background image

10

If the integrated control LED of the unit is flashing, this means the unit sensors detected a problem. See the table below to know where on the
unit the problem occurs.

Table 5 – Troubleshooting

LED flashes GREEN.

Thermistor error.

Reference Table 6 for proper temperature vs. resistance relationship. If thermistor
is defective, replace the entire port assembly (fresh air from outside port).

LED flashes RED.

The door is open and the unit is not
unplugged.

Close the door and press once on the integrated control push button to reset the
unit.

Exhaust motor error.

Go to Problem 5 below.

LED flashes AMBER.

Damper error.

Go to Problem 6 below.

Problem:

Possible causes:

You should try this:

1. Unit does not work.

S

The circuit board may be defective.

S

Unplug the unit. Disconnect the main
control and the optional control(s) (if need

be). Jump G and B terminals. Plug the unit
back and wait about 10 seconds. If the
motors run on high speed and the damper

opens, the circuit board is not defective.

NO  C  NC   I   OC OL  Y    R   G   B

2. The damper actuator

does not work.

S

The damper actuator or the integrated
damper port mechanism may be

defective.

S

Unplug the unit. Disconnect the main control and the optional controls(s) (if need
be).Wait 10 seconds and plug the unit back. Check if the damper opens. If not,

use a multimeter and check for 24VAC on J12--1 and J12--2 (in electrical
compartment). If there is 24VAC, replace the entire port assembly.

NOTE

: It is normal to experience a small delay (7--8 seconds) before detecting

the 24VAC signal at starting--up. This signal will stay during 17--18 seconds
before disappearing.

S

The circuit board may be defective.

S

If there is no 24VAC, replace the circuit board.

3. The wall control does

not work OR its indi-
cator flashes.

S

The wires may be in reverse position.

S

Ensure that the color coded wires have been connected to their work OR its
indicator flashes. appropriate places.

S

The wires may be broken.

S

Inspect every wire and replace any that are damaged.

S

The wire in the wall OR the wall.

S

Remove the wall control and test it right beside the unit using another control
may be defective. shorter wire. If the wall control works there, change the wire. If

it does not, change the wall control.

4. The

dehumidistat

does not work OR
the 20--minute. push--

button timer does not
work OR its indicator
light does not stay
on.

S

The wires may be in reverse position.

S

Ensure that the color coded wires have been connected to their appropriate
places.

S

The dehumidified or push button may be
defective.

S

Jump the OL and OC terminals. If the unit
switch to high speed, remove the

dehumidistat or push button and test it right
beside the unit using another shorter wire. If
it works here, change the wire. If it doesn’t,

change the dehumidistat or the push button.

NO  C  NC   I   OC OL  Y    R   G    B

5. The supply and/or

exhaust motor do not
work.

S

The circuit board may be defective.

S

Press on the integrated control push button until the unit turn on low speed (the
LED will light AMBER). Using a multimeter, check the voltage on J4--1 and

J4--2 (for supply motor), and on J5--1 and J5--2 (for exhaust motor). The reading
must be

±

68VAC. Then set the unit on high speed by pressing on the integrated

control 1 more time (the LED will light GREEN).Using a multimeter, check the

voltage on J4--1 and J4--2 (for supply motor), and on J5--1 and J5--2 (for exhaust
motor). The reading must be

±

120VAC. If all the readings correspond to the right

voltage values, the circuit board is not defective. If one or both readings are
different, change the circuit board.

S

The motor(s) may be defective.

S

Using a multimeter, check the ohms value on each motor connectors. Black
motors values: For BLUE and BLACK motor wires, the right value is

±

55 ohms.

For BLUE and BROWN motor wires, the right value is

±

35 ohms. For BROWN

and BLACK motor wires, the right value is

±

89 ohms. Aluminum motors values:

For BLUE and BLACK motor wires, the right value is

±

51 ohms. For BLUE and

BROWN motor wires, the right value is

±

47 ohms. For BROWN and BLACK

motor wires, the right value is

±

98 ohms. If he ohms values are the same, the

motor is not defective. Replace the motor capacitor.

6. The defrost cycle

does not work (the
fresh air duct is fro-

zen OR the fresh air
distributed is very
cold. (See Table 7 for
Defrost Cycle Tim-

ing.)

S

Ice deposits may be hindering the
damper operation.

S

Remove the ice.

S

The damper rod or the port damper itself
may be broken.

S

Inspect these parts and replace if necessary.

S

The damper actuator or circuit board
may be defective.

S

See Problem 2.

7. The integrated con-

trol push button does
not work.

S

The 30 --second boot sequence is not
completed.

S

See Boot Sequence.

ER

V

/HR

V

Содержание ERVCCSHB1100

Страница 1: ...staller or agency must use factory authorized kits or accessories when modifying this product Refer to the individual instructions packaged with kits or accessories when installing Follow all safety codes Wear safety glasses protective clothing and work gloves Have a fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions included in literature and attach...

Страница 2: ...m unit should be located next to or close to the indoor equipment COMPONENT DESCRIPTION The following listed items are components of ERVCCSHA See Fig 4 1 Exhaust air connected to outdoor air exhaust hood 2 Fresh air intake connected to outdoor air inlet hood 3 Fresh air supply from ERV connected to return air duct of forced air system 4 Mechanical filters trap dust contained in the air 5 Energy re...

Страница 3: ... heater WARNING Return air or stale air pickup registers are normally located to draw from kitchen bathroom basement or other rooms where stale air can exist Proper size and type of registers must be used to minimize pressure drop The velocity of airflow through register should not be above 400 ft 122m per minute Maximum length of duct for the system should be designed according to the highest spe...

Страница 4: ... air pockets See Fig 7 Both intake and exhaust hoods must be 18 in 457mm from ground and at least 12 in 305mm above anticipated snow level After selecting proper hood locations make appropriate size hole through exterior wall pass flexible duct through hole and insert hood tube into duct Tape duct vapor barrier tightly around hood tube and insert assembly back into wall and fasten securely Condens...

Страница 5: ...s to ensure highest degree of humidity control in cooling season the INTERMITTENT mode should be used Integrated Control All units are equipped with an integrated control located under the unit in front of the electrical compartment Use the push button 1 to control the unit The LED 2 will then shows on which mode the unit is in Integrated Control overrides Wall Control function When LED is off ven...

Страница 6: ... electrical connections must comply with National and Local Electrical Codes or other ordinances that might apply ELECTRICAL SHOCK FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Do not use an extension cord as a power source for operating the ERV HRV WARNING 12VDC Wiring The ERV HRV circuit board wall control and accessories operate on 12VDC...

Страница 7: ...ve furnace air handler blower OFF If the outside temperature is below 32_F 0_C make sure the unit is not running in defrost while balancing By waiting 10 minutes after plugging the unit in you are assured that the unit is not in a defrost cycle Step 2 Magnehelic gauge placement Place the magnehelic gauge on a level surface and adjust it to zero Step 3 Connect tubing from gauge to EX HAUST air flow...

Страница 8: ...opens contact on K5 relay which opens outside air damper Then 115VAC is applied between orange and gray wires on Molex plug pins 1 and 6 and blower motor runs in high speed operation Low Speed Air Exchange When low speed air exchange occurs K1 Relay is energized which closes the contacts K2 and K5 relays are de energized This keeps low speed contacts closed and high speed contacts open on K2 relay...

Страница 9: ...all Control Board Operation and Care and Maintenance sections before continuing NOTE If there is a short circuit or an open circuit at thermistor CPU will go into a 5 minute defrost cycle every 20 minutes This feature is not there on older board versions with 3 pin jumpers Override Test To use override test function a thermistor must be connected to the control board Unit must not be in defrost mo...

Страница 10: ...e dehumidistat does not work OR the 20 minute push button timer does not work OR its indicator light does not stay on S The wires may be in reverse position S Ensure that the color coded wires have been connected to their appropriate places S The dehumidified or push button may be defective S Jump the OL and OC terminals If the unit switch to high speed remove the dehumidistat or push button and t...

Страница 11: ...12 16560 55 13 15900 57 14 15280 59 15 14690 61 16 14120 63 17 13580 64 18 13060 66 19 12560 68 20 12090 70 21 11630 72 22 11200 73 23 10780 75 24 10380 77 25 10000 79 26 9632 81 27 9281 82 28 8944 84 29 8622 86 30 8313 88 31 8014 90 32 7728 91 33 7454 93 34 7192 95 35 6940 97 36 6699 99 37 6467 100 38 6245 Table 7 Defrost Cycle HRV DEFROST CYCLES Outside Temp F C Defrosting minutes Operation time...

Страница 12: ... ICP RED BLK 1 2 3 HI JU1 MED Ref 1 ORG YEL ORG PRP BLU 71V 64V 57V nc nc nc RED BLU BLU RED ORG PRP GRY BLK BLK WHT WHT BLK BLU BRN BLK BLK BLK BLU BRN BLK BLK GRN WHT BLK GRN BLK GRN RED YEL GRN 6 BLK K5 K2 K3 K1 MODE M1 Supply M2 Exhaust DAMPER 0 0 0 0 OFF OFF OFF Closed 1 0 1 1 Exchange low speed LO LO Opened 1 1 1 1 Exchange high speed HI HI Opened 1 1 1 0 Circulation high speed HI OFF Closed...

Страница 13: ...12 4 J12 3 J2 3 J2 4 J2 5 Door interlock switch J11 2 J11 1 K1 K3 K5 J14 3 J14 1 J14 2 Furnace blower interlock optional see notes 3 5 J14 4 J14 5 J14 6 J14 7 J14 8 J14 9 J14 10 Override switch optional see notes 3 4 Field wiring remote control see notes 3 4 MED LO 1 2 3 HI MED JU1 Ref 1 9 5V class 2 YEL neutral YEL 24V class 2 ORG 120V 106V 81V GRY WHT RED BLK ORG ORG PRP BLU 71V 64V 57V 120V 106...

Страница 14: ... when used in Canada S ERVCCSVB1100 S ERVCCSHB1100 S HRVCCSVB1100 S HRVCCSHB1100 Energy Star Canada Copyright 2010 Carrier Corp S 7310 W Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 05 10 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No ERVHRV 3SI Replaces ERVHRV 2SI ERV HRV ...

Отзывы: