Attaching Power Exhaust to the Unit
1. Make sure all power exhaust harness are connected as
indicated in the previous steps. See Fig. 6 and 7.
2. Make sure all wiring is secure. Use field-supplied wire
ties if necessary. Be sure that wiring does not interfere
with operation of the HVAC unit, economizer, or power
exhaust.
3. For units with a standard filter panel (i.e., no hinged
door): Install the gasketing (provided) on the back of
power exhaust side mating flanges. (See Fig. 11.)
NOTE: This step does not apply to units with a hinged
door.
Fig. 11 — Gasketing Location Detail
(Standard Filter Panel Only)
4. Lift power exhaust and install over economizer using the
#10 x
3
/
4
in. long screws provided. Make sure wiring har-
nesses are properly secured. (See Fig. 12.)
Fig. 12 — Power Exhaust Installed on Unit
5. Locate the aluminum filter shipped with the economizer.
Open the filter clips under the top hood of the power
exhaust. Slide aluminum filter into the outside air open-
ing of the power exhaust. Filter will slide past filter clips.
Close filter clips, which will lock filter in place.
6. Reinstall the fan shield.
7. Return power to unit and remove lockout tag.
8. Test power exhaust operation by setting the power
exhaust set point on the economizer controller to 0%.
Power exhaust performance is shown in Fig. 13.
9. Adjust the power exhaust set point on the economizer
controller to the desired activation point per unit sche-
matic.
10. For units with a standard filter access panel, reinstall the
unit filter access door.
For units with a hinged access door (Small and Large
Cabinet), install the hinged door seal angle included in
the power exhaust kit using the instructions in this
instruction. Do not proceed unless the sealing angle is
installed. Units with a hinged door that do not have a
sealing angle may not have a watertight seal.
Fig. 13 — Power Exhaust Performance
UNIT CORNER
POST
GASKETING
POWER
EXHAUST
ECONOMI$ER IV
CONTROLLER
ALUMINUM
FILTER
POWER EXHAUST
5000
4000
3000
2000
1000
0
0
0.1
0.2
0.3
0.4
0.5
EXHAUST
AIRFLOW (cfm)
RETURN DUCT STATIC PRESSURE (in wc)
Small Cabinet
Large and
Extra-Large
Cabinet