Installing the Hinged Door Angle (Small and
Large Cabinet)
Follow these instructions if the unit has a hinged panel in-
stead of a standard filter panel. Hinged Door Angle CRPE-
CONV003A00 is for small cabinets and CRPE-
CONV004A00 is for large cabinets.
NOTE: A separate hinged door angle kit must be ordered for the
extra-large cabinet.
1. Find the sealing angle and three screws provided in the
power exhaust kit.
2. Attach the sealing angle to the top of the power exhaust
hood using the screws provided. Refer to Fig. 14 and 15.
Note that the gasketing flange will be facing out.
3. If there are NO pre-drilled holes in the Power Exhaust
hood: Lay the hinged panel, insulation side up, on top of
the hood so that the hinge screw holes align with the pre-
drilled screw holes in the sealing angle. (For hoods with
pre-drilled holes, skip to Step 7.)
4. Check the alignment of the hinged door with the side of
the filter opening to be sure it will close properly.
5. Use a pencil to mark the hood where the screw holes will
be.
6. Remove the hinged door and drill four (4)
11
/
64
in. holes
where the marks are.
NOTE: The sealing angle will be in place; use the holes
in it as a guide.
7. Place the door and hinges back on the unit. Screw
through the door hinges and sealing angle into the
flanged top of the hood using the 4 screws set aside when
the hinged door was removed. (See Fig. 16.)
8. Close the hinged door and adjust handle if necessary.
Fig. 14 — Power Exhaust Installation
Fig. 15 — Install Sealing Angle
Fig. 16 — Install the Hinged Door
PremierLink™ — Operational Notes for Testing
Purposes
If the “continuous power exhaust” function is disabled, the
power exhaust fan will operate during EconoMi$er purge cy-
cles when the EconoMi$er damper position is above the con-
figured minimum value. If enabled, the power exhaust fan
will follow the supply fan's operation for PremierLink ver-
sion 1.2 and will follow the occupancy configuration for Pre-
mierLink version 1.3.
The PremierLink “Auxiliary Output” function defines the
specific use of the auxiliary output (HS3/EXH/RVS) for the
power exhaust. The output will be energized or deenergized
by the appropriate algorithm that uses that specific output.
A setting of 1 = Exhaust fan output.
The Power Exhaust set point in the set point table deter-
mines the power exhaust damper “percent open” when the
power exhaust is energized. The damper percentage set point
has a 10% hysteresis.
If “Continuous” in the service configuration table is set to
“enable”, the power exhaust output will energize when occu-
pied (for PremierLink controls version 1.3 and later) and will
be energized when the supply fan relay is on (for versions pri-
or to 1.3).
POWER
EXHAUST
SIDE FLANGES
GASKET
LOCATION
(STANDARD
FILTER PANEL
ONLY)
GASKET LOCATION
GASKETED
FLANGE
SEE
NOTE
SEE
NOTE
SEALING
ANGLE
SCREW ANGLE
TO HOOD (3)
SEALING
ANGLE
HINGED DOOR
POWER EXHAUST
HOOD