Table 2 -- Menu Structure

a

(cont)

Menu

Parameter

Parameter

Default

Value

Parameter

Range and Increment

b

Notes

SETPOINTS

MAT SET

53

_

F

38 to 65

_

F;

increment by 1

Setpoint determines where the economizer will modulate the OA damper

to maintain the mixed air temperature.

LOW T LOCK

32

_

F

---45 to 80

_

F;

increment by 1

Setpoint determines outdoor temperature when the mechanical cooling

cannot be turned on. Commonly referred to as the Compressor lockout.

DRYBLB SET

63

_

F

48 to 80

_

F;

increment by 1

Setpoint determines where the economizer will assume outdoor air

temperature is good for free cooling; e.g.: at 63

_

F unit will economize at

62

_

F and below and not economize at 64

_

F and above. There is a

2

_

F deadband.

ENTH CURVE

ES3

ES1, ES2, ES3, ES4, or

ES5

Enthalpy boundary “curves” for economizing using single enthalpy.

DCV SET

1100ppm

500 to 2000 ppm;

increment by 100

Displays only if CO

2

sensor is connected. Setpoint for Demand Control

Ventilation of space. Above the setpoint, the OA dampers will modulate

open to bring in additional OA to maintain a space ppm level below the

setpoint.

MIN POS

4.4 V

2 to 10 Vdc

Displays ONLY if a CO

2

sensor is NOT connected.

VENTMAX With 2---speed

fan units VENTMAX L (low

speed fan) and VENTMAX

H (high speed fan) settings

are required

4.4 V

2 to 10 Vdc

or

100 to 9990 cfm

increment by 10

Displays only if a CO

2

sensor is connected. Used for Vbz (ventilation max

cfm) setpoint. Displays 2 to 10 V if <3 sensors (RA, OA and MA). In

AUTO mode dampers controlled by CFM.

VENTMAX L

6 V

VENTMAX H

4.4 V

VENTMIN With 2---speed

fan units VENTMIN L (low

speed fan) and VENTMIN H

(high speed fan) set

2.8 V

2 to 10 Vdc

or

100 to 9990 cfm

increment by 10

Displays only if a CO

2

sensor is connected. Used for Va (ventilation min

cfm) setpoint. Displays 2 to 10 V if <3 sensors (RA, OA and MA). Va is

only set if DCV is used. This is the ventilation for less than maximum

occupancy of the space. In AUTO mode dampers controlled by CFM.

VENTMIN L

3.7 V

VENTMIN H

2.8 V

ERV OAT SP

32

_

F

0 to 50

_

F;

increment by 1

Only when AUX1 O = ERV

EXH1 SET With 2---speed

fan units Exh1 L (low speed

fan) and Exh1 H (high

speed fan) settings are

required

50%

0 to 100%;

increment by 1

Setpoint for OA damper position when exhaust fan 1 is powered by the

economizer.

Exh1 L

65%

Exh1 H

50%

EXH2 SET With 2---speed

fan units Exh2 L (low speed

fan) and Exh2 H (high

speed fan) settings are

required

75%

0 to 100%;

increment by 1

Setpoint for OA damper position when exhaust fan 2 is powered by the

economizer. Only used when AUX is set to EHX2.

Exh2 L

80%

Exh2 H

75%

SYSTEM

SETUP

INSTALL

01/01/10

Display order = MM/DD/YY

Setting order = DD, MM, then YY.

UNITS DEG

_

F

_

F or

_

C

Sets economizer controller in degrees Fahrenheit or Celsius.

EQUIPMENT

CONV

Conventional or HP

CONV = conventional; HP O/B = Enable Heat Pump mode. Use AUX2 I

for Heat Pump input from thermostat or controller.

AUX2 I

W

SD/W or HP(O)/HP(B)

In CONV mode: SD + Enables configuration of shutdown (default); W =

Informs controller that system is in heating mode. In HP O/B mode:

HP(O) = energize heat pump on Cool (default); HP(B) = energize heat

pump on Heat.

FAN TYPE

2 speed

1 speed/2 speed

Sets the economizer controller for operation of 1 speed or 2 speed

supply fan.

FAN CFM

5000cfm

100 to 15000 cfm;

increment by 100

This is the capacity of the RTU. The value is found in the Project

Submittal documents for the specific RTU.

AUX OUT

NONE

NONE

ERV

EXH2

SYS

S

NONE = not configured (output is not used)

S

ERV = Energy Recovery Ventilator

d

S

EXH2 = second damper position relay closure for second exhaust fan

S

SYS = use output as an alarm signal

OCC

INPUT

INPUT or ALWAYS

When using a setback thermostat with occupancy out (24 Vac), the 24

Vac is input “INPUT” to the OCC terminal. If no occupancy output from

the thermostat then change program to “ALWAYS” OR ad a jumper from

terminal R to OCC terminal.

LLECO

N

--

01

S

I

Содержание EconoMiser X

Страница 1: ...1 Clearing Alarms 11 SAFETY CONSIDERATIONS Improper installation adjustment alteration service maintenance or use can cause explosion fire electrical shock or other conditions which may cause personal...

Страница 2: ...Nomenclature In addition to criteria in Table 1 all units equipped with a factory installed EconoMi er X display a 6 in the 14th position of the model number indicating the low leak economizer control...

Страница 3: ...ge parameter and configuration settings Using the Keypad with Menus To use the keypad when working with menus S Press the Up arrow button to move to the previous menu S Press the Down arrow button to...

Страница 4: ...Displays if not connected short or out of range DA TEMP _ _ __F 0 to 140_F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ __F if sensor sends...

Страница 5: ...t if DCV is used This is the ventilation for less than maximum occupancy of the space In AUTO mode dampers controlled by CFM VENTMIN L 3 7 V VENTMIN H 2 8 V ERV OAT SP 32_F 0 to 50_F increment by 1 On...

Страница 6: ...libration temperature sensor RA H CAL 0 RH 10 RH Allows for the operator to adjust for an out of calibration humidity sensor DA T CAL 0 0_F 2 5_F Allows for the operator to adjust for an out of calibr...

Страница 7: ...abel Type Description Top Left Terminal Block MAT MAT 20k NTC and COM Mixed Air Temperature Sensor polarity insensitive connection OAT OAT 20k NTC and COM Outdoor Air Temperature Sensor polarity insen...

Страница 8: ...he W7220 calculates the enthalpy and dew point using the OA temperature and humidity input from the OA sensor When the OA temperature OA humidity and OA dew point are all below the selected boundary t...

Страница 9: ...Hood Factory Option The outside air hood for factory option economizer is shipped in knock down form and requires field assembly See the base unit Installation Instructions for details on assembling a...

Страница 10: ...outside air temperature When space temperature demand is satisfied thermostat Y1 opens the dampers will return to Minimum Damper position if indoor fan is running or fully closed if fan is off If acc...

Страница 11: ...d start over Under the SYSTEM SETUP menu you can change the setpoints to the factory defaults Will I be able to see the LCD screen when it is in the unit The LCD screen has a backlight that is always...

Страница 12: ...012 Carrier Corp D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 02 12 Manufacturer reserves the right to change at any time specifications and designs without notice and with...

Отзывы: