background image

8

Table 5 

 Menu Structure

a

 (cont)

Menu

Parameter

Parameter

Default

Value

Parameter

Range and Increment

b

Notes

SYSTEM 

SETUP

FACTORY DEFAULT

NO

NO or YES

Resets all set points to factory defaults when set to YES. LCD will 

briefly flash YES and change to NO but all parameters will change to 

the factory default values.

ADVANCED

SETUP

MA LO SET

45

o

F

35 to 55

o

F;

Incremented by 1

o

Temperature to achieve Freeze Protection (close damper and alarm if 

temperature falls below setup value).

FREEZE POS

CLO

CLO or MIN

Damper position when freeze protection is active (closed or MIN POS).

CO2 ZERO

0ppm

0 to 500 ppm;

Increment by 10

CO

2

 ppm level to match CO

2

 sensor start level.

CO2 SPAN

2000ppm

1000 to 3000 ppm;

Increment by 10

CO

2

 ppm span to match CO

2

 sensor.

STG3 DLY

2.0h

0 min, 5 min, 15 min, 

then 15 min intervals. 

Up to 4 h or OFF

Delay after stage 2 cool has been active. Turns on 2

nd

 stage of cooling 

when economizer is 1

st

 stage and mechanical cooling is 2

nd

 stage. 

Allows three stages of cooling, 1 economizer and 2 mechanical. 

OFF = no Stage 3 cooling

SD DMPR POS

CLO

CLO or OPN

Indicates shutdown signal from space thermostat or unitary controller. 

When controller receives 24 Vac input on the SD terminal in conven-

tional mode, the OA damper will open if programmed for OPN and OA 

damper will close if programmed for CLO. All other controls, e.g., fans, 

etc. will shut off.

DCVCAL ENA

MAN

MAN (manual)

AUTO

Turns on the DCV automatic control of the dampers. Resets ventilation 

based on the RA, OA, and MA sensor conditions. Requires all 3 RA, 

OA, and MA sensors.

MAT T CAL

0.0

o

F

+/-2.5

o

F

Allows for the operator to adjust for an out of calibration temperature 

sensor.

OA T CAL

0.0

o

F

+/-2.5

o

F

Allows for the operator to adjust for an out of calibration temperature 

sensor.

OA H CAL

0% RH

+/-10% RH

Allows for operator to adjust for an out of calibration humidity sensor.

RA T CAL

0.0

o

F

+/-2.5

o

F

Allows for the operator to adjust for an out of calibration temperature 

sensor.

RA H CAL

0% RH

+/-10% RH

Allows for operator to adjust for an out of calibration humidity sensor.

DA T CA;

0.0

o

F

+/-2.5

o

F

Allows for the operator to adjust for an out of calibration temperature 

sensor.

CHECKOUT

DAMPER VMIN─HS

n/a

n/a

Positions damper to VMIN position

DAMPER VMAX─HS

n/a

n/a

Positions damper to VMAX position

DAMPER OPEN

n/a

n/a

Position damper to the full open position.

Exhaust fan contacts enable during the DAMPER OPEN test. Make 

sure you pause in the mode to allow exhaust contacts to energize due 

to the delay in the system.

DAMPER CLOSE

n/a

n/a

Positions damper to the fully closed position

CONNECT Y1─O

n/a

n/a

Closes the Y1─O relay (Y1─O)

CONNECT Y2─O

n/a

n/a

Closes the Y2─O relay (Y2─O)

CONNECT AUX

n/a

n/a

Energizes the AUX output. If Aux setting is:

•  NONE ─ not action taken

•  ERV ─ 24 Vac out. Turns on or signals an ERV that the conditions

   are not good for economizing but are for ERV operation.

d

•  SYS ─ 24 Vac out. Issues a system alarm

ALARMS(

_

)

MA T SENS ERR

n/a

n/a

Alarms display only when they are active. The menu title “ALARMS(_)” 

includes the number of active alarms in parenthesis ( ).

CO2 SENS ERR

n/a

n/a

OA T SENS ERR

n/a

n/a

DA ENTHL ERR

n/a

n/a

SYS ALARM

n/a

n/a

When AUX is set to SYS and there is any alarm (e.g., failed sensors, 

etc.), the AUX terminal has 24 Vac out.

NOTE:

  The alarms listed are examples. Additional alarms display depending on the parameter settings and configuration.

              For example if you do not have a DCV (CO

2

) sensor, then none of the DCV parameters appear. 

a

     Table 2 illustrates the complete hierarchy. Your menu parameters may be different depending on your configuration.

      For example if you do not have a DCV (CO

2

) sensor, then none of the DCV parameters appear

b

     When values are displayed, pressing and holding the ▲ or ▼ button causes the display to automatically increment.

c

     n/a = not applicable

d

     ERV Operation: When in Cooling mode AND the conditions are NOT OK for economizing - the ERV terminal will be energized.

      In the Heating mode the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu.

Содержание CRECOMZR067A00

Страница 1: ...entilation is supported Units displaying 17th position of the model number to indicate that the unit is equipped with the factory installed VFD Variable Frequency Drive option for 2 speed indoor fan control The VFD option is required for units equipped with EconoMi er X For detailed information on the VFD see the Variable Frequency Drive VFD Installation Setup and Troubleshooting Supplement The Ec...

Страница 2: ...y installed outdoor dry bulb temperature sensor with accessory enthalpy sensor HH57AC081 See Fig 1 12 Remove the indoor fan motor access panel See Fig 9 13 The supply air temperature sensor looks like an eyelet terminal with wires running to it The sensor is located on the crimp end and is sealed from moisture Mount the supply air temperature sensor provided to the lower left section of the indoor...

Страница 3: ... 43 19 05 29 5 55 lb CRECOMZR069A00 40 37 22 28 24 48 36 27 80lb CRECOMZR071A00 52 92 27 03 33 41 49 92 98lb NOTE The CRECOMZR071A00 hood has 2 aluminum filters and a hood filter divider that installs between the filters See Fig 5A Fig 5 EconoMi er X Installed in HVAC Unit 3 to 6 Ton Shown Fig 4A Hood for Extra Large Cabinet Hood Filter Divider HVAC Unit Filters Insert Screw in EconoMi er X Flange...

Страница 4: ...xhaust instructions instead 16 Install the EconoMi er X hood over the EconoMi er X Use screws provided See Fig 10 17 The W7220 EconoMi er X controller is shipped mounted to a bracket Install the controller bracket in the top left corner of the unit control box as shown in wiring diagram Fig 8 Screw in place through pre punched holes 18 Connect the plugs coming from the controller as shown in wirin...

Страница 5: ...3 are used to scroll through the menus and menu items select menu items and to change parameter and configuration settings Using the Keypad with Menus To use the keypad when working with menus Press the Up arrow button to move to the previous menu Press the Down arrow button to move to the next menu Press the Enter button to display the first item in the currently displayed menu Press the Menu Up ...

Страница 6: ... sensor Displays _ _ _ o F if not connected short or out of range DA TEMP _ _ _o F 0 to 140o F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ _o F if sensor sends invalid value if not con nected short or out of range OA TEMP _ _ _o F 40 to 140o F Displays measured value of outdoor air temperature Displays _ _ _o F if sensor sends invalid va...

Страница 7: ...a is only set if DCV is used This is the ventilation for less than maximum occupancy of the space In AUTO mode dampers controlled by CFM VENTMIN L 3 7 V VENTMIN H 2 8 V ERV OAT SP 32o F 0 to 50o F increment by 1 Only when AUX1 O ERV EXH1 SET With 2 speed fan units Exh1 L low speed fan and Exh1 H high speed fan settings are required 50 0 to 100 increment by 1 Setpoint for OA damper position when ex...

Страница 8: ...or an out of calibration temperature sensor RA H CAL 0 RH 10 RH Allows for operator to adjust for an out of calibration humidity sensor DA T CA 0 0o F 2 5o F Allows for the operator to adjust for an out of calibration temperature sensor CHECKOUT DAMPER VMIN HS n a n a Positions damper to VMIN position DAMPER VMAX HS n a n a Positions damper to VMAX position DAMPER OPEN n a n a Position damper to t...

Страница 9: ...and Terminal Blocks Time out and Screen Saver When no buttons have been pressed for 10 minutes the LCD displays a screen saver which cycles through the Status items Each Status item displays in turn and cycles to the next item after 5 seconds Label Type Description Top Left Terminal Block MAT MAT 20k NTC and COM Mixed Air Temperature Sensor Polarity insensitive connections OAT OAT 20k NTC and COM ...

Страница 10: ...o F Enthalpy btu lb da Point P1 Point P2 Temp o F Humidity RH Temp o F Humidity RH ES1 80 0 60 0 28 0 80 0 36 8 66 3 80 1 ES2 75 0 57 0 26 0 75 0 39 6 63 3 80 0 ES3 70 0 54 0 24 0 70 0 42 3 59 7 81 4 ES4 65 0 51 0 22 0 65 0 44 8 55 7 84 2 ES5 60 0 48 0 20 0 60 0 46 9 51 3 88 5 HL 86 0 66 0 32 4 86 0 38 9 72 4 80 3 Fig 13 shows the 5 current boundaries There is also a high limit boundary for differ...

Страница 11: ...dampers will be closed When SAT rises to 48o F the damp ers will re open to Minimum Position setting Should 100 outside air not be capable of satisfying the space tempera ture space temperature will rise until Y2 is closed The economizer control will call for compressor operation Dampers will modulate to maintain SAT at 50 to 55o F concurrent with Compressor 1 operation The Low Ambient Lockout The...

Страница 12: ... power returns above 18 Vac Alarms The Economizer module provides alarm messages that display on the 2 line LCD NOTE Upon power up the module waits several seconds before checking for alarms This allows time for all the configured devices e g sensors actuator to become operational If one or more alarms are present and there has been no keypad activity for at least 5 minutes the Alarms menu display...

Страница 13: ...I am using enthalpy sensors Why did the control ask me to input a dry bulb changeover temperature In the even the humidity sensor in the enthalpy sensors fails the backup algorithm in the control is to default to the temperature sensor in the enthalpy sensor In checkout the outdoor damper closes when I command it to open Check the actuator linkage or rotation In the CHECKOUT mode the outdoor dampe...

Страница 14: ...n 7310 W Morris St Indianapolis IN Manufacturer reserves the right to discontinue or change at any time specification or designs without notice and without incurring obligations Catalog No IIK CRECOMZR67 01 Edition Date 5 12 Replaces New ...

Отзывы: