5
ERVXXLHB1200, HRVXXLHB1150, HRVXXLHB1250
17”
(432 mm)
17¼” (438 mm)
6”
(152 mm)
30¼” (768 mm)
35” (891 mm)
17”
(432 mm)
17¼” (438 mm)
6”
(152 mm)
34” (864 mm)
39” (991 mm)
ERV
HRV
1
2
3
4
1
2
3
4
1. Fresh air to house.
2. Exhaust air from house.
3. Fresh air from outside.
4. Exhaust air to outside.
A12341
PHYSICAL & ELECTRICAL DATA
MODEL
CAPACITY (LO---HI)
PORT
LOC.
CORE
WEIGHT
LBS. [KG]
VOLTAGE
MAX
POWER
WATTS
MAX
AMPS
CFM
L/S
TYPE
AIR FLOW
ERVXXLHB1200
80 --- 198
38 --- 93
Ends
Enthalpic
transfer media Cross flow
76 [35]
115/60/1
200
2.1
HRVXXLHB1150
66 --- 163
31 --- 77
Ends
Polypropylene Cross flow
65 [30]
115/60/1
160
1.5
HRVXXLHB1250
82 --- 204
39 --- 96
Ends
Polypropylene Cross flow
65 [30]
115/60/1
195
2.1
DEFROST OPERATION
MODEL
OUTSIDE TEMPERATURE
DEFROST CYCLE (MIN.)
EXTENDED DEFROST CYCLES
(MIN.)
_
C
_
F
Defrosting
Operation Time
Between Each
Defrost Cycle
Defrosting
Operation Time
Between Each
Defrost Cycle
ERVXXLHB1200
---5
23
10
60
10
30
---15
5
10
30
10
20
---27
---17
10
20
10
15
HRVXXLHB1150
---5
23
7
50
10
30
---15
5
7
25
10
20
---27
---17
10
20
10
15
HRVXXLHB1250
---5
23
6
50
10
30
---15
5
6
25
10
20
---27
---17
10
20
10
15