Fan Performance Table - 7
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
4000
555
0.93
1.04
622
1.13
1.27
686
1.36
1.52
747
1.59
1.78
804
1.84
2.06
4500
589
1.20
1.34
652
1.42
1.59
711
1.65
1.86
767
1.90
2.14
823
2.17
2.43
5000
624
1.51
1.69
682
1.75
1.96
737
2.01
2.25
790
2.27
2.54
841
2.54
2.85
5500
658
1.87
2.10
711
2.13
2.39
762
2.40
2.69
813
2.68
3.00
861
2.96
3.32
6000
689
2.28
2.56
739
2.55
2.86
788
2.83
3.18
835
3.13
3.51
881
3.43
3.85
6500
721
2.74
3.07
765
3.01
3.38
811
3.31
3.71
855
3.62
4.06
899
3.93
4.41
7000
745
3.20
3.59
788
3.49
3.92
830
3.80
4.26
873
4.12
4.62
914
4.45
4.99
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
4000
859
2.09
2.35
910
2.43
2.72
959
2.62
2.94
1007
2.90
3.25
1052
3.18
3.57
4500
875
2.44
2.73
924
2.72
3.05
971
3.00
3.37
1018
3.29
3.70
1062
3.60
4.04
5000
891
2.83
3.17
939
3.13
3.51
986
3.43
3.85
1030
3.74
4.20
1073
4.06
4.55
5500
909
3.27
3.66
955
3.58
4.01
998
3.89
4.36
1042
4.23
4.74
1083
4.56
5.11
6000
925
3.74
4.20
969
4.07
4.56
1012
4.40
4.94
1054
4.75
5.32
1094
5.10
5.72
6500
942
4.26
4.78
983
4.60
5.15
1024
4.94
5.54
1065
5.30
5.94
1104
5.66
6.35
7000
954
4.79
5.37
994
5.13
5.76
1034
5.49
6.16
1072
5.86
6.57
1110
6.24
7.00
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
4000
555
0.87
1.02
622
1.06
1.25
686
1.27
1.50
747
1.49
1.75
804
1.72
2.03
4500
589
1.12
1.32
652
1.33
1.57
711
1.55
1.83
767
1.79
2.10
823
2.03
2.39
5000
624
1.42
1.67
682
1.64
1.93
737
1.88
2.21
790
2.13
2.50
841
2.39
2.81
5500
658
1.76
2.07
711
2.00
2.35
762
2.25
2.65
813
2.51
2.95
861
2.78
3.27
6000
689
2.14
2.52
739
2.39
2.81
788
2.66
3.12
835
2.94
3.45
881
3.22
3.79
6500
721
2.57
3.02
765
2.83
3.32
811
3.11
3.65
855
3.40
3.99
899
3.69
4.34
7000
745
3.01
3.53
788
3.28
3.86
830
3.57
4.19
873
3.87
4.55
914
4.18
4.91
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
RPM
KWI
BHP
4000
859
1.96
2.31
910
2.28
2.68
959
2.46
2.89
1007
2.72
3.20
1052
2.99
3.51
4500
875
2.29
2.69
924
2.55
3.00
971
2.82
3.31
1018
3.09
3.64
1062
3.38
3.97
5000
891
2.66
3.12
939
2.94
3.45
986
3.22
3.79
1030
3.51
4.13
1073
3.81
4.48
5500
909
3.07
3.60
955
3.36
3.95
998
3.65
4.29
1042
3.97
4.66
1083
4.28
5.03
6000
925
3.51
4.13
969
3.82
4.49
1012
4.13
4.86
1054
4.46
5.24
1094
4.79
5.63
6500
942
4.00
4.71
983
4.31
5.07
1024
4.64
5.45
1065
4.98
5.85
1104
5.32
6.25
7000
954
4.49
5.28
994
4.82
5.66
1034
5.15
6.06
1072
5.50
6.47
1110
5.86
6.88
8. Conversion - Bhp to KWI
Unit - 50TJM - 018 - 15 Tons - 50Hz (Standard Motor)
Air Flow Rate
(CFM)
Available External Static Pressure (in. wg)
Available External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
1.4
1.6
1.8
2.0
Available External Static Pressure (in. wg)
Available External Static Pressure (in. wg)
0.2
Bold, Italics
-
Standard Motor and Drive Package
0.4
0.6
0.8
1.0
1.2
Air Flow Rate
(CFM)
Air Flow Rate
(CFM)
Unit - 50TJM - 018 - 15 Tons - 50Hz (Standard Motor) (cont)
1.2
1.4
1.6
1.8
2.0
Unit - 50TJM - 18 - 15 Tons - 50Hz (High Efficiency Motor)
5. Extensive motor and drive testing on these units ensures that the full brake horsepower and watts range of the motor can be utilized with confidence. Using
your fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
6. Bold data shows the range of air flow rate for unit management system, other rpms require field-supplied drive.
7. Use of field-supplied motor may affect wiring size. Contact your Carrier representative for details.
Air Flow Rate
(CFM)
Unit - 50TJM - 18 - 15 Tons - 50Hz (High Efficiency Motor) (cont)
BHP -
Brake Horsepower Input to Fan
CFM -
Cubic Feet per Minute
Bold , Italics
-
High Efficiency Motor and Drive Package
KWI -
Kilo Watts Input to Motor
RPM -
Revolutions Per Minute
Legend:
Notes:
1. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operatin cfm.
2. Static Pressure (i.e Filters) must be added to external static pressure before entering fan performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters and casing loses.
KWI=
Bhp X 0.746
Motor efficiency
Page 20
Содержание DesertMaster 50TJM
Страница 13: ...Page 13 Fig 6...
Страница 14: ...Page 14 Fig 7...