Table 24B — Example of Configuring Dual Chiller Control (Slave Chiller)
NOTES:
1. Slave is always configured for switch control.
2. Slave CCN Address must be different than Master.
3. Slave CCN Bus Number must be the same as Master.
4. Slave does not require LLBL, LLBD or LLDY to be configured.
5. Yes = Parallel piping configuration. No = Series piping configuration.
Master and Slave chillers must both be configured for the same piping configuration.
SUB-MODE
ITEM
KEYPAD ENTRY
DISPLAY
ITEM EXPANSION
COMMENT
OPT2
OPT2
CTRL
SWITCH
CONTROL METHOD
SEE NOTE 1
SWITCH
CTRL
CTRL
CCNA
CCNA
1
CCN ADDRESS
SCROLLING STOPS
1
VALUE FLASHES
2
SELECT 2 (SEE NOTE 2)
CCNA
2
CCN ADDRESS
CHANGE ACCEPTED
CCNA
CCNB
CCNB
0
CCN BUS NUMBER
DEFAULT 0 (SEE NOTE 3)
CCNB
OPT2
RSET
PROCEED TO SUBMODE RSET
RSET
RSET
CRST
COOLING RESET TYPE
LLEN
LEAD/LAG CHILLER ENABLE
15 ITEMS
LLEN
DSBL
SCROLLING STOPS
DSBL
VALUE FLASHES
ENBL
SELECT ENBL
LLEN
ENBL
LEAD/LAG CHILLER ENABLE
CHANGE ACCEPTED
LLEN
MSSL
MASTER/SLAVE SELECT
MSSL
MAST
SCROLLING STOPS
MAST
VALUE FLASHES
SLVE
SELECT SLAVE
MSSL
SLVE
MASTER/SLAVE SELECT
CHANGE ACCEPTED
MSSL
5 ITEMS
PARA
NO
PARALLEL CONFIGURATION
YES
SELECT YES
PARA
YES
PARALLEL CONFIGURATION
SEE NOTE 5
RSET
SLAVE COMPLETE
ENTER
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ESCAPE