ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential
CARRIER CORPORATION ©2020
Installation and Operation Guide
All rights reserved
46
Technician Settings P35 to P42
P35 – Enable/Disable Freeze protection
“00”
- Disable Freeze protection
“01”
- Enable Freeze protection
Note: If enabled, freeze protection will start when the thermostat is
either ON or OFF and regardless of the current system mode.
P36 – Freeze protection cut-in setpoint
Range: 8...15°C / 46…59°F
Default: 8°C / 46°F
The room ambient temperature which will trigger Heating ON.
P37 – Freeze protection cut-out setpoint
Range: 10...17°C / 50…63°F
Default: 10°C / 50°F
The room ambient temperature which will switch the Heating back
OFF.
P40 – View filter counter (hours) – Read only
Range: 0…999 hours
The filter counter is related to Fan running time.
P41 – Reset filter time
Press the ▲button to reset the filter counter.
The display will change from “00” to “01” and back to “00”.
P42 – Adjust filter alarm delay time counter (hours)
Range: 0…999 hours
Default: 0 hours (0 = Disable)