Table 4A — Electrical Data — 50HQL072-120 Units
LEGEND
*Time-delay fuse or HACR circuit breaker.
Table 4B — Electrical Data — 50VQL080-300 Units
LEGEND
*Time-delay fuse or HACR circuit breaker.
NOTE: Contact factory for electrical data with optional oversize blower motor.
UNIT
50HQL
VOLTAGE
(3 Ph — 60 Hz)
VOLTAGE
RANGE
BLOWER MOTOR
FACTORY INSTALLED
OPTION
COMPRESSOR
FAN
MOTOR
TOTAL
FLA
MCA
MOCP*
Min
Max
Qty
RLA
LRA
HP
FLA
072
208/230
187
253
Standard
2
10.4
65.5
1.5
5.0
25.8
28.4
35
Large
2
10.4
65.5
2.0
6.2
27.0
29.6
40
460
414
506
Standard
2
4.9
33.0
1.5
2.4
12.2
13.4
15
Large
2
4.9
33.0
2.0
3.1
12.9
14.1
15
096
208/230
187
253
Standard
2
14.3
91.0
2.0
6.5
35.1
38.7
50
Large
2
14.3
91.0
3.0
8.8
37.4
41.0
50
460
414
506
Standard
2
7.2
46.0
2.0
3.1
17.5
19.3
25
Large
2
7.2
46.0
3.0
4.2
18.6
20.4
25
575
518
633
Standard
2
5.7
37.0
2.0
2.8
14.2
15.6
20
Large
2
5.7
37.0
3.0
3.4
14.8
16.2
20
120
208/230
187
253
Standard
2
19.3
123.0
2.0
6.5
45.1
49.9
60
Large
2
19.3
123.0
3.0
8.8
47.4
52.2
70
460
414
506
Standard
2
7.5
49.5
2.0
3.1
18.1
20.0
25
Large
2
7.5
49.5
3.0
4.2
19.2
21.1
25
575
518
633
Standard
2
6.4
40.0
2.0
2.8
15.6
17.2
20
Large
2
6.4
40.0
3.0
3.4
16.2
17.8
20
FLA
—
Full Load Amps
HACR
—
Heating, Air Conditioning, and Refrigeration
LRA
—
Locked Rotor Amps
MCA
—
Minimum Circuit Amps
MOCP —
Minimum Over Current Protection
RLA
—
Rated Load Amps
UNIT
50VQL
VOLTAGE
(3 Ph - 60 Hz)
VOLTAGE RANGE
BLOWER MOTOR
FACTORY-INSTALLED
OPTION
COMPRESSOR
FAN MOTOR
TOTAL
FLA
MCA
MOCP*
Min
Max
Qty
RLA
LRA
Qty
HP
FLA
080
208-230
197
253
Standard
1
20.7
156
1
1.5
5.0
25.7
30.9
50
Large
1
20.7
156
1
2.0
6.2
26.9
32.1
50
460
414
506
Standard
1
10.0
75
1
1.5
2.4
12.4
14.9
20
Large
1
10.0
75
1
2.0
3.1
13.1
15.6
25
575
518
633
Standard
1
8.2
54
1
1.5
1.9
10.1
12.1
20
Large
1
8.2
54
1
2.0
2.3
10.5
12.5
20
100
208-230
197
253
Standard
1
32.1
195
1
1.5
5.8
37.9
45.9
70
Large
1
32.1
195
1
2.0
6.2
38.3
46.3
70
460
414
506
Standard
1
16.4
95
1
1.5
2.4
18.8
22.9
35
Large
1
16.4
95
1
2.0
3.1
19.5
23.6
40
575
518
633
Standard
1
12.0
80
1
1.5
1.9
13.9
16.9
25
Large
1
12.0
80
1
2.0
2.3
14.3
17.3
25
120
208-230
197
253
Standard
1
33.6
225
1
2.0
6.2
39.8
48.2
80
Large
1
33.6
225
1
3.0
8.4
42.0
50.4
80
460
414
506
Standard
1
17.3
114
1
2.0
3.1
20.4
24.5
40
Large
1
17.3
114
1
3.0
4.2
21.5
25.8
40
575
518
633
Standard
1
13.5
80
1
2.0
2.3
15.8
19.2
30
Large
1
13.5
80
1
3.0
3.4
16.9
20.3
30
160
208-230
197
253
Standard
2
20.7
156
1
3.0
8.4
49.8
55.0
70
460
414
506
Standard
2
10.0
74
1
3.0
4.2
24.2
26.7
35
575
518
633
Standard
2
8.2
54
1
3.0
3.4
19.8
21.9
30
200
208-230
197
253
Standard
2
32.1
195
2
1.5
5.0
74.2
75.8
110
Large
2
32.1
195
2
2.0
6.2
76.6
84.6
110
460
414
506
Standard
2
16.4
95
2
1.5
2.4
37.6
41.7
50
Large
2
16.4
95
2
2.0
3.1
39.0
43.1
50
575
518
633
Standard
2
12.0
80
2
1.5
1.9
27.8
30.8
40
Large
2
12.0
80
2
2.0
2.3
28.6
31.6
40
240
208-230
197
253
Standard
2
33.6
225
2
2.0
6.2
79.6
88.0
110
Large
2
33.6
225
2
3.0
8.4
84.0
92.4
125
460
414
506
Standard
2
17.3
114
2
2.0
3.1
40.8
45.1
60
Large
2
17.3
114
2
3.0
4.2
43.0
47.3
60
575
518
633
Standard
2
13.5
80
2
2.0
2.3
31.6
35.0
45
Large
2
13.5
80
2
3.0
3.4
33.8
37.2
50
300
208-230
197
253
Standard
2
47.1
245
2
3.0
8.4
111.0
122.8
150
460
414
506
Standard
2
19.6
125
2
3.0
4.2
47.6
52.5
70
575
518
633
Standard
2
15.8
100
2
3.0
3.4
38.4
42.4
50
FLA
—
Full Load Amps
HACR —
Heating, Air Conditioning, and Refrigeration
LRA
—
Locked Rotor Amps
MCA
—
Minimum Circuit Amps
MOCP —
Minimum Over Current Protection
RLA
—
Rated Load Amps
Содержание AQUAZONE VQL
Страница 15: ...15 AQUAZONE THERMOSTAT Fig 8A 50HQL072 120 and 50VQL160 With Complete C Controls Typical ...
Страница 16: ...16 AQUAZONE THERMOSTAT Fig 8B 50HQL072 120 and 50VQL160 with Deluxe D Controls Typical ...
Страница 17: ...17 AQUAZONE THERMOSTAT Fig 9A 50VQL080 120 with Complete C Controls Typical ...
Страница 18: ...18 AQUAZONE THERMOSTAT Fig 9B 50VQL080 120 with Deluxe D Controls Typical ...
Страница 19: ...19 AQUAZONE THERMOSTAT Fig 10A 50VQL200 300 with Complete C Controls Typical ...
Страница 20: ...20 AQUAZONE THERMOSTAT Fig 10B 50VQL200 300 with Deluxe D Controls Typical ...