7
ELECTRICAL DATA
UNIT SIZE
--- VOLTAGE,
SERIES
V/PH
OPER
VOLTS*
COMPR
FAN
MCA
MIN
WIRE
SIZE
{
MIN
WIRE
SIZE
{
MAX
LENGTH
(FT)
}
MAX
LENGTH
(FT)
}
MAX
FUSE**
or CKT
BRK
AMPS
MAX
MIN.
LRA
RLA
FLA
60
°
C
75
°
C
60
°
C
75
°
C
18---30
208---230---1
253
197
48.0
9.0
0.5
11.7
14
14
67
64
15
24---30
58.3
13.5
0.75
17.6
14
14
45
43
25
30---30
64.0
12.8
0.75
16.8
14
14
47
45
25
36---30
77.0
14.1
1.4
19.0
12
12
66
63
30
42---30
112.0
17.9
1.1
23.5
12
12
53
51
40
48---30
109.0
19.9
1.4
26.2
10
10
76
73
40
60---30
134.0
26.4
1.2
34.2
8
8
91
86
50
30---50
208/230---3
253
197
58.0
10.1
0.8
13.4
14
14
68
65
20
36---50
71.0
9.2
1.4
12.9
14
14
70
67
20
42---50
88.0
13.5
1.2
18.1
12
12
80
76
30
48---50
83.1
13.6
1.2
18.2
12
12
79
76
30
60---50
110.0
17.7
1.2
23.3
12
12
62
59
40
36---60
460---3
506
414
38.0
5.6
0.7
7.8
14
14
233
222
15
42---60
44.0
6.0
0.5
8.0
14
14
227
216
15
48---60
41.0
6.1
0.6
8.2
14
14
222
211
15
60---60
52.0
7.8
0.6
10.3
14
14
177
168
15
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{
If wire is applied at ambient greater than 30
˚
C (86
˚
F), consult table 310---16 of the NEC (ANSI/NFPA 70). The ampacity of non---metallic---sheathed cable
(NM), trade name ROMEX, shall be that of 60
˚
C (140
˚
F) conditions, per the NEC (ANSI/NFPA 70) Article 336---26. If other than uncoated (no---plated), 60
_
or 75
˚
C (140
_
or 167
˚
C) insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables
of the NEC (ANSI/NFPA 70).
}
Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time---Delay fuse.
FLA
--- Full Load Amps
LRA
--- Locked Rotor Amps
MCA
--- Minimum Circuit Amps
RLA
--- Rated Load Amps
NOTE
: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All
motors/compressors contain internal overload protection.
A--WEIGHTED SOUND POWER (DBA)
UNIT SIZE --- VOLTAGE, SERIES
STANDARD
RATING
TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
125
250
500
1000
2000
4000
8000
18---30
74
50.0
61.5
64.5
66.5
64.0
61.0
54.5
24---30
74
55.5
63.5
67.0
70.0
66.0
63.5
57.0
30---30
30---50
74
52.5
63.0
68.5
70.0
66.5
62.5
56.5
36---30
36---50
36---60
74
57.0
65.0
67.5
69.5
67.5
65.0
60.0
42---30
42---50
42---60
74
55.0
64.0
68.0
68.5
64.5
60.0
54.0
48---30
48---50
48---60
74
52.5
62.5
65.5
69.0
63.5
60.5
56.0
60---30
60---50
60---60
74
54.0
59.0
65.5
67.5
63.5
60.0
55.5
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE---VOLTAGE, SERIES
REQUIRED SUBCOOLING (
_
F)
18---30
8
24---30
13
36---30
36---50
36---60
16
36---30
36---50
36---60
16
42---30
42---50
42---60
10
48---30
48---50
48---60
17
60---30
60---50
60---60
11
24AC
A
3
24AC
A
3
Содержание Comfort 24ACA3
Страница 8: ...8 DIMENSIONS 24ACA3 ...