DETAILED COOLING CAPACITIES
{{
(CONT.)
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES deg F
75
85
95
105
115
125
CFM
EWB
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Capacity
MBtuh†
Total
System
KW**
Total Sens
‡
Total Sens
‡
Total Sens
‡
Total Sens
‡
Total Sens
‡
Total
24ACA360A30 Outdoor Section With CAP**6024A** Indoor Section
1750
72
67.65 35.66
4.15
64.56 34.48
4.58
61.30 33.25
5.06
57.89 31.98
5.58
54.20 30.63
6.15
50.10 29.15
6.77
67
62.07 43.94
4.10
59.24 42.75
4.53
56.25 41.50
5.01
53.12 40.22
5.54
49.74 38.85
6.11
46.03 37.38
6.74
62
57.01 52.17
4.06
54.45 50.95
4.49
51.79 49.66
4.97
49.04 48.27
5.50
46.34 46.34
6.08
43.50 43.50
6.72
57
55.50 55.50
4.04
53.42 53.42
4.48
51.22 51.22
4.96
48.89 48.89
5.50
46.35 46.35
6.08
43.51 43.51
6.72
2000
72
68.69 37.30
4.26
65.46 36.09
4.69
62.07 34.85
5.16
58.54 33.56
5.69
54.71 32.19
6.26
50.48 30.69
6.87
67
63.07 46.60
4.21
60.11 45.38
4.64
57.00 44.12
5.11
53.75 42.82
5.64
50.27 41.45
6.21
46.44 39.94
6.84
62
58.17 55.80
4.16
55.57 54.47
4.59
52.95 52.95
5.07
50.49 50.49
5.61
47.78 47.78
6.19
44.74 44.74
6.82
57
57.57 57.57
4.16
55.35 55.35
4.59
52.99 52.99
5.07
50.50 50.50
5.61
47.78 47.78
6.19
44.74 44.74
6.82
2250
72
69.44 38.83
4.36
66.10 37.62
4.79
62.61 36.36
5.27
58.97 35.06
5.79
55.04 33.67
6.36
50.70 32.16
6.97
67
63.79 49.12
4.31
60.73 47.89
4.74
57.53 46.62
5.21
54.20 45.31
5.74
50.63 43.90
6.31
46.72 42.34
6.93
62
59.18 59.18
4.27
56.90 56.90
4.70
54.41 54.41
5.18
51.77 51.77
5.72
48.91 48.91
6.30
45.70 45.70
6.93
57
59.25 59.25
4.27
56.90 56.90
4.70
54.42 54.42
5.18
51.78 51.78
5.72
48.91 48.91
6.30
45.70 45.70
6.93
Multipliers for Determining the Performance With Other Indoor Sections
Cooling Indoor
Model
Capacity
Power
Furnace Model
*CAP**6024A**
1.00
1.00
CAP**6021A**
0.98
0.98
CNPH*6024A**
0.97
0.97
CNPV*6024A**
0.99
0.99
CSPH*6012A**
0.98
0.98
FE4ANB006
0.99
0.97
FV4BNB006
0.99
0.97
FX4CN(B,F)060
1.01
1.01
FY4ANB060
0.98
0.98
Cooling Indoor
Model
Capacity
Power
Furnace Model
CAP**6021A**
0.97
0.97
58CV(A,X)110---20
CSPH*6012A**
0.97
0.97
58CV(A,X)110---20
CAP**6024A**
0.98
0.98
58CV(A,X)135---22
CNPH*6024A**
0.97
0.96
58CV(A,X)135---22
CNPV*6024A**
0.97
0.97
58CV(A,X)135---22
CSPH*6012A**
0.97
0.95
58CV(A,X)135---22
CAP**6024A**
0.98
0.97
58CV(A,X)155---22
CNPH*6024A**
0.98
0.97
58CV(A,X)155---22
CNPV*6024A**
0.98
0.97
58CV(A,X)155---22
CSPH*6012A**
0.97
0.95
58CV(A,X)155---22
* Tested combination.
{
Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
}
Sensible capacities shown are based on 80
˚
F (27
˚
C) entering air at the indoor coil. For sensible capacities at other than 80
˚
F (27
˚
C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80
˚
F (27
˚
C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air
per degree above 80
˚
F (27
˚
C).
** Total system kW is total of indoor and outdoor unit kilowatts.
{{
Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240---94. If additional tubing length and/or
indoor unit is located above outdoor unit, a slight variation in capacity may occur.
When the required data fall between the published data, interpolation may be performed.
NOTE
: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.