Table 6 — 

 Menu Structure (cont) 

See Legend and notes on page 18.

MENU

PARAMETER

PARAMETER 

DEFAULT 

VALUE

PARAMETER RANGE AND 

INCREMENT

NOTES

SETPOINTS

MAT SET

53°F

38°F to 65°F; increment by 1

Setpoint determines where the economizer will modulate the 

OA damper to maintain the mixed air temperature.

LOW T LOCK

32°F

-45°F to 80°F;

increment by 1

Setpoint determines outdoor temperature when the 

mechanical cooling cannot be turned on. Commonly referred 

to as the Compressor lockout.

DRYBLB SET

63°F

48°F to 80°F; increment by 1

Setpoint determines where the economizer will assume 

outdoor air temperature is good for free cooling; e.g.; at 63°F 

unit will economize at 62°F and below and not economize at 

64°F and above. There is a 2°F deadband.

ENTH CURVE

ES3

ES1,ES2,ES3,ES4, or ES5

Enthalpy boundary “curves” for economizing using single 

enthalpy.

DCV SET

1100ppm

500 to 2000ppm; increment 

by 100

Displays only if CO

2

 sensor is connected. Setpoint for Demand 

Control Ventilation of space. Above the setpoint, the OA 

dampers will modulate open to bring in additional OA to 

maintain a space ppm level below the setpoint.

MIN POS

4.4 V

2 to 10 Vdc

Displays ONLY if a CO

2

 sensor is NOT connected.

VENTMAX 

With 2-speed fan units 

VENTMAX L (low speed 

fan) and VENTMAX H 

(high speed fan) settings 

are required

4.4 V

2 to 10 Vdc

or

100 to 9990 cfm; 

increment by 10

Displays only if a CO

2

 sensor is connected. Used for Vbz 

(ventilation max cfm) setpoint. Displays 2 to 10 V if <3 sensors 

(RA,OA, and MA). In AUTO mode dampers controlled by 

CFM.

VENTMAX L

6 V

N/A

N/A

VENTMAX H

4.4 V

N/A

N/A

VENTMIN 

With 2-speed 

fan units VENTMIN L (low 

speed fan) and VENTMIN 

H (high speed fan) set

2.8 V

2 to 10 Vdc or 100 to 9990 

cfm increment by 10

Displays only if a CO

sensor is connected. Used for Ba 

(ventilation min cfm) setpoint. Displays 2 to 10 V if <3 sensors 

(RA, OA, and MA). Va is only set if DCV is used. This is the 

ventilation for less than maximum occupancy of the space. In 

AUTO mode dampers controlled by CFM.

VENTMIN L

3.7 V

N/A

N/A

VENTMIN H

2.8 V

N/A

N/A

ERV OAT SP

32°F

0 to 50F; increment by 1

Only when AUX1 O = ERV

EXH1 SET 

With 2-speed fan units 

Exh1 L (low speed fan) 

and Exh1 H (high speed 

fan) settings are required

50%

0 to 100%;increment by 1

Setpoint for OA damper position when exhaust fan 1 is 

powered by the economizer.

Exh1 L

65%

N/A

N/A

Exh1 H

50%

N/A

N/A

EXH2 SET 

With 2-speed fan units 

Exh2 L (low speed fan) 

and Exh2 H (high speed 

fan) settings are required

75%

0 to 100%; increment by 1

Setpoint for OA damper position when exhaust fan 2 is 

powered by the economizer. Only used when AUX is set to 

EHX2.

Exh2 L

80%

N/A

N/A

Exh2 H

75%

N/A

N/A

SYSTEM SETUP

INSTALL

01/01/10

N/A

Display order = MM/DD/YY

Setting order = DD, MM, then YY.

UNITS DEG

F

F or C

Sets economizer controller in degrees Fahrenheit or Celsius

EQUIPMENT

CONV

Conventional or HP

CONV = conventional; HP O/B = Enable Heat Pump mode. 

Use AUX2 I for Heat Pump input from thermostat or 

controller.

AUX2 I

W

SD/W or HP(O)/HP(B)

In CONV mode: SD + Enables configuration of shutdown 

(default); W = Informs controller that system is in heating 

mode. In HP O/B mode: HP(O) = energize heat pump on Cool 

(default); HP(B) = energize heat pump on heat.

FAN TYPE

2 speed

1 speed/2 speed

Sets the economizer controller for operation of 1 speed or 2 

speed supply fan. (NOTE: for 3 speed units (48/50LC 14-26), 

setpoint is a 2 speed.)

FAN CFM

5000cfm

100 to 15000 cfm; 

increment by 100

This is the capacity of the RTU. The value is found in the 

Project Submittal documents for the specific RTU.

AUX OUT

NONE

NONE

ERV

EXH2

SYS

• NONE = not configured (output is not used)

• ERV = Energy Recovery Ventilator

• EXH2 = second damper position relay closure for second 

exhaust fan

• SYS = use output as an alarm signal

OCC

INPUT

INPUT or ALWAYS

When using a setback thermostat with occupancy out (24 

vac), the 24 vac is input “INPUT” to the OCC terminal. If no 

occupancy output from the thermostat then change program to 

“ALWAYS” OR add a jumper from terminal R to OCC 

terminal.

FACTORY DEFAULT

NO

NO or YES

Resets all set points to factory defaults when set to YES. LCD 

will briefly flash YES and change to NO but all parameters will 

change to the factory default values.

Содержание CRECOMZR074A01

Страница 1: ...symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are us...

Страница 2: ...nomizer Table 1 Carrier Usage Chart CARRIER MODEL NUMBER ECONOMI ER X PART NUMBER 48 50TC 17 24 CRECOMZR074A00 48 50HC 17 20 48 50LC 14 48 50TCQ 17 24 48 50TC 28 30 CRECOMZR075A00 48 50HC 24 28 48 50L...

Страница 3: ...with shroud attached as shown in Fig 3 into the return air section of the unit Be careful not to pinch the wires during installation The bottom of the economizer will rest on the base of the unit See...

Страница 4: ...crew panel into economizer in two places See Fig 9 Fig 9 End View of Unit 11 Locate the mixed supply air temperature sensor HH79AH001 in the economizer hardware bag A 2 wire sensor harness with spade...

Страница 5: ...Item 1 so that central retainer is perpendicular to hood and each filter support Secure using screws provided i Apply seal strip to top diverters Item 7 j Secure top diverters Item 7 to hood top Item...

Страница 6: ...conomizer shroud flange Screw through the corner post and through the economizer shroud See Fig 5 and 6 7 Insert provided screw through the bottom left rear of the economizer and into the unit base Se...

Страница 7: ...tical applications Reinstall the hinges and damper on the side of the field supplied return duct See page 8 NOTE A relief hood for the horizontal application can be ordered separately part number CRBA...

Страница 8: ...CRBARHOD001A00 hood sides and top together See Fig 25 Caulk the backside of the mating flanges to ensure a watertight seal Install the CRBARHOD001A00 over the relief damper and screw to the return du...

Страница 9: ...d with economizer accessory 7 Inside the control box the brown and orange wires with male terminals from the 50HEHMRAE A10 harness connect to the female terminals on the pink and violet wires from the...

Страница 10: ...10 Fig 28 Typical EconoMi er X Wiring Diagram for 1 and 2 Speed Units...

Страница 11: ...3 Speed Unit Instructions for Complete Diagram NOTES 1 Wires shown in bold are part of 48LCHSRADH A00 harness which is provided with 48 50LC 14 26 size with 3 speed units 2 Harness 50HEHMRAEH A00 whic...

Страница 12: ...8LCHSRADH A00 Harness for 3 Speed Units 48 50LC 14 26 Provided with 3 Speed Units Field Attached to W7220 Controller FIELD ATTACH TO W7220 CONTROLLER CONNECT TO UNIT TERMINAL BOARD CONNECT TO UNIT TER...

Страница 13: ...on to display the first item in the currently displayed menu Press the Menu Up Exit button to exit a menu s item and return to the list of menus USING THE KEYPAD WITH SETTINGS AND PARAMETERS To use th...

Страница 14: ...d the setting under SYSTEM SETUP FAN TYPE must be changed to 1 speed ROOF TOP UNIT Y1O Y2O Y1I Y2I OCC 24 VAC E GND Y1 G W2 W1 Y2 O B OCC W7220 ECONOMIZER CONTROLLER MODULE THERMOSTAT CO2 SENSOR 2 10...

Страница 15: ...40 F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40...

Страница 16: ...led by CFM VENTMIN L 3 7 V N A N A VENTMIN H 2 8 V N A N A ERV OAT SP 32 F 0 to 50F increment by 1 Only when AUX1 O ERV EXH1 SET With 2 speed fan units Exh1 L low speed fan and Exh1 H high speed fan s...

Страница 17: ...f the dampers Resets ventilation based on the RA OA and MA sensor conditions Requires all 3 RA OA and MA sensors MAT T CAL 0 0 F 2 5 F Allows for the operator to adjust for an out of calibration tempe...

Страница 18: ...hen replace sensor if the alarm continues OA SENS T ERR N A N A Outdoor air temperature sensor has failed or become disconnected check wiring then replace if the alarm continues ACT ERROR N A N A Actu...

Страница 19: ...tem as a test that the system is operable SETUP AND CONFIGURATION W7220 Economizer Module Wiring Use Fig 33 and Tables 7 and 8 to locate the wiring terminals for the economizer module NOTE The four te...

Страница 20: ...below the selected boundary the economizer sets the economizing mode to YES economizing is available When all of the OA conditions are above the selected boundary the conditions are not good to econom...

Страница 21: ...12 HH57AC081 Sensor DIP Switch If using differential return enthalpy or temperature option see Table 9 for California Title 24 setting requirements by region ENTHALPY CURVE TEMP DRY BULB F TEMP DEWPOI...

Страница 22: ...until Y2 is closed The economizer control will call for compressor operation Dampers will modulate to maintain SAT at set point concurrent with Compressor 1 operation The Low T Temp setting default 32...

Страница 23: ...inals Temperature sensors are to be wired to the OAT and MAT terminals If my enthalpy sensor drifts in accuracy over time can I re calibrate it The sensor is not able to be re calibrated in the field...

Страница 24: ...t to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480147 01 Printed in U S A Form IIK CRECOMZR74 04 Pg 24 9 21 Replaces...

Отзывы: