Fan Performance Table - 7 (cont)
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
5000
535
1.06
1.21
592
1.27
1.45
647
1.50
1.71
700
1.75
2.00
753
2.02
2.31
5500
564
1.30
1.49
618
1.53
1.75
669
1.77
2.03
718
2.03
2.32
766
2.29
2.62
6000
596
1.59
1.82
643
1.82
2.09
692
2.07
2.37
738
2.34
2.68
783
2.63
3.01
6500
625
1.92
2.19
671
2.16
2.47
715
2.43
2.78
759
2.70
3.09
801
2.99
3.43
7000
656
2.28
2.61
698
2.54
2.91
740
2.82
3.22
781
3.10
3.55
821
3.40
3.89
7500
686
2.70
3.09
726
2.97
3.40
766
3.26
3.73
804
3.55
4.06
843
3.86
4.42
8000
714
3.15
3.61
753
3.43
3.93
790
3.74
4.28
827
4.04
4.63
864
4.37
5.00
8500
743
3.64
4.17
779
3.94
4.51
815
4.25
4.87
849
4.56
5.22
884
4.89
5.60
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
5000
801
2.30
2.64
849
2.61
2.98
898
2.93
3.36
944
3.28
3.75
989
3.64
4.17
5500
813
2.60
2.97
859
2.90
3.32
904
3.23
3.70
948
3.58
4.10
990
3.94
4.51
6000
827
2.93
3.36
870
3.23
3.70
913
3.57
4.09
955
3.92
4.48
996
4.28
4.90
6500
843
3.30
3.77
884
3.62
4.15
924
3.96
4.53
964
4.30
4.93
1002
4.67
5.34
7000
861
3.72
4.25
900
4.05
4.64
939
4.39
5.02
976
4.74
5.43
1013
5.11
5.85
7500
880
4.19
4.79
917
4.52
5.18
954
4.87
5.57
989
5.22
5.98
1025
5.60
6.41
8000
899
4.69
5.37
935
5.04
5.76
969
5.39
6.17
1004
5.76
6.59
1038
6.14
7.03
8500
919
5.23
5.99
952
5.59
6.40
985
5.96
6.82
1017
6.32
7.24
1051
6.71
7.68
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
5000
535
1.02
1.21
592
1.22
1.45
647
1.44
1.71
700
1.69
2.00
753
1.95
2.31
5500
564
1.25
1.49
618
1.47
1.75
669
1.71
2.02
718
1.96
2.32
766
2.21
2.62
6000
596
1.53
1.82
643
1.76
2.08
692
2.00
2.37
738
2.26
2.68
783
2.53
3.01
6500
625
1.85
2.19
671
2.08
2.47
715
2.34
2.78
759
2.60
3.09
801
2.89
3.43
7000
656
2.20
2.61
698
2.45
2.91
740
2.71
3.22
781
2.99
3.55
821
3.28
3.89
7500
686
2.60
3.09
726
2.87
3.40
766
3.14
3.73
804
3.42
4.06
843
3.72
4.42
8000
714
3.04
3.61
753
3.31
3.93
790
3.60
4.28
827
3.90
4.62
864
4.21
5.00
8500
743
3.51
4.17
779
3.79
4.50
815
4.10
4.86
849
4.40
5.22
884
4.71
5.60
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
5000
801
2.22
2.64
849
2.51
2.98
898
2.83
3.35
944
3.16
3.75
989
3.51
4.17
5500
813
2.50
2.97
859
2.80
3.32
904
3.12
3.70
948
3.45
4.10
990
3.79
4.50
6000
827
2.83
3.35
870
3.12
3.70
913
3.44
4.09
955
3.77
4.48
996
4.13
4.90
6500
843
3.18
3.77
884
3.49
4.15
924
3.81
4.53
964
4.15
4.92
1002
4.50
5.34
7000
861
3.58
4.25
900
3.91
4.64
939
4.23
5.02
976
4.57
5.43
1013
4.92
5.85
7500
880
4.04
4.79
917
4.36
5.18
954
4.69
5.57
989
5.04
5.98
1025
5.40
6.41
8000
899
4.52
5.37
935
4.85
5.76
969
5.20
6.17
1004
5.55
6.59
1038
5.92
7.03
8500
919
5.05
5.99
952
5.39
6.40
985
5.74
6.82
1017
6.10
7.24
1051
6.47
7.68
8. Conversion - Bhp to KWI
Air Flow Rate
(CFM)
Unit - 50TJM - 28 - 23 Tons - 50Hz (Standard Motor) (cont)
Air Flow Rate
(CFM)
Available External Static Pressure (in. wg)
Available External Static Pressure (in. wg)
0.2
0.4
0.4
1.8
Legend:
RPM -
Revolutions Per Minute
Bold, Italics
-
Standard Motor and Drive Package
0.6
0.8
1.0
Unit - 50TJM - 28 - 23 Tons - 50Hz (Standard Motor)
KWI=
Bhp X 0.746
Motor efficiency
Unit - 50TJM - 28 - 23 Tons - 50Hz (High Efficiency Motor)
0.6
0.8
1.0
1.2
1.4
1.6
2.0
0.2
Bold , Italics
-
High Efficiency Motor and Drive Package
Air Flow Rate
(CFM)
Unit - 50TJM - 28 - 23 Tons - 50Hz (High Efficiency Motor) (cont)
1.2
1.4
1.6
1.8
2.0
Air Flow Rate
(CFM)
Available External Static Pressure (in. wg)
Available External Static Pressure (in. wg)
KWI -
Kilo Watts Input to Motor
BHP -
Brake Horsepower Input to Fan
CFM -
Cubic Feet per Minute
Notes:
1. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operatin cfm.
2. Static Pressure (i.e Filters) must be added to external static pressure before entering fan performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters and casing loses.
5. Extensive motor and drive testing on these units ensures that the full brake horsepower and watts range of the motor can be utilized with confidence. Using
your fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
6. Bold data shows the range of air flow rate for unit management system, other rpms require field-supplied drive.
7. Use of field-supplied motor may affect wiring size. Contact your Carrier representative for details.
Page 22
Содержание DesertMaster 50TJM
Страница 13: ...Page 13 Fig 6...
Страница 14: ...Page 14 Fig 7...