background image

ERV & HRV: User and Installer Manual

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

16

INSTALLER’S TROUBLESHOOTING (CONT’D)

WARNING

DESCRIPTION

SOLUTION

W22

Supply airflow

STEP 1: Perform  a visual inspection of the supply damper  system. Clean  filters, distribution registers and

outside supply hood. Inspect ducting to ensure it is not squeezed or bent. If STEP 1 did not fix the problem,

perform STEP 2: Remove ducting of the supply path. On the LCD screen, select MAX to check if the unit is

able to reach the selected flow. If so, review the ducting path.
If STEP 2 did not fix the problem, perform STEP 3: On the LCD screen, select the MIN and MAX flow setting

values then reset the unit. MAX flow value will display on the LCD screen. If MAX flow is above desired

MAX flow, set MAX and MIN flows.
If STEP 3 did not fix the problem, perform STEP 4: Replace the supply blower and repeat STEP 3.
If STEP 4 did not fix the problem, perform STEP 5: Replace the electronic assembly.

W32

Exhaust airflow

STEP 1: Perform a visual inspection of the exhaust damper system. Clean filters, distribution registers and

outside supply hood. Inspect ducting to ensure it is not squeezed or bent. If STEP 1 did not fi x the problem,

perform STEP 2: Remove ducting of the supply path. On the LCD screen, select MAX to check if the unit is

able to reach the selected flow. If so, review the ducting path.
If STEP 2 did not fix the problem, perform STEP 3: On the LCD screen, select the MIN and MAX flow setting

values then reset the unit. MAX flow value will display on the LCD screen. If MAX flow is above desired

MAX flow, set MAX and MIN flows.
If STEP 3 did not fix the problem, perform STEP 4: Replace the exhaust blower and repeat STEP 3.
If STEP 4 did not fix the problem, perform STEP 5: Replace the electronic assembly.

W52

Initial setting 

incomplete

STEP 1: Press + or - to access the selection menu.

STEP 2: Complete configuration. (Refer to 

(AUTO-BALANCING PROCEDURE on p11)

 for more details).

W61

Protection mode 

electronics 

overheating

The  unit  is  currently  in  protection  mode.  The  power  transmitted  to  the  motor  is  deliberately  reduced  to

decrease electronics temperature. The unit will exit this mode by itself once conditions are back to normal. It is

normal to observe reduction in airflows during this period. 
This condition should appear only when the unit is located in a warm environment, for example over 60°C

(140°F). If this condition appears while the unit is located in an environment where the ambient temperature is

under 30°C (86°F), replace the electronic assembly.

Содержание ERVXXSHA1130

Страница 1: ...r heat energy recovery ventilator is installed can make a significant difference to the electrical energy you use To minimize the electricity use of the heat energy recovery ventilator a stand alone fully ducted installation is recommended If you choose a simplified installation that operates your furnace air handler for room to room ventilation an electrically efficient furnace that has an electr...

Страница 2: ...ation comprises more restrictive installation and or certification requirements the aforementioned requirements prevail on those of this document and the installer agrees to conform to these at his own expenses CAUTION TO AVOID UNIT DAMAGE AND ENSURE LONG LIFE 1 To avoid prematurely clogged filters turn the unit OFF during construction or renovation 2 Please read specification label on product for...

Страница 3: ...ELECTRICAL CONNECTION TO OPTIONAL MAIN WALL CONTROL 8 Connection to Speed Selector Automatic Dehumidistat or Premium Optional Main Wall Control 8 Electrical Connection to Optional Auxiliary Wall Control 9 Electrical Connection to Bathroom Override Optional Auxiliary Wall Control 9 CONNECTION TO THE FURNACE AHU 9 UNIT OPERATION USING A FURNACE AHU THERMOSTAT 9 UNIT INTERCONNECTION WITH FURNACE AHU ...

Страница 4: ...e to a drain If no drain is close by use a pail to collect run off Away from hot chimneys electrical panel and other fire hazards Within 6 feet of a power source standard outlet Suspended to the Joists or Trusses Slightly bend the brackets on the unit to insert the provided chains Fig 2 Hang the unit to the joists using the provided chains Springs are not required Always make sure that the unit is...

Страница 5: ... duct connection to the furnace AHU installation must be done in accordance with all applicable codes and standards Please refer to your local building code A200563 Fig 6 Exhaust Ducted System STALE AIR EXHAUST DUCTWORK Same as for Fully Ducted System FRESH AIR DISTRIBUTION Connect the fresh air distribution duct of the unit to the furnace AHU return duct at least 10 feet away from the furnace AHU...

Страница 6: ...elected on the LCD screen when auto balancing the unit ALTERNATE INSTALLATION T 5 A200566 Fig 9 Alternate Installation Unit should be synchronized with AHU Furnace operation to building avoid condensation and mold growth in furnace AHU distribution ducting if cooling mode of furnace AHU is used NOTE For this type of configuration the T 5 option must be selected on the LCD screen when auto balancin...

Страница 7: ...following procedure to connect the insulated flexible ducts to the ports of the unit exhaust to outside and fresh air from outside 1 Expose the flexible duct by pulling back the insulation and place it over the inner port ring 2 Attach the flexible duct to the port using a tie wrap 3 Seal the joint using duct tape 4 Pull the insulation and vapor barrier over the joint tuck them between the inner a...

Страница 8: ...y inserted in their corresponding holes in the terminal connector Use screws to fix wires in the terminal connector Once the wall control connections have been made insert the terminal connector in the electrical compartment NOTE For information about the operation of the wall control refer to the corresponding Installation and User Guide Connection to Speed Selector Automatic Dehumidistat or Prem...

Страница 9: ...ower operation when ventilating NOTE These connections are required for installation configuration T 4 INSTALLING THE DUCTWORK AND THE REGISTERS on p5 SYNCHRONIZATION WITH AHU FUNCTION The new ventilation technology allows synchronizing the unit operation with the furnace AHU operating time It prevents unnecessary AHU operating time while providing a better air distribution NOTE W and Y connection...

Страница 10: ...i L N u e l a r t 1 K G f G C A i L n e r e t l i F 2 1 J F1 o V h g i H e g a t l C A V 0 2 1 1 1 J J o T 2 U C M 1 K 3 M e t S e p p r D e v i r r T o J 5 M A R G A I D G N I R I W BDM 1 5A 5 2 1 V C A 3 J 2 J 6 J 5 J 7 J 1 1 1 1 1 a 7 J J a 5 1 1 2 A L D C S A SE B M LY N R G e V n a l i t n o i t F a o M n r o t s BLU RED 2 M 3 M 4 M S p p u y l l p p u S y n o i t p O l a R e c r i c t s u a ...

Страница 11: ...SYSTEM This balanced ventilation unit is designed to provide fresh air to your home while exhausting stale humid air Thanks to its energy heat recovery module the unit recovers a large proportion of heat or energy that is part of indoor or outdoor air according to the seasons to improve comfort and energy efficiency during the heating and the cooling periods With the new ventilation technology thi...

Страница 12: ...SCRIPTION PART NUMBER HRVXXSVA1130 HRVXXSHA1130 ERVXXSVA1130 ERVXXSHA1130 HRVXXSVA1160 HRVXXSHA1160 ERVXXSVA1160 ERVXXSHA1160 HRVXXSVB1160 HRVXXSHB1160 ERVXXSVB1145 ERVXXSHB1145 1 6 port warm side SV66139 2 2 2 2 5 port warm side SV66140 2 2 2 6 metal port motorized damper SV66135 1 1 1 1 5 metal port motorized damper SV66136 1 1 3 Electronic assembly SV66144 1 1 1 1 1 1 4 Terminal blocks SV66145 ...

Страница 13: ...ILATION UNIT MODEL ELECTRONIC ASSEMBLY PART NUMBER HRVXXSHA1130 HRVXXSVA1130 HRVXXSHA1160 HRVXXSVA1160 HRVXXSHB1160 HRVXXSVB1160 ERVXXSHA1130 ERVXXSVA1130 ERVXXSHA1150 ERVXXSVA1150 ERVXXSHB1145 ERVXXSVB1145 SV66144 03 X SV66144 04 X SV66144 05 X SV66144 06 X SV66144 09 X SV66144 10 X SV66144 11 X SV66144 12 X SV66144 13 X SV66144 14 X SV66144 17 X SV66144 18 X ...

Страница 14: ...ay have to be removed to access the damper system Plug unit If STEP 1 did not fix the problem perform STEP 2 Open electrical compartment check if connector J6 blue is well inserted check for any loose wires If STEP 2 did not fix the problem perform STEP 3 If the damper is not moving at all unplug J5 white from the electronic assembly connect the blue damper system connector into J5 If the damper m...

Страница 15: ...n If STEP 1 did not fix the problem perform STEP 2 Replace the electronic assembly E35 Exhaust motor drive under voltage E36 Exhaust motor drive over temp STEP 1 Validate if the air exchanger is exposed to ambient temperatures within the operating limits LOCATING AND MOUNTING THE UNIT on p4 If STEP 1 did not fix the problem perform STEP 2 Replace the electronic assembly E40 Outside air thermistor ...

Страница 16: ...o ensure it is not squeezed or bent If STEP 1 did not fi x the problem perform STEP 2 Remove ducting of the supply path On the LCD screen select MAX to check if the unit is able to reach the selected flow If so review the ducting path If STEP 2 did not fix the problem perform STEP 3 On the LCD screen select the MIN and MAX flow setting values then reset the unit MAX flow value will display on the ...

Страница 17: ...nit to malfunction a Make sure there are no leaves twigs ice or snow that could be drawn into the vent b Clean if necessary 7 Reassemble the components Pay special attention to the filters by making sure that they are engaged in their slots 8 Rotate the blower wheels by hand If one of the wheels does not rotate easily contact your installer 9 Close the unit door and reconnect power supply 10 Reset...

Страница 18: ...water and let it dry 1 Remove the dust on the core using a vacuum cleaner and a soft brush attachment CAUTION DO NOT SOAK THE ENERGY RECOVERY CORE IN WATER PROBLEM TRY THIS 1 Nothing works See if the unit is plugged in See if the unit is receiving power from the house circuit breaker or fuse 2 Noisy unit Clean the unit see Section 9 If the problem is not solved contact your installer 3 Condensatio...

Отзывы: