Table 29 — Configuring Demand Limit
NOTE: Heating reset values skipped in this example.
Table 30 — Menu Configuration of 4 to 20 mA Cooling Set Point Control
MODE
KEYPAD
ENTRY
SUB-MODE
KEYPAD
ENTRY
ITEM
DISPLAY
ITEM EXPANSION
COMMENT
CONFIGURATION
DISP
TEST
ON/OFF
Test Display LEDs
UNIT
TYPE
X
Unit Type
OPT1
FLUD
X
Cooler Fluid
OPT2
CTRL
X
Control Method
RSET
CRST
X
Cooling Reset Type
CRT1
XXX.X °F
No Cool Reset Temperature
CRT2
XXX.X °F
Full Cool Reset Temperature
DGRC
XX.X
∆
F
Degrees Cool Reset
DMDC
X
Demand Limit Select
Default: 0
0 = None
1 = Switch
2 = 4 to 20 mA Input
3 = CCN Loadshed
DM20
XXX%
Demand Limit at 20 mA
Default: 100%
Range: 0 to 100
SHNM
XXX
Loadshed Group
Number
Default: 0
Range: 0 to 99
SHDL
XXX%
Loadshed Demand
Delta
Default: 0%
Range: 0 to 60%
SHTM
XXX MIN
Maximum Loadshed
Time
Default: 60 min.
Range: 0 to 120 min.
DLS1
XXX %
Demand Limit
Switch 1
Default: 80%
Range: 0 to 100%
DLS2
XXX%
Demand Limit
Switch 2
Default: 50%
Range: 0 to 100%
MODE
(RED LED)
KEYPAD
ENTRY
SUB-MODE
KEYPAD
ENTRY
ITEM
DISPLAY
ITEM
EXPANSION
COMMENT
CONFIGURATION
DISP
UNIT
OPT1
OPT2
RSET
SLCT
CLSP
0
COOLING SETPOINT SELECT
0
Scrolling Stops
0
Flashing ‘0’
4
Select ‘4’
4
Change Accepted
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER