background image

31

DIAGNOSIS AND SOLUTION (CONT)

High temperature protection of compressor top diagnosis and solution (P2)

Error Code

P2

Malfunction decision conditions

If the sampling voltage is not 5V, the LED displays the failure.

Supposed causes

·

Power supply problems

·

System leakage or block

·

PCB faulty

Troubleshooting

Check the air flow system 

of indoor and outdoor units 

Clear up the air inlet and outlet or the heat 

exchanger of indoor and outdoor units.

Yes

No

Yes

Yes

Power off, then restart the unit 10

minutes later

Check the temperature 

of the compressor 

No

Check refrigerant system

Yes

Check the overload 

protector

Correct the connection.

No

Measure the resistance 

between the two ports of 

the OLP. Is it zero?

Yes

Replace the OLP.

No

Replace the outdoor control PCB.

Yes

Содержание DHMSHAQ09XA1

Страница 1: ...ER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which...

Страница 2: ...L NOT USED INDOOR UNIT DH MS 3 Q DH FAN COIL UNIT MS MODEL VOLTAGE 1 115 1 60 3 208 230 1 60 SYSTEM TYPE Q HEAT PUMP NOMINAL CAPACITY 09 3 4 TON 12 1 TON 18 1 1 2 TONS 24 2 TONS 30 2 1 2 TONS 36 3 TON...

Страница 3: ...2 2 3 3 3 Fins per inch 20 20 20 20 20 18 18 18 Circuits 3 3 3 3 4 7 7 7 Indoor Unit Width in mm 32 87 835 32 87 835 32 87 835 32 87 835 38 98 990 46 69 1186 46 69 1186 46 69 1186 Unit Height in mm 11...

Страница 4: ...343 13 39 343 13 39 343 Width In mm 32 87 835 32 87 835 32 87 835 32 87 835 38 98 990 46 69 1186 46 69 1186 46 69 1186 Depth In mm 7 80 198 7 80 198 7 80 198 7 80 198 8 58 218 10 16 258 10 16 258 10 1...

Страница 5: ...s are line voltage AC power one is communication wiring S and the other is a ground wire Wiring between indoor and outdoor unit is polarity sensitive The use of BX wire is NOT recommended If installed...

Страница 6: ...208 230V Notes 1 Do not use thermostat wire for any connection between indoor and outdoor units 2 All connections between indoor and outdoor units must be as shown The connections are sensitive to po...

Страница 7: ...09 12 115V Table 6 INDOOR UNIT CONTROL BOARD INPUT or OUTPUT VALUE L_IN Power Voltage AC115V CN11 Power Voltage AC115V CN16 Relative to the N terminal voltage DC 24V CN15 Maximum voltage DC5V CN4 Indo...

Страница 8: ...s 09 36 208 230V Table 7 INDOOR UNIT CONTROL BOARD INPUT or OUTPUT VALUE L_IN Power Voltage AC230V CN11 Power Voltage AC230V CN16 Relative to the N terminal voltage DC24V CN15 Maximum voltage DC5V CN4...

Страница 9: ...mps REFRIGERANT LINES IMPORTANT Both refrigerant lines must be insulated separately Table 2 lists the pipe sizes for the indoor unit Refer to the outdoor unit installation instructions for other allow...

Страница 10: ...Fig 9 Manifold Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accuratelymeasuring this vacuum depth The deep...

Страница 11: ...hen there is only one malfunctioning temperature sensor the air conditioner keeps working yet displays the error code in case of any emergency use When there is more than one malfunctioning temperatur...

Страница 12: ...continues to runs the indoor and outdoor motors stop and the indoor unit defrost lamp illuminates and appears Evaporator Coil Temperature Protection Fig 17 Evaporator Coil Temperature Protection When...

Страница 13: ...mpressor delays start up for 1 minute before powering on In other instances the compressor waits three 3 minutes before restarts Refrigerant Leakage Detection With this new technology the display area...

Страница 14: ...aying temperature is the actual value 2 The temperature is _C no matter what kind of remote controller is used 3 T1 T2 T3 T4 T2B display range 25 70 TP display range 20 130 4 Frequency display range 0...

Страница 15: ...r Electrolytic Capacitors HIGH VOLTAGE CAUTION Fig 19 Electrolytic Capacitors For other models please connect discharge resistance approximately 100 40W or a soldering iron plug between the terminals...

Страница 16: ...ge detection H 1 time O F0 Overload current protection H 2 times O F1 Outdoor ambient temperature sensor T4 open circuit or short circuit H 3 times O F2 Condenser coil temperature sensor T3 open circu...

Страница 17: ...allation mistake PCB faulty Troubleshooting Yes Replace the indoor outdoor main PCB Power off then restart the unit 2 minutes later EEPROM A read only memory whose contents can be erased and reprogram...

Страница 18: ...ulty Troubleshooting Measure Vs is it a positive fluctuation Vs represents the voltage S and N of the outdoor unit Red pan S Black pan N Power off then restart the unit 2 minutes later Replace the ind...

Страница 19: ...ing normal the voltage moves alternately between 50V to 50V If the outdoor unit has a malfunction the voltage will move alternately with positive value If the indoor unit has malfunction the voltage w...

Страница 20: ...receive a zero crossing signal feedback for 4 minutes or the zero crossing signal time interval is abnormal Supposed causes Connection mistake PCB faulty Troubleshooting Check if the connections and...

Страница 21: ...the failure Supposed causes Wiring mistake Fan assembly faulty Fan motor faulty PCB faulty Troubleshooting Power off then restart the unit 2 minutes later Shut off the power supply Rotate the fan by h...

Страница 22: ...VOLTAGE 1 Red Vs Vm 140V 190V 2 3 Black GND 0V 4 White Vcc 14 17 5V 5 Yellow Vsp 0 5 6V 6 Blue FG 14 17 5V 2 Outdoor DC Fan Motor control chip is in the outdoor PCB S Power on the unit and check if t...

Страница 23: ...he sampling voltage is lower than 0 06V or higher than 4 94V the LED displays the failure Supposed causes Wiring mistake Sensor faulty PCB faulty Troubleshooting Check the connection between the tempe...

Страница 24: ...n for 4 seconds and this situation occurs 3 times the display area displays EC and the air conditioner will turn off Supposed causes T2 sensor faulty Indoor PCB faulty System problems such as leakage...

Страница 25: ...uses Power supply problems System blockage PCB faulty Wiring mistake Compressor malfunction Troubleshooting Check the power supply Check the connections and wires Stop the unit No Yes No Correct the c...

Страница 26: ...ke IPM malfunction Outdoor fan assembly faulty Compressor malfunction Outdoor PCB faulty Troubleshooting Check the wiring between main the PCB and the compressor Correct the connection or replace the...

Страница 27: ...27 DIAGNOSIS AND SOLUTION CONT Fig 27 P U Fig 28 P V...

Страница 28: ...28 DIAGNOSIS AND SOLUTION CONT Fig 29 P W Fig 30 N U...

Страница 29: ...29 DIAGNOSIS AND SOLUTION CONT Fig 31 N V Fig 32 N W...

Страница 30: ...sed causes Power supply problems System leakage or block PCB faulty Troubleshooting Check the power supply Check the connections and wires Stop the unit No Yes No Correct the connections or replace th...

Страница 31: ...faulty Troubleshooting Check the air flow system of indoor and outdoor units Clear up the air inlet and outlet or the heat exchanger of indoor and outdoor units Yes No Yes Yes Power off then restart t...

Страница 32: ...Wiring mistake IPM malfunction Outdoor fan assembly faulty Compressor malfunction Outdoor PCB faulty Troubleshooting Check the wiring between main PCB and compressor Correct the connection or replace...

Страница 33: ...CB measure the resistance value with a tester Fig 34 Tester Temperature sensors Room temp T1 sensor Indoor coil temp T2 sensor Outdoor coil temp T3 sensor Outdoor ambient temp T4 sensor Compressor dis...

Страница 34: ...71 1 29078 117 243 0 38991 2 28 39 8239 38 100 5 62961 78 172 1 25423 118 244 0 37956 1 30 37 1988 39 102 5 39689 79 174 1 2133 119 246 0 36954 0 32 35 2024 40 104 5 17519 80 176 1 17393 120 248 0 359...

Страница 35: ...84 115 239 2 422 4 25 222 8 36 97 34 32 76 169 7 82 116 241 2 357 3 27 211 4 37 99 32 94 77 171 7 566 117 243 2 294 2 28 200 7 38 100 31 62 78 172 7 321 118 244 2 233 1 30 190 5 39 102 30 36 79 174 7...

Страница 36: ...201 2 125 257 4 39 2 33 91 4 64 147 2 95 203 126 258 8 4 5 40 1 34 93 2 65 149 96 204 8 127 260 6 5 41 35 95 66 150 8 97 206 6 128 262 4 6 42 8 36 96 8 67 152 6 98 208 4 129 264 2 7 44 6 37 98 6 68 1...

Страница 37: ...ANCE VALUE Red Black Several M Red Black Several M P N U N U V V W W Red Indoor AC Fan Motor Measure the resistance value of each winding by using the tester Table 17 Resistance Value POSITION RESISTA...

Страница 38: ...l 1 Pull the bottom side of the panel and release the clips Then remove the front panel 2 Remove the filter and horizontal louver 3 Remove the four screws 4 Remove the cover one screw 5 Lift the panel...

Страница 39: ...2 Pull out the clip toward the left side and open the cover 3 Remove the securing screw and open the box cover 4 Pull out the connectors of the swing motor and the fan motor 5 Remove the securing scr...

Страница 40: ...electrical parts sections 1 and 2 remove the pipe holder at the rear side of the unit 2 Remove the two screws on the evaporator at the base bearing side 3 Remove the two screws on the evaporator at t...

Страница 41: ...an and motor How to remove the fan and motor 1 After removing the evaporator assembly see sections 1 3 remove the three 3 screws securing the cover 2 Remove the screw securing the motor and then pull...

Страница 42: ...BDP D 7310 W Morris St D Indianapolis IN 46231 Edition Date 11 17 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No SG...

Отзывы: