UNIT AUTO-BALANCING
PREPARATION
Follow these steps to ensure accurate measurements:
• Seal all the ductwork with tape. Close all windows and doors.
• Turn off all exhaust devices such as range hood, dryer and bathroom
fans.
• If the installation is in any way connected to the ductwork of the cold
air return of a furnace/air handler, make sure that the furnace/air
handler blower is ON. If not, leave furnace/air handler blower OFF.
AUTO-BALANCING PROCEDURE
1. Plug the unit and wait for 90 seconds (airflow test).
2. The maximum CFM will display on the LCD screen. Use (+/-) to
adjust the CFM and OK to confirm.
3. The minimum CFM will display on the LCD screen. Use (+/-) to
adjust the CFM and OK to confirm.
4. INS will display on the LCD screen. Choose among T-1, T-2, T-3,
T-4 or T-5 following the installation configuration
THE DUCTWORK AND THE REGISTERS on p5)
.
A200579
Fig. 19 – Integrated Control
5. If required, options can be configured. While on the CFG OPT
screen, press on the OK button for 4 seconds. Use (+/-) to change
the configuration and OK to confirm. If not required, press OK to
skip this menu.
6. Auto-balancing is completed.
* Factory setting
NOTE:
If no selection is confirmed within 10 minutes, the unit will exit
the menu without saving any changes.
NOTE:
If speed or configuration need to be modified, go to MIN, MAX
or CFG using (+/-), then press on the OK button for 4 seconds. Use (+/-)
to increase/decrease speed and OK to confirm.
If any change is made to the ducting, reset settings to restart the airflow
test.
PROCEDURE TO RESET SETTINGS
Press on the OK and (-) buttons simultaneously for 4 seconds. Use (+/-)
to select Yes or No and OK to confirm. Then perform the auto-balancing
procedure.
USING THIS UNIT
YOUR VENTILATION SYSTEM
This balanced ventilation unit is designed to provide fresh air to your
home while exhausting stale, humid air. Thanks to its energy/heat
recovery module, the unit recovers a large proportion of heat or energy
that is part of indoor or outdoor air according to the seasons to improve
comfort and energy efficiency during the heating and the cooling
periods. With the new ventilation technology, this unit responds to the
variations in its environment in an autonomous way, ensuring to provide
a proper level of ventilation and air quality. This unit also features
automatic modes (AUTO or SMART) that manage autonomously the
required ventilation level as per indoor and/or outdoor conditions. In
colder areas, the unit will perform, at intervals, recovery module discreet
defrost to maintain performance and comfort.
INTEGRATED CONTROL
A200579
All units are equipped with an integrated control, located in front of the
electrical compartment. For more convenience, these units can be
controlled using an optional wall control or the furnace/AHU thermostat
equipped with external fan activation.
MODE SELECTION
1. To change the mode, use (+/-) to access the Mode screen. Press OK
to edit the mode and use (+/-) to change the mode (Standby, Min,
Max).
2. Press OK to confirm selection. The airflows will be displayed for
both MIN and MAX modes.
NOTE:
If an optional auxiliary wall control or the furnace/AHU
thermostat equipped with external fan activation is used, it overrides the
integrated control.
Options
Configurations available
DEF
(Defrost)
DIS*
(Discretion - defrost without speed variation for more comfort),
PLU
(Plus - extended defrost for colder areas)
INS
(Installation)
T-1, T-2, T-3, T-4*, T-5
(INSTALLING THE DUCTWORK AND THE REGISTERS on p5)
DRY
(Dry contact)
MIN*
(Minimum),
INT
(Intermittent),
AUT
(AUTO),
MAX
(UNIT OPERATION USING A FURNACE/AHU
OVR
(Override)
BAL*
(Balanced),
PER
(Performance),
DIS
(Electrical Connection to Bathroom Override Optional Auxiliary
INT
(Intermittent)
STB*
(Standby - 20 min in MIN speed and 40 min in standby mode)