background image

EconoMi$er X

Factory---Installed Option

Low Leak Economizer

for 2 Speed SAV (Staged Air Volume) Systems

Installation, Setup & Troubleshooting Supplement

This document is a supplemental installation instruction for the factory-installed
EconoMi$er X (low leak economizer) option. It is to be used with the base unit
Installation Instructions for 48/50TC, 50TCQ, 48/50HC, and 50HCQ 2-Stage cooling
units, sizes 08 – 30. Units equipped with the EconoMi$er X option are identified by
an indicator in the unit's model number (see the unit's nameplate). Use Table 1 (on
page 2) to identify whether or not a given unit is equipped with the
factory-installed EconoMi$er X.

NOTE

: Read the entire instruction manual before starting the installation.

TABLE OF CONTENTS

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . .

GENERAL

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Identifying Factory Option

2

. . . . . . . . . . . . . . . . . . . . . .

EconoMi$er X

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

W7220 Economizer Controller

3

. . . . . . . . . . . . . . . . . . .

User Interface

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Menu Structure

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Checkout Tests

7

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SETUP AND CONFIGURATION

7

. . . . . . . . . . . . . . . . .

W7220 Economizer Module Wiring

7

. . . . . . . . . . . . . .

Time--Out and Screen Saver

7

. . . . . . . . . . . . . . . . . . . . .

Enthalpy Settings

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Enthalpy Control Sensor Configuration

8

. . . . . . . . . . . .

Install Outside Air Hood — Factory Option

9

. . . . . . . .

15 to 25 Ton Horizontal Return Application with . . . .

Barometric Relief

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

OPERATION

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Cooling, Unit with EconoMi$er X

10

. . . . . . . . . . . . . . .

Heating, Unit with EconoMi$er X

10

. . . . . . . . . . . . . . .

Demand Control Ventilation

10

. . . . . . . . . . . . . . . . . .

TROUBLESHOOTING

11

. . . . . . . . . . . . . . . . . . . . . . . . .

Power Loss (Outage or Brownout)

11

. . . . . . . . . . . . . . .

Alarms

11

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Clearing Alarms

11

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service,

maintenance, or use can cause explosion, fire, electrical

shock or other conditions which may cause personal injury

or property damage. Consult a qualified installer, service

agency, or your distributor or branch for information or

assistance. The qualified installer or agency must use

factory--authorized kits or accessories when modifying this

product. Refer to the individual instructions packaged with

the kits or accessories when installing.

Follow all safety codes. Wear safety glasses and work

gloves. Use quenching cloths for brazing operations and

have a fire extinguisher available. Read these instructions

thoroughly and follow all warnings or cautions attached to

the unit. Consult local building codes and appropriate

national electrical codes (in USA, ANSI/NFPA70, National

Electrical Code (NEC); in Canada, CSA C22.1) for special

requirements.

It is important to recognize safety information. This is the
safety--alert symbol

. When you see this symbol on the

unit and in instructions or manuals, be alert to the

potential for personal injury.

Understand the signal words DANGER, WARNING,

CAUTION, and NOTE. These words are used with the

safety--alert symbol.

DANGER identifies the most serious hazards which

will

result

in severe personal injury or death. WARNING signifies hazards

which

could

result in personal injury or death.

CAUTION is used to identify unsafe practices, which

may

result in minor personal injury or product and

property damage.

Содержание EconoMiser X

Страница 1: ...1 Clearing Alarms 11 SAFETY CONSIDERATIONS Improper installation adjustment alteration service maintenance or use can cause explosion fire electrical shock or other conditions which may cause personal...

Страница 2: ...Nomenclature In addition to criteria in Table 1 all units equipped with a factory installed EconoMi er X display a 6 in the 14th position of the model number indicating the low leak economizer control...

Страница 3: ...ge parameter and configuration settings Using the Keypad with Menus To use the keypad when working with menus S Press the Up arrow button to move to the previous menu S Press the Down arrow button to...

Страница 4: ...Displays if not connected short or out of range DA TEMP _ _ __F 0 to 140_F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ __F if sensor sends...

Страница 5: ...t if DCV is used This is the ventilation for less than maximum occupancy of the space In AUTO mode dampers controlled by CFM VENTMIN L 3 7 V VENTMIN H 2 8 V ERV OAT SP 32_F 0 to 50_F increment by 1 On...

Страница 6: ...libration temperature sensor RA H CAL 0 RH 10 RH Allows for the operator to adjust for an out of calibration humidity sensor DA T CAL 0 0_F 2 5_F Allows for the operator to adjust for an out of calibr...

Страница 7: ...abel Type Description Top Left Terminal Block MAT MAT 20k NTC and COM Mixed Air Temperature Sensor polarity insensitive connection OAT OAT 20k NTC and COM Outdoor Air Temperature Sensor polarity insen...

Страница 8: ...he W7220 calculates the enthalpy and dew point using the OA temperature and humidity input from the OA sensor When the OA temperature OA humidity and OA dew point are all below the selected boundary t...

Страница 9: ...Hood Factory Option The outside air hood for factory option economizer is shipped in knock down form and requires field assembly See the base unit Installation Instructions for details on assembling a...

Страница 10: ...outside air temperature When space temperature demand is satisfied thermostat Y1 opens the dampers will return to Minimum Damper position if indoor fan is running or fully closed if fan is off If acc...

Страница 11: ...d start over Under the SYSTEM SETUP menu you can change the setpoints to the factory defaults Will I be able to see the LCD screen when it is in the unit The LCD screen has a backlight that is always...

Страница 12: ...012 Carrier Corp D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 02 12 Manufacturer reserves the right to change at any time specifications and designs without notice and with...

Отзывы: