Table 14 — Troubleshooting (cont)
LEGEND
FAULT
HEATING
COOLING
POSSIBLE CAUSE
SOLUTION
Only Compressor Runs
X
X
Thermostat wiring
Check G wiring at heat pump. Jumper G and R for fan operation.
X
X
Fan motor relay
Jumper G and R for fan operation. Check for line voltage across BR
contacts.
Check fan power enable relay operation (if present).
X
X
Fan motor
Check for line voltage at motor. Check capacitor.
X
X
Thermostat wiring
Check Y and W wiring at heat pump. Jumper Y and R for compressor
operation in test mode.
Unit Does Not Operate in
Cooling
X
Reversing valve
Set for cooling demand and check 24 VAC on RV coil and at control.
If RV is stuck, run high pressure up by reducing water flow and while
operating engage and disengage RV coil voltage to push valve.
X
Thermostat setup
Check for 'O' RV setup not 'B'.
X
Thermostat wiring
Check O wiring at heat pump. Jumper O and R for RV coil.
Insufficient capacity/
Not cooling or heating
properly
X
X
Dirty filter
Replace or clean.
X
Reduced or no airflow in
heating
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
Too high external static. Check blower Tables 5A-5J.
X
Reduced or no airflow in
cooling
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
Too high external static. Check blower Tables 5A-5J.
X
X
Leaky ductwork
Check supply and return air temperatures at the unit and at distant duct
registers if significantly different, duct leaks are present.
X
X
Low refrigerant charge
Check superheat and subcooling.
X
X
Restricted metering device
Check superheat and subcooling. Replace.
X
Defective reversing valve
Perform RV touch test.
X
X
Thermostat improperly
located
Check location and for air drafts behind thermostat.
X
X
Unit undersized
Recheck loads and sizing check sensible cooling load and heat pump
capacity.
X
X
Scaling in water heat
exchanger
Perform Scaling check and clean if necessary.
X
X
Inlet water too hot or cold
Check load, loop sizing, loop backfill, ground moisture.
High Head Pressure
X
Reduced or no airflow in
heating
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
Too high external static. Check blower Tables 5A-5J.
X
Reduced or no water flow in
cooling
Check pump operation or valve operation/setting.
Check water flow adjust to proper flow rate.
X
Inlet water too hot
Check load, loop sizing, loop backfill, ground moisture.
X
Air temperature out of range
in heating
Bring return air temperature within design parameters.
X
Scaling in water heat
exchanger
Perform Scaling check and clean if necessary.
X
X
Unit overcharged
Check superheat and subcooling. Reweigh in charge.
X
X
Non-condensables in
system
Vacuum system and reweigh in charge.
X
X
Restricted metering device
Check superheat and subcooling. Replace.
Low Suction Pressure
X
Reduced water flow in
heating
Check pump operation or water valve operation/setting.
Plugged strainer or filter. Clean or replace.
Check water flow adjust to proper flow rate.
X
Water temperature out of
range
Bring water temperature within design parameters.
X
Reduced airflow in cooling
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
Too high external static. Check blower Tables 5A-5J.
X
Air temperature out of range Too much cold vent air. Bring entering air temperature within design
parameters.
X
X
Insufficient charge
Check for refrigerant leaks.
Low discharge air
temperature in heating
X
Too high airflow
Check blower Tables 5A-5J.
X
Poor performance
See 'Insufficient Capacity'.
High humidity
X
Too high airflow
Check blower Tables 5A-5J.
X
Unit oversized
Recheck loads and sizing check sensible cooling load and heat pump
capacity.
FP
—
Freeze Protection
LP/LOC —
Low Pressure/Loss of Charge
HP
—
High Pressure
RV
—
Reversing Valve
LED —
Light Emitting Diode
Содержание AQUAZONE VQL
Страница 15: ...15 AQUAZONE THERMOSTAT Fig 8A 50HQL072 120 and 50VQL160 With Complete C Controls Typical ...
Страница 16: ...16 AQUAZONE THERMOSTAT Fig 8B 50HQL072 120 and 50VQL160 with Deluxe D Controls Typical ...
Страница 17: ...17 AQUAZONE THERMOSTAT Fig 9A 50VQL080 120 with Complete C Controls Typical ...
Страница 18: ...18 AQUAZONE THERMOSTAT Fig 9B 50VQL080 120 with Deluxe D Controls Typical ...
Страница 19: ...19 AQUAZONE THERMOSTAT Fig 10A 50VQL200 300 with Complete C Controls Typical ...
Страница 20: ...20 AQUAZONE THERMOSTAT Fig 10B 50VQL200 300 with Deluxe D Controls Typical ...