24
Thresholds
This section configures the temperature and time thresholds associated
with the heating and cooling equipment.
Your Carrier thermostat is preconfigured for the most common system
type. The advanced settings and configuration options detailed in this
section are intended for professional installers only. Incorrect
configuration may lead to improper operation and equipment damage.
You must configure the Equipment settings (page 22) before setting the
thresholds. Only the applicable threshold settings will be displayed (i.e. if
no air conditioner is configured, you will not see the options related to air
conditioners).
To configure threshold settings:
From the Home screen, press
MENU
.
Select
Settings
"
Installation Settings
.
Select
Thresholds
.
Configure the temperature threshold settings.
Allow Auto Heat/Cool
Enabling this option allows the user to select auto change- over as a
system mode.
Heat/Cool Min Delta
The minimum difference between the heat mode set temperature and the
cool mode set temperature when the system mode is in auto change- over.
The delta is adjustable from 2 to 10
°
F (1.1 to 5.5
°
C). The default value
is 5
°
F (2.8
°
C).
Compressor Settings
d
Min Cycle Off Time
Configures the compressor off time be-
tween cycles. This ensures the compressor does not short cycle
(which could affect the operating life of the system). This time is
adjustable from 240–900 seconds.