select 0 90 profile 6 CONTINUOUS FAN Select desired fan speed when thermostat is set to continuous fan I COMFORT OPTIONS WARMER HEATING AND SUPER DEHUMIDIFY...

Страница 14: ...AUX and HUM terminals on the Easy Select Board are tied directly to the G terminal and provide a 24 vac signal whenever the G terminal is energized See Fig 17 and 18 During Super Dehumidify and SuperC...

Страница 15: ...iguration instructions If the indoor temperature is below the temperature set point and the humidity is above the humidity set point the Thermidistat closes circuit R to O opens circuits R to DH and R...

Страница 16: ...60 1050 610 770 1225 700 880 1400 875 1100 1750 NOTE 1 The above airflows result with the AC HP CFM ADJUST select jumper set on NOM 2 Airflow can be adjusted 15 percent or 10 percent by selecting HI o...

Страница 17: ...LO NOM HI 005 30 000 975 975 1040 1100 1100 1100 36 000 980 1085 1250 1100 1100 1250 1250 1250 1250 42 000 1140 1270 1460 1140 1270 1460 1250 1270 1460 48 000 1305 1450 1665 1305 1450 1665 1305 1450 1...

Страница 18: ...SELECT BOARD 1 Unplug harness from board 2 Check for appropriate voltages on pins with Easy Select Board screw terminals jumpered See Table 7 for values and see example below If proper signals are no...

Страница 19: ...e The disconnect when used on access panel does not disconnect power to the line side of disconnect but does allow safe service to all other parts of unit If unit does not have a disconnect disregard...

Страница 20: ...utor for maintenance procedures WARNING As with any mechanical equipment personal injury can result from sharp metal edges etc therefore care should be taken when removing parts Using the Owner s User...

Страница 21: ...n as other HFC s is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not install a s...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...2003 CAC BDP 7310 W Morris St Indianapolis IN 46231 imfv4B02 24 Book Tab 1 4 3d 2e Catalog No 63FV 4B1...