Carrier CRPWREXH021A01 Скачать руководство пользователя страница 9

9

Attaching Power Exhaust to the Unit

1. Make sure all power exhaust harness are connected as

indicated in the previous steps. See Fig. 6 and 7.

2. Make sure all wiring is secure. Use field-supplied wire

ties if necessary. Be sure that wiring does not interfere
with operation of the HVAC unit, economizer, or power
exhaust.

3. For units with a standard filter panel (i.e., no hinged

door): Install the gasketing (provided) on the back of
power exhaust side mating flanges. (See Fig. 11.)
NOTE: This step does not apply to units with a hinged
door.

Fig. 11 — Gasketing Location Detail

(Standard Filter Panel Only)

4. Lift power exhaust and install over economizer using the

#10 x 

3

/

4

 in. long screws provided. Make sure wiring har-

nesses are properly secured. (See Fig. 12.)

Fig. 12 — Power Exhaust Installed on Unit

5. Locate the aluminum filter shipped with the economizer.

Open the filter clips under the top hood of the power
exhaust. Slide aluminum filter into the outside air open-
ing of the power exhaust. Filter will slide past filter clips.
Close filter clips, which will lock filter in place.

6. Reinstall the fan shield.
7. Return power to unit and remove lockout tag.
8. Test power exhaust operation by setting the power

exhaust set point on the economizer controller to 0%.
Power exhaust performance is shown in Fig. 13.

9. Adjust the power exhaust set point on the economizer

controller to the desired activation point per unit sche-
matic.

10. For units with a standard filter access panel, reinstall the

unit filter access door.
For units with a hinged access door (Small and Large
Cabinet), install the hinged door seal angle included in
the power exhaust kit using the instructions in this
instruction. Do not proceed unless the sealing angle is
installed. Units with a hinged door that do not have a
sealing angle may not have a watertight seal.

Fig. 13 — Power Exhaust Performance

UNIT CORNER
POST

GASKETING

POWER
EXHAUST

ECONOMI$ER IV
CONTROLLER

ALUMINUM
FILTER

POWER EXHAUST

5000

4000

3000

2000

1000

0

0

0.1

0.2

0.3

0.4

0.5

EXHAUST

AIRFLOW (cfm)

RETURN DUCT STATIC PRESSURE (in wc)

Small Cabinet

Large and
Extra-Large
Cabinet

Содержание CRPWREXH021A01

Страница 1: ...cautions that may apply Follow all safety codes including ANSI American National Standards Institute Z223 1 Wear safety glasses and work gloves Use quenching cloth for unbrazing operations Have fire e...

Страница 2: ...installed transformer part no HT01AH859 must be used with 208 230v power exhaust The vertical power exhaust can be used with 3 different types of economizers While the physical installation of the po...

Страница 3: ...nsion harness plug to the power exhaust harness 4 For EconoMi er IV Route the other end of the low volt age extension harness to the EconoMi er IV controller See Fig 4 The harness is connected to the...

Страница 4: ...ig 4 Power Exhaust Harness Installation for EconoMi er IV with W7212 Controller Fig 5 Power Exhaust Harness Installation for EconoMi er X with W7220 Controller COIL FILTERS HVAC UNIT W7212 CONTROLLER...

Страница 5: ...d Wiring 575 V transformer No HT01AH859 is ordered separately from power exhaust Economizer actuator and controller are shipped with the Economizer not with power exhaust Connections from End Switch p...

Страница 6: ...X Field Supplied Wiring Economizer actuator and controller are shipped with the Economi er not with power exhaust Connection from End Switch Plug to the Economi er controller are made by installer If...

Страница 7: ...Do not drill routing holes Be careful not to route the power exhaust harness on top of the indoor coil 9 Wire the end of the high voltage harness extension to the power exhaust power source 10 Field I...

Страница 8: ...ALLED POSITION ROOF HIGH VOLTAGE HARNESS KNOCKOUTS UNIT ROOF CURB HIGH VOLTAGE EXTENSION HARNESS LOW VOLTAGE EXTENSION HARNESS TO PERMIERLINK CONTROLLER PREMIERLINK TERMINAL J8 PWR HS3 EXH RVS CUT FOR...

Страница 9: ...r open ing of the power exhaust Filter will slide past filter clips Close filter clips which will lock filter in place 6 Reinstall the fan shield 7 Return power to unit and remove lockout tag 8 Test p...

Страница 10: ...n the hinged door was removed See Fig 16 8 Close the hinged door and adjust handle if necessary Fig 14 Power Exhaust Installation Fig 15 Install Sealing Angle Fig 16 Install the Hinged Door PremierLin...

Страница 11: ......

Страница 12: ...scontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480206 01 Printed in U S A Form IIK CRPWREXH021 07 Pg 12 8 18 Replaces IIK CR...

Отзывы: