background image

3

*Accessory CO

2

 sensors.

†Accessory aspirator boxes required for duct-mounted applications.

**CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2

and 33ZCASPCO2 accessories.

INSTALLATION

Figure  1  shows  component  locations  on  the  EconoMi$er  X

system.

Vertical Installation

These economizers are designed to work in both vertical and

horizontal  applications.  These  instructions  are  for  vertical

installations.

1. Turn off unit power supply and install lockout tag.

2. Prepare the unit for economizer installation: 

 a. For units with 2 position damper installed, remove the

outside  air  hood.  Unplug  the  damper  actuator  and

remove assembly from the unit. 

 b. For  units  with  manual  damper  installed,  remove  the

manual damper and hood.

3. Remove the upper panel and bottom panel (provided with the

HVAC  unit)  on  the  end  of  the  unit  to  expose  the  return

section.  (See  Fig.  2.)  Save  the  screws  for  use  later  when

replacing the panel. The panels can be discarded.

Fig. 1 — 

EconoMi$er X System Component 

Locations

Fig. 2 — 

Upper and Bottom Panel on End of Unit

4. Remove the unit’s left side corner post and left side panel

from the unit to allow for easy economizer installation. (See

Fig. 3.)

5. Install economizer, with shroud attached as shown in Fig. 3,

into the return air section of the unit. Be careful not to pinch

the wires during installation. The bottom of the economizer

will rest on the base of the unit. (See Fig. 4.)

6. Reinstall the left side corner post on to the unit. NOTE: The

corner post will sit behind the economizer shroud flange (see

Fig.  5).  Screw  through  the  corner  post  and  through  the

economizer shroud. (See Fig. 4 and 5.)

Fig. 3 — 

Unit Left Side Panel and Corner Post

 

Fig. 4 — 

Side View

Table 5 — 

 

EconoMi$er X

®

 Sensor Usage

APPLICATION

ECONOMI$ER X

®

 WITH OUTDOOR AIR DRY 

BULB SENSOR

Accessories Required

Outdoor Air Dry 

Bulb

The HH79AH001 outdoor air dry bulb sensor is 

factory installed on the economizer.

Mixed Air 

Sensor

HH79AH001 provided with economizer and 

field-installed in blower compartment.

Single Enthalpy

HH57AC081

Differential Dry 

Bulb or 

Enthalpy

HH57AC081

CO

2

 for DCV 

Control using a 

Wall-Mounted 

CO

2

 Sensor

33ZCSENCO2

OR

CGCDXSEN004A00

CO

2

 for DCV 

Control using a 

Duct-Mounted 

CO

2

 Sensor

33ZCSENCO2 OR

CGCDXSEN004A00*

and

33ZCSENCO2 

OR

CGCDXASP00100†

OR

CRCBDIOX005A00**

Outside Air
Damper

Economizer

Actuator

(This End)

Wiring
Harness

Return Air Damper

Upper End Panel
Shipped On 
Base Unit

Bottom Panel
Shipped On 
Base Unit

Indoor Fan Panel

Unit’s Left
Side Panel

Economizer

Shroud

Left
Corner
Post

EconoMi$er X

EconoMi$er X

Shroud

Screw 
Economizer
To Base

Economizer
Actuator

Содержание CRECOMZR074A01

Страница 1: ...symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are us...

Страница 2: ...nomizer Table 1 Carrier Usage Chart CARRIER MODEL NUMBER ECONOMI ER X PART NUMBER 48 50TC 17 24 CRECOMZR074A00 48 50HC 17 20 48 50LC 14 48 50TCQ 17 24 48 50TC 28 30 CRECOMZR075A00 48 50HC 24 28 48 50L...

Страница 3: ...with shroud attached as shown in Fig 3 into the return air section of the unit Be careful not to pinch the wires during installation The bottom of the economizer will rest on the base of the unit See...

Страница 4: ...crew panel into economizer in two places See Fig 9 Fig 9 End View of Unit 11 Locate the mixed supply air temperature sensor HH79AH001 in the economizer hardware bag A 2 wire sensor harness with spade...

Страница 5: ...Item 1 so that central retainer is perpendicular to hood and each filter support Secure using screws provided i Apply seal strip to top diverters Item 7 j Secure top diverters Item 7 to hood top Item...

Страница 6: ...conomizer shroud flange Screw through the corner post and through the economizer shroud See Fig 5 and 6 7 Insert provided screw through the bottom left rear of the economizer and into the unit base Se...

Страница 7: ...tical applications Reinstall the hinges and damper on the side of the field supplied return duct See page 8 NOTE A relief hood for the horizontal application can be ordered separately part number CRBA...

Страница 8: ...CRBARHOD001A00 hood sides and top together See Fig 25 Caulk the backside of the mating flanges to ensure a watertight seal Install the CRBARHOD001A00 over the relief damper and screw to the return du...

Страница 9: ...d with economizer accessory 7 Inside the control box the brown and orange wires with male terminals from the 50HEHMRAE A10 harness connect to the female terminals on the pink and violet wires from the...

Страница 10: ...10 Fig 28 Typical EconoMi er X Wiring Diagram for 1 and 2 Speed Units...

Страница 11: ...3 Speed Unit Instructions for Complete Diagram NOTES 1 Wires shown in bold are part of 48LCHSRADH A00 harness which is provided with 48 50LC 14 26 size with 3 speed units 2 Harness 50HEHMRAEH A00 whic...

Страница 12: ...8LCHSRADH A00 Harness for 3 Speed Units 48 50LC 14 26 Provided with 3 Speed Units Field Attached to W7220 Controller FIELD ATTACH TO W7220 CONTROLLER CONNECT TO UNIT TERMINAL BOARD CONNECT TO UNIT TER...

Страница 13: ...on to display the first item in the currently displayed menu Press the Menu Up Exit button to exit a menu s item and return to the list of menus USING THE KEYPAD WITH SETTINGS AND PARAMETERS To use th...

Страница 14: ...d the setting under SYSTEM SETUP FAN TYPE must be changed to 1 speed ROOF TOP UNIT Y1O Y2O Y1I Y2I OCC 24 VAC E GND Y1 G W2 W1 Y2 O B OCC W7220 ECONOMIZER CONTROLLER MODULE THERMOSTAT CO2 SENSOR 2 10...

Страница 15: ...40 F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40...

Страница 16: ...led by CFM VENTMIN L 3 7 V N A N A VENTMIN H 2 8 V N A N A ERV OAT SP 32 F 0 to 50F increment by 1 Only when AUX1 O ERV EXH1 SET With 2 speed fan units Exh1 L low speed fan and Exh1 H high speed fan s...

Страница 17: ...f the dampers Resets ventilation based on the RA OA and MA sensor conditions Requires all 3 RA OA and MA sensors MAT T CAL 0 0 F 2 5 F Allows for the operator to adjust for an out of calibration tempe...

Страница 18: ...hen replace sensor if the alarm continues OA SENS T ERR N A N A Outdoor air temperature sensor has failed or become disconnected check wiring then replace if the alarm continues ACT ERROR N A N A Actu...

Страница 19: ...tem as a test that the system is operable SETUP AND CONFIGURATION W7220 Economizer Module Wiring Use Fig 33 and Tables 7 and 8 to locate the wiring terminals for the economizer module NOTE The four te...

Страница 20: ...below the selected boundary the economizer sets the economizing mode to YES economizing is available When all of the OA conditions are above the selected boundary the conditions are not good to econom...

Страница 21: ...12 HH57AC081 Sensor DIP Switch If using differential return enthalpy or temperature option see Table 9 for California Title 24 setting requirements by region ENTHALPY CURVE TEMP DRY BULB F TEMP DEWPOI...

Страница 22: ...until Y2 is closed The economizer control will call for compressor operation Dampers will modulate to maintain SAT at set point concurrent with Compressor 1 operation The Low T Temp setting default 32...

Страница 23: ...inals Temperature sensors are to be wired to the OAT and MAT terminals If my enthalpy sensor drifts in accuracy over time can I re calibrate it The sensor is not able to be re calibrated in the field...

Страница 24: ...t to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480147 01 Printed in U S A Form IIK CRECOMZR74 04 Pg 24 9 21 Replaces...

Отзывы: