ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential
CARRIER CORPORATION ©2020
Installation and Operation Guide
All rights reserved
25
FC configurations for 2-pipe systems
Find the configuration you want in the tables below, then find that configuration number (22 through 29) on the
Wiring and
DIP switch/jumper settings
(page 33).
FC Configurations for 2-Pipe systems without humidification/dehumidification
Outputs
Configuration
22
23
24
25
Cool/Heat valve
•
•
Cool/Heat valve PID
•
•
Heat element (2nd stage)
○
○
○
○
Fan VFS
•
•
Fan speeds
1 2 3 1 2 3
Economizer
○
○
○
○
○
○
FC Configurations for 2-Pipe systems with humidification/dehumidification
Outputs
Configuration
26
27
28
29
Cool/Heat valve
•
•
•
Cool/Heat valve PID
•
Heat element (2nd stage)
○
○
○
○
Fan VFS
•
Fan speeds
1 2 3 1 2 3
1 2 3
Economizer
○
○
○
○
○
○
○
Humidifier
•
•
•
•
Dehumidify
Dehumidifier
or
•
Reheat
•
•
•
•
• Yes
○ Option
Содержание ComfortVu Plus TBPL-H
Страница 70: ......