14. Turn ON power to unit.

On power up, depending on the thermostat model being used, the

LCD readout will display either AC for air conditioner model
(1--stage heat/1--stage cool) or HP for heat pump model (2--stage

heat/1--stage cool).

Step 3 — Set Thermostat Configuration

Configuration options enable the installer to configure the
thermostat for a particular installation.
These are not presented to the homeowner and therefore must be
properly set by the installer. Following is a list of the options

available, an explanation of their function, and their factory default
settings. Not all numbers are used in the Base Series because not all

options are available in this series.

Configuration Options -- Summary:

Option 01 -- Equipment type
Option 03 -- Fahrenheit/Centigrade
Option 04 -- Fan (G) on with W output
Option 10 -- Reversing valve
Option 13 -- Room air temperature offset
Option 21 -- Keypad Lockout
Option 26 -- Minimum Cooling Setpoint
Option 27 -- Maximum Heating Setpoint

To Enter The Configuration Mode:

Press and hold the FAN key for about 10 seconds until the display
changes so that only two pairs of digits are showing. The

configuration

number,

now

01,

will

appear

in

the

setpoint/temperature location and the configuration setting will

appear in the clock location. The configuration number (left pair)

will be flashing which means it can be adjusted using the UP and
DOWN keys. To cause the opposite pair to flash (to be adjustable),

press the H/C key. Successive presses of the H/C key alternate
between the configuration number (left) and the configuration

setting (right). To exit the configuration mode, press the

HOLD/END key. If no key is pressed for 3 minutes, the
configuration mode will automatically exit, returning the

thermostat to normal operation.

Configuration Options -- Selection:

Option 01 -- Equipment type

Selections: with HP thermostat: HP, AC, PH, or PC

with AC thermostat: AC or PC

Meanings:
PH or PC selects PTAC units (Packaged Terminal Air

Conditioners) which are used in motel rooms and other rented

spaces. When this option is selected, the display shows only the
setpoint, not the room temperature. Also, the compressor

timeguard is disabled, allowing the compressor to turn on
immediately when a demand is established.
HP or PH controls 1 speed heat pump with 1 stage of aux heat.
AC or PC controls 1 speed air conditioner with one stage of heat.
Note that this option allows a HP thermostat to be converted to

control an AC system.

Option 03 -- Fahrenheit/Centigrade

Selections: F = Fahrenheit — This is default.

C = Centigrade.

Selects temperature display units.

Option 04 -- Fan (G) ON with W output

Selections: OF = G not energized with W — This is default.

ON = G energized with W.

This selection determines whether the fan (G) is to be ON or OFF

when the W (furnace or strip heat) is ON. Furnaces and fan coils
which manage their own blowers do not require a separate G

signal. Some auxiliary heaters require a separate G signal to operate
the blower when W is applied.
This option allows a HP thermostat to control an AC system.

Option 10 -- Reversing valve

Selections: C = reversing valve energized in cooling —This is

default.
H = reversing valve energized in heating — Only

appears in HP systems.

Option 13 -- Room Air Temperature Offset

Selections:

±

5

_

F /3

_

C. Default is 0.

The number of degrees to be added to the displayed temperature to

calibrate or deliberately miscalibrate the measured room
temperature. This option is in

_

F even if Option 3 is set for

_

C.

Option 21 -- Keypad Lockout

Selections: ON, OF — Default is OF.
With OF selected, the keypad cannot be locked. With ON selected
the keypad will be locked and can be unlocked by simultaneously

pressing the UP and DOWN keys for 5 seconds. Once unlocked, it

will relock 2 minutes after the last keypad press. If any key is
pressed and the thermostat is locked, “loc” will be displayed in the

clock digits.

Option 26 -- Minimum Cooling Setpoint

Selections: 50

_

to 90

_

F/10

_

to 32

_

C — Default is 52

_

F/11

_

C.

Sets the lowest cooling setpoint available to the user.

Option 27 -- Maximum Heating Setpoint

Selections: 50

_

to 90

_

F/10

_

to 32

_

C — Default is 88

_

F/31

_

C.

Sets the highest heating setpoint available to the user.

Step 4 — Understand Thermostat Operation

Temperature Display

Thermostat will display room temperature until UP or DOWN
button is pressed. The words SET TEMP appear when these

buttons are pressed and the current setpoint is displayed. If no
buttons are pressed for 5 sec, the display will change back to show

room temperature.

Back lighting

Continuous back--lighting is not available. The backlight will come

on for 10 seconds after any button press. Without AC power and
when the battery is low, the backlight will remain off with button

presses.

Battery Indicator

A battery indication icon on the display shows nothing, half, or
low/no battery condition. If the battery is full or operation is from

AC power, no icon appears. Under battery operation, if the battery
is half full, a half full battery icon appears. As the battery depletes

below half, the icon remains at half, but the 10 second backlight

disappears. When the battery is absent or depleted, the display goes
blank except for an empty battery icon and all outputs are turned

off.

Timeguard Timer

A 5--minute timeguard is built into the thermostat immediately
upon power up, and any time the compressor turns off. The

compressor will not turn on until the timeguard has expired. The
timeguard affects only compressor operation. Pressing UP and

FAN buttons simultaneously will override the timeguard for 1

cycle. If PTAC operation (PH or PC) is selected under Option 1,
the timeguard timer is eliminated.

Cycle Timer

In normal heating and cooling operation the thermostat will not

allow more than 4 equipment cycles per hour (or 1 cycle every 15
minutes). Both the Y and W outputs have a 15--minute timer that

starts counting down when the output is turned on, (e.g., if Y

output is turned on for 9 minutes and then satisfies, it cannot turn
back on for another 6 minutes regardless of demand). However,

TB

--

PA

C

/TB

--

PH

P

Содержание BASE SERIES PROGRAMMABLE THERMOSTATS TB-PAC

Страница 1: ...identifies the most serious hazards which will result in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation INTRODUCTION ...

Страница 2: ...re is disconnected record wire color and terminal marking d Discard or recycle old thermostat ENVIRONMENTAL HAZARD Failure to follow this caution may result in environmental damage Mercury is a hazardous waste and may be found in the old thermostat Federal regulations require that Mercury be disposed of properly CAUTION 3 Separate front and back plastic assembly of thermostat 4 Route thermostat wi...

Страница 3: ...a separate G signal to operate the blower when W is applied This option allows a HP thermostat to control an AC system Option 10 Reversing valve Selections C reversing valve energized in cooling This is default H reversing valve energized in heating Only appears in HP systems Option 13 Room Air Temperature Offset Selections 5_F 3_C Default is 0 The number of degrees to be added to the displayed te...

Страница 4: ...art continuous fan operation FAN ON icon will turn on 2 Press FAN button again This will stop continuous fan oper ation FAN ON icon will turn off Heating Operation 1 Press H C button until HEAT is displayed 2 Press UP button until LCD readout reads 3_F 2_C above room temperature Press UP and FAN buttons simultan eously to defeat timers Heating system should begin to op erate immediately 3 For HP t...

Страница 5: ...m Temperature The large display reads room temperature until a button is pressed 4 To Adjust the Setpoint In normal operation the large display shows room temper ature At the first press of the UP or DOWN button the large display shows the current setpoint and the SET TEMP icon is turned on Further presses of the UP or DOWN but ton adjust the setpoint upward or downward Five seconds after the last...

Страница 6: ...er your programmed comfort schedule Method 2 Temporary Override At the first press of the UP or DOWN button the current temperature setting will appear on the display Pressing the UP or DOWN button again will temporarily change the setpoint as needed At the next programmed time the programmed comfort schedule will resume CHANGING BATTERIES In some situations two AA batteries are the power source f...

Страница 7: ...d is transferable only to the extent and as stated in the Warranty Conditions and below The warranty period in years depending on the part and the claimant is as shown in the chart below Limited Warranty Years Series Item Original Owner Subsequent Owner Infinity User Interface Smart Sensor 10 or 5 10 or 5 Zoning Board 10 or 5 10 or 5 Network Interface 10 or 5 10 or 5 Remote Access 10 or 5 10 or 5 ...

Страница 8: ... AN IMPLIED WARRANTY OR CONDITION LASTS SO THE ABOVE MAY NOT APPLY TO YOU THE EXPRESS WARRANTIES MADE IN THIS WARRANTY ARE EXCLUSIVE AND MAY NOT BE ALTERED ENLARGED OR CHANGED BY ANY DISTRIBUTOR DEALER OR OTHER PERSON WHATSOEVER THIS WARRANTY DOES NOT COVER 1 Labor or other costs incurred for diagnosing repairing removing installing shipping servicing or handling of either defective parts or repla...

Отзывы: